Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.4 LAccepted-AOC | ₹29.4 L Quoted ₹30.2 L | L1 | Accepted-AOC L1 |
| 2 | L2₹37.4 L+₹7.2 L (23.8%)Rejected-AOC 37 222 BUNDU KATRA AGRA UP | AGRA | UP | ₹37.4 L+₹7.2 L (23.8%) | L2 | Rejected-AOC L2 |
| 3 | L3₹38.9 L+₹8.7 L (28.8%)Rejected-AOC | ₹38.9 L+₹8.7 L (28.8%) | L3 | Rejected-AOC L3 |
| 4 | L4₹46.5 L+₹16.3 L (53.9%)Rejected-AOC | ₹46.5 L+₹16.3 L (53.9%) | L4 | Rejected-AOC L4 |
| 5 | L5₹49.6 L+₹19.4 L (64.2%)Rejected-AOC | ₹49.6 L+₹19.4 L (64.2%) | L5 | Rejected-AOC L5 |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
9 Dec 2021, 6:00 pmClosed
GE Bharatpur
Kanjoli line Bharatpur
Repair to LT external electric supply LT cables, LT OH Line, LT panels and connected works at 39 FAD Mil Stn Bharatpur
2021_MES_487806_1
8102/E8
Open Tender
Civil Works
Item Rate
270 days
GE Bharatpur
As per tender document
6 documents required · 6 mandatory
₹500
GE Bharatpur
₹60,000
Yes
22 Feb 2022
11 Nov 2021
11 Dec 2021
11 Nov 2021
9 Dec 2021
22 Nov 2021
12 Nov 2021 - 17 Nov 2021
Amount
M&L for attending, repair and rectification of external LT electric supply compliants on 1100 Volts grade, under ground / over head system alongwith necessary T & P, safety devices as per site requirement for the following type of complaints complete all as specified and directed:- 1.01 Replacement of wornout jumpers, jointing and tightening with new ACSR conductor. Note:- Single phase or 3 phase system will be considered as one job for payment purpose.
Disconnecting from over head conductor, cutting worn out portion of LT cables of any type and size, carry out repairs including taking out cables from under ground loop line and rejoining the same to restore electric supply. Notes:- (i) LT Jointing kits, Cable protection Pipe if required at site will be measured and paid separately. (ii) Quoted rate is deemed to be inclusive of cutting and removing the Pole coping and inserting the cable along with protection pipes.Note for Item Nos: 1.01 & 1.02 :- (a) The contractor will be alloted complaints at MES complaint cell on daily basis on all working days and sufficient resources will be deployed by him / her for completion of day to day comaplaints within 24 Hrs from the time of reporting. Any delay beyond above mentioned time limit without intimation of sufficient cause, penalties will be recovered twice of the quoted rate for each un-attended complaint. (b) A detailed log of complaints with completion/non-completion remarks from users/MES will be maintained by the contractor and the same will be updated on daily basis in consulatation with Engr-in-Charge or JE E&M as detailed.(c) The contractor will make suitable arrangment for emergency complaints and will notify authorised rep/Engr-in-Charge about extraordinary circumstances for probable non-completion or delay in rectification of complaints beyond stated time limit set for disposal of complaint. In case of any dispute the decision of accepting officer will be final and binding in this regard. (d) The contractor will intimate MES authority well in advance if electric shutdown is required during rectification of complaints. (e) The quoted rate is deemed to be inclusive of transportation and other expenses required for the resource deployment at the complaint site around scattered Military station at Bharatpur. (f) The contractor will maintain location wise record of each spare utilized as per inventry format given by AGE E/M, Bharatpur and the same shall be submitted to E/M store on daily basis.
S&F in replacement of old unserviceable lugs after cutting the worn out /faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugs including crimping with crimping tools in the existing LT cable 3.5 core upto 50 Sqmm including necessary connection complete all as specified and directed.
All as per item No 2 above but aluminium lugs of size 70 to 120 Sq mm.
All as per item No 2 here-in-before but aluminium lugs of size 150 to 185 Sq mm.
All as per item No 2 here-in-before but aluminium lugs of size 240 to 300 Sq mm.
Excavation in trenches, n. exc 1.5 Mtr wide and n. exc 1.5 Mtr in depth for foundation/laying of cable and getting out in soft/loose soil.
Removing of excavated soil to a distance n. Exc 50 Mtr and depositing where directed at a level n. Exc 1.5 Mtr above the starting point
Returning, filling in including spreading, levelling, watering and well ramming in layers n. Exc 25 cm thick.
Supply & spread unwashed dry river sand for sand cushioning and covering the under ground cable in trenches. (Note :- Punning thickness shall be measured.)
M&L for brick protection with sub Class`B` bricks old size laid dry, flat over cable perpendicular across the cable in trenches complete all as directed.
Taking out Unsv U/G cable PVC insulated armoured PVC sheathed / Al. Conductor, LT type of 10 sqmm to 16 sqmm any size.
Taking out Unsv U/G cable PVC insulated armoured PVC sheathed / Al. Conductor, LT type of 35 sqmm to 70 sqmm any size.
Taking out Unsv U/G cable PVC insulated armoured PVC sheathed / Al. Conductor, LT type of 120 sqmm to 185 sqmm any size.
M&L for PCC (1:3:6) type C1 using 20mm grade stone aggregate in foundation including necessary form work complete all as specified.
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate in coping of poles struts, posts etc including necessary form work, finished the exposed surfaces fair and even without using extra cement complete all as specified and directed.
Taking out old unserviciable Pole of any type of size supplying, errecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long) including painting with two coats of aluminium paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide including taking down old unserviceable PCC poles of any type complete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
Supply, laying, testing & commissioning LT XLPE insulated armoured (heavy duty) electric cable with stranded aluminium conductor 1100 volts grade (ISI marked) & laid in trenches/pipes or fixed on pole of the following sizes:- 17.01 185 Sqmm 3.5 core
120 Sqmm 3.5 core
70 Sqmm 3.5 core
35 Sqmm 3.5 core
16 Sqmm 4 core
10 Sqmm 2 core
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections 4 Sqmm service connections, one twin core cable circular
S&F 20 mm dia Unplasticised PVC pipes of pressure rating 10 Kgf/cm2 fixed on pole with MS clamps made out 25 x 3 mm thick MS flat with the size of pole , nut, bolt etc at the interval of 1 meter all as specified and directed
M&L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size
Repair/maintenance, excluding major spares but including regualr maintenance of the Automatic Power factor correction panel capacity up to 120 KVARs and up to12 stages installed at various locations including carrying out complete maintenance/repairs as required of all the sub systems viz. based control panels, feeder pillar, APFC relay, Power capacitor bank, Power contactors, Control wiring, Monitoring CT, MCBs/MCCBs for isolation (with all the accessoires) any breakdown maintenance and replacement of unserviceable parts, refixing of old serviceable parts/new parts if any project completion and trouble shooting responsibility also lies with contractor including following provisions complete all as specified and directed. Notes:- (i) Rate quoted by tenderer is deemed to be inclusive of checking of system, replacement of defective control wiring, small part such as Push button, lugs any auxilary contatct,auto selctor switch etc and necessary servicing repair by authorised rep of company. (iii) The scope of work includes the labour charges required for removing, repairing, refixing, carrying out electrical termination, capacitors bank, APFC relay, power contactor, contol CT, MCBs/MCCB and fixing/installing/testing and commissioning the complete system. (iii) capacitors bank, APFC relay, power contactor, control CT, MCBs/MCCB shall be measured and paid saperatly (iv) All parts required such as capacitor /Contarcor /MCBs & MCCBs shall be paid as supply only
Supply only power factor correction capacitor, 5 KVAR, ultra heavy duty oil filled 440 volts 50 Hz completee all as specified and directed. Make: L&T Cat no:LTBCU or equivalent make as specified in Appx 'B '
All as per item No 22 above but 10 KVAR Capactor Bank.Make: L&T Cat no:LTBCU or equivalent make as specified in Appx 'B '
S&F power contactor heavy duty, 3 pole, 40 Amps with 2 No + 2NC, type ML3 complete all as specified and directed. Make:- L&T / IndoAsian/Standard/HPL.
Trimming/prunning and removing of tree branches or any other forein objects from LT street light pole and clearing the steet light pole from vegitation of any type and size for one span of any length i (ii) The contractor is responsible for provision of Necessary T & P and safety equipments to complete the job.
Supply & fix in repair MCCB 63 Amp, 4 Pole, fixed type breaking capacity 18 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified and directed by Engg-in-Charge.Make : L&T/ABB/Legrand
Supply & fix in repair MCCB 100 Amp, 4 Pole, fixed type breaking capacity 18 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.Make : L&T/ABB/Legrand
Supply & fix in repair MCCB 125 Amp, 4 Pole, fixed type breaking capacity 25 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.Make : L&T/ABB/Legrand
Supply & fix in repair MCCB 160 Amp, 4 Pole,adjustable type breaking capacity 25 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.Make : L&T/ABB/Legrand
Supply & fix in repair MCCB 200 Amp, 4 Pole,adjustable type breaking capacity 36 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.Make : L&T/ABB/Legrand
Supply & fix in repair MCCB 250 Amp, 4 Pole,adjustable type breaking capacity 50 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.Make : L&T/ABB/Legrand
Supply & fix in repair MCCB 400 Amp,4 Pole,adjustable type breaking capacity 50 KA, 415 V - 50 Hz, fixed in existing panel & connecting complete all as specified & directed by Engr in charge.Make : L&T/ABB/Legrand
Taking out old u/s pipe of any size and any type
S & laying galvanised steel tubing light grade (ISI marked) for protection of under ground cable on poles/wallsor under road crossing of size 50mm bore.
S & laying galvanised steel tubing light grade (ISI marked) for protection of under ground cable on poles/walls or under road crossing of size 80mm bore.
Taking out Old unserviciable Earthing of any size and any type,with material and labour for renewal of earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to galvanised GI strip of size 32 x 6 mm by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore galvanised iron medium grade and 40 mm bore galvanised iron light grade for earth strip protection including all excavation earth work in any type of soil, PCC pit in PCC 1:2:4 type B-1 and RCC 1:2:4, type B1 for precast chamber cover 50 mm thick, reinforced with welded steel wire fabric or XPM Jali (weight not less than 4.00 Kg / sqm), with charcoal, salt, funnel complete all as shown in the electrical plate No 3 of SSR part –I and testing on completion.Note:-Quoted rates shall be deemed to include for earth strip with protection pipe up to 7.5 M length.
M&L for cable jointing kit for 1.1 KV grade for straight through joint complete with jointing material and accessaries suitable for 3.5/4 core XLPE armourd aluminium conductor cable of following size.Make:3 M,Denson or equivalent 37.01 70 Sqmm to 120 Sqmm
Taking out Old unserviciable aluminium cable connected from transformer to LT panel of any size/core
Supply, laying and commissioning Single Core HRFR PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables with copper lugs as per site requirement , 1100 Volt IS-694 marked complete all as specified and dircted of following cross sectional area :- 46.01 70 Sqmm, single core cable
95 Sqmm, single core cable
Material and Labour for cleaning of dust particles from inside the LT Panel by air blowers, tightening of loose connections, filling of gaps with sealants, removing of vegetation, surface dressing surrounding the panel, welding of damaged panel doors, fixing of hinges, providing locking arrangements, , painting of panel with two coats synthetic enamel paint of existing colour complete including providing lock all as specified and directed by Engr-in-charge.
Taking out old unserviciable on load change over from existing panel and S&F ON LOAD change over switch 415V 4 pole of capacity 800 Amps. Make:model Fr 4 of L&T or equivalent make specified in Appx B
S&F Air Circuit Breaker 630A capacity Thermal-Magnetic DN1 ,4 pole Breaking Capacity Icu=Ics=Icw (1 sec) 415 V - 50 Hz fixed type with carry out necessary copper / Aluminium bus bar to connection as per existing bus barto make it senciable , fixed in existing panel & connecting complete all as specified & directed by Engr-in-Charge.Make : L&T/ABB/Legrand
PD GUPTA AND COMPANY
M/s Ranaji Construction Co
M/S S.S Traders
krishna Associate
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .