Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 CrAdmitted-Finance | ₹1.6 Cr | L1 | Admitted-Finance |
| 2 | Rejected-Technical | - | - | Rejected-Technical CONDITIONS OF TECHANICAL BIDS NOT FULFILLED |
| Sl No | Description | Qty | Unit | M/s cee kay Traders L1 |
|---|---|---|---|---|
| 1.00STAGE-0 | ||||
| 1.10 | Providing, installation, testing and commissioning of 5000 GPH x 40 meter head raw water HC pump set alongwith mono bloc submersible both with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions)by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces, Cast steel Sluice valve 80mm dia and NRV 80mm dia alongwith by pass arrangement (class 150 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 10mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 16mm2 copper cable upto MCCB-bus bar-voltage stabilizer in three leads approximately 30 meters in length alongwith neutral wire conforming to ISI standards with proper thimbling and insulation material. Job covers providing and fitting of 100 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc. | 2 | Jobs | 4,15,000 ₹8,30,000 Lowest |
| 1.20 | Making connection of delivery pipe of mono bloc pump with suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of bus bar arrangement complete with frame and insulation work on the wall of the pump room(common for mono bloc pump and 5000 GPH x 40 MH pump).Job includes providing, laying and fixing of insulation rubber mats around electro mechanical machinery on the floor of the pump house Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc. | 1 | Job | 70,000 ₹70,000 Lowest |
| 1.30 | Design, fabrication, installation, testing and commissioning of 50 ampere rating, 3 phase, LT control panel cum protection panel cum automatic star delta starter alongwith allied works by way of fabrication of panel with 3 pole Main and delta power contactors of 50A rating 01 no. each and star power contactor of 50 A rating-1no., complete with all protection, safety and control devices / mechanism compatible with the design / rating of the prime mover, of reputed make, conforming to ISI standards. The system should be provided with fault analyzer cum controller unit or equivalent of standard and reputed make. The complete system should be enclosed in MS steel enclosure box of suitable dimensions. The enclosure should be finished with powder coated painting from inside as well as from outer surface of approved colour. Providing / laying of copper conductors of proper rating alongwith insulation material as per site requirement. The enclosure should be front shutter mounted with key locking system having glass window. Digital electronic voltmeter & ampere meter should be provided along with the required current transformer and selector switches. The internal control wiring should be done with flexible PVC LT cable with proper thimbling at each end. The system should trip the motor on power failure and on appearance of an electrical fault mentioned below which may otherwise damage the motor field coils and should not restart automatically until unless the system is reset manually, thus providing automation to the system and protection to the motor .The system / star delta auto starter should not fall into delta if it does not fall into star mode first and should remain de-energised to avoid damage to the motor / machinery and also to the power source / transformer. The system / star delta auto starter should trip off if it does not fall into delta & remains in star mode for more than 10-20 seconds. The system shall provide protection against:-Low voltage below 350 V, High Voltage above 450 V, Single phasing, Reverse phasing, Un Balanced phasing, Dry running, Overloading. In addition the system should have the following audio & visual features for a quick and accurate diagnosis of the appeared fault / status for a speedy rectification of the system-- Separate LED fault / status indicators, LED phase indicators. Isolation by pass system, for fault analysis of system, with a blinking indicator. An audio warning system/Siren which activates only on starter failure to trip the motor on appearance of any electrical fault mentioned above, to warn the operator to switch off the motor manually.3 LED, contactor ‘COIL OK’, indicators, one for each of the contactors / coils. LED star & delta indicators to access the star to delta timing. A tamper proof starting system to avoid manipulations by the motor operator to keep the system in a permanently ON position Testing of panel after making all incoming / outgoing connections on no load and then on full load. Proper chemical earthing of equipment should be done. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc, | 2 | Jobs | 1,25,000 ₹2,50,000 Lowest |
| 1.40 | Providing, carriage, installation, testing and commissioning of 3 phase, 63 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 14 gauge container chamber alongwith allied works. Job includes providing of 63 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 95mm2 from electric pole to 100 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of 16mm2 copper cable from 100 ampere main switch to voltage stabilizer approximately 20 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc. | 1 | Job | 2,50,000 ₹2,50,000 Lowest |
| 1.50 | Providing, installation, testing and commissioning of 5000 GPH x 335 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions)by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces, Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 50mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 70mm2 copper cable upto MCCB-bus bar-voltage stabilizer in three leads approximately 30meters in length alongwith neutral wire conforming to ISI standards with proper thimbling and insulation material. Job covers providing and fitting of 250 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc. | 2 | Jobs | 9,10,000 ₹18,20,000 Lowest |
| 1.60 | Making connection of sump outlet with suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of bus bar arrangement complete with frame and insulation work on the wall of the pump room. Job includes providing, laying and fixing of insulation rubber mats around electro mechanical machinery on the floor of the pump house Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc. | 1 | Job | 70,000 ₹70,000 Lowest |
| 1.70 | Design, fabrication, installation, testing and commissioning of 140 ampere rating, 3 phase, LT control panel cum protection panel cum automatic star delta starter alongwith allied works by way of fabrication of panel with 3 pole Main and delta power contactors of 140A rating 01 no. each and star power contactor of 110A rating-1no., complete with all protection, safety and control devices / mechanism compatible with the design / rating of the prime mover, of reputed make, conforming to ISI standards. The system should be provided with fault analyzer cum controller unit or equivalent of standard and reputed make. The complete system should be enclosed in MS steel enclosure box of suitable dimensions. The enclosure should be finished with powder coated painting from inside as well as from outer surface of approved colour. Providing / laying of copper conductors of proper rating alongwith insulation material as per site requirement. The enclosure should be front shutter mounted with key locking system having glass window. Digital electronic voltmeter & ampere meter should be provided along with the required current transformer and selector switches. The internal control wiring should be done with flexible PVC LT cable with proper thimbling at each end. The system should trip the motor on power failure and on appearance of an electrical fault mentioned below which may otherwise damage the motor field coils and should not restart automatically until unless the system is reset manually, thus providing automation to the system and protection to the motor .The system / star delta auto starter should not fall into delta if it does not fall into star mode first and should remain de-energised to avoid damage to the motor / machinery and also to the power source / transformer. The system / star delta auto starter should trip off if it does not fall into delta & remains in star mode for more than 10-20 seconds. The system shall provide protection against:-Low voltage below 350 V, High Voltage above 450 V, Single phasing, Reverse phasing, Un Balanced phasing, Dry running, Overloading. In addition the system should have the following audio & visual features for a quick and accurate diagnosis of the appeared fault / status for a speedy rectification of the system-- Separate LED fault / status indicators, LED phase indicators. Isolation by pass system, for fault analysis of system, with a blinking indicator. An audio warning system/Siren which activates only on starter failure to trip the motor on appearance of any electrical fault mentioned above, to warn the operator to switch off the motor manually.3 LED, contactor ‘COIL OK’, indicators, one for each of the contactors / coils. LED star & delta indicators to access the star to delta timing. A tamper proof starting system to avoid manipulations by the motor operator to keep the system in a permanently ON position Testing of panel after making all incoming / outgoing connections on no load and then on full load. Proper chemical earthing of equipment should be done. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc, | 2 | Jobs | 2,00,000 ₹4,00,000 Lowest |
| 1.80 | Providing, carriage, installation, testing and commissioning of 3 phase, 150 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 12 gauge container chamber alongwith allied works. Job includes providing of 150 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 240mm2 from electric pole to 300 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of single core copper cable of 70mm2 from 300 ampere main switch to voltage stabilizer and further upto bus bar approximately 40 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc. | 1 | Job | 5,50,000 ₹5,50,000 Lowest |
| 2.00STAGE-1ST | ||||
Tender Value
Refer Docs
EMD Value
₹3.2 L
Closing Date
22 Jan 2024, 3:00 pmClosed
XEN JAL SHAKTI PHE MECHANICAL DIVISION UDHAMPUR
MH MORH
Providing, installation, testing and commissioning of electro-mechanical machinery alongwith allied works at Pinger
2023_PHE_238946_1
ENIT NO. 68-JJM OF 2023-24
Open Tender
Repair and Maintenance Works
Item Rate
120 days
XEN JAL SHAKTI PHE MECHANICAL DIVISION UDHAMPUR
Providing, installation, testing and commissioning of electro-mechanical machinery alongwith allied works at Pinger
8 documents required · 8 mandatory
₹500
XEN JAL SHAKTI PHE MECHANICAL DIVISION UDHAMPUR
₹3.2 L
Yes
28 Feb 2024
4 Dec 2023
23 Jan 2024
4 Dec 2023
22 Jan 2024
4 Dec 2023
Amount
STAGE-0
Providing, installation, testing and commissioning of 5000 GPH x 40 meter head raw water HC pump set alongwith mono bloc submersible both with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions)by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces, Cast steel Sluice valve 80mm dia and NRV 80mm dia alongwith by pass arrangement (class 150 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 10mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 16mm2 copper cable upto MCCB-bus bar-voltage stabilizer in three leads approximately 30 meters in length alongwith neutral wire conforming to ISI standards with proper thimbling and insulation material. Job covers providing and fitting of 100 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of delivery pipe of mono bloc pump with suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of bus bar arrangement complete with frame and insulation work on the wall of the pump room(common for mono bloc pump and 5000 GPH x 40 MH pump).Job includes providing, laying and fixing of insulation rubber mats around electro mechanical machinery on the floor of the pump house Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
Providing, carriage, installation, testing and commissioning of 3 phase, 63 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 14 gauge container chamber alongwith allied works. Job includes providing of 63 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 95mm2 from electric pole to 100 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of 16mm2 copper cable from 100 ampere main switch to voltage stabilizer approximately 20 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc.
Providing, installation, testing and commissioning of 5000 GPH x 335 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions)by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces, Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 50mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 70mm2 copper cable upto MCCB-bus bar-voltage stabilizer in three leads approximately 30meters in length alongwith neutral wire conforming to ISI standards with proper thimbling and insulation material. Job covers providing and fitting of 250 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of sump outlet with suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of bus bar arrangement complete with frame and insulation work on the wall of the pump room. Job includes providing, laying and fixing of insulation rubber mats around electro mechanical machinery on the floor of the pump house Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
Providing, carriage, installation, testing and commissioning of 3 phase, 150 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 12 gauge container chamber alongwith allied works. Job includes providing of 150 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 240mm2 from electric pole to 300 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of single core copper cable of 70mm2 from 300 ampere main switch to voltage stabilizer and further upto bus bar approximately 40 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc.
STAGE-1ST
Providing, installation, testing and commissioning of 5000 GPH x 310 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions) by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces, Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 35mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 50mm2 copper cable upto MCCB-bus bar-voltage stabilizer in three leads approximately 30 meters in length alongwith neutral wire conforming to ISI standards with proper thimbling and insulation material. Job covers providing and fitting of 250 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of sump outlet pipe with suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of bus bar arrangement complete with frame and insulation work on the wall of the pump room. Job includes providing, laying and fixing of insulation rubber mats around electro mechanical machinery on the floor of the pump house Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
Providing, carriage, installation, testing and commissioning of 3 phase, 150 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 12 gauge container chamber alongwith allied works. Job includes providing of 150 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 240mm2 from electric pole to 300 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of 50mm2 copper cable from 300 ampere main switch to voltage stabilizer approximately 20 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc.
STAGE-2ND
Providing, installation, testing and commissioning of 5000 GPH x 300 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions) by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces,Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 35mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 50mm2 copper cable upto MCCB-bus bar in three leads approximately 20 meters in length conforming to ISI standards with proper thimbling and insulation material.Job covers providing and fitting of 250 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of bus bar arrangement complete with frame and insulation work on the wall of the pump room. Job includes providing, laying and fixing of insulation rubber mats around electro mechanical machinery on the floor of the pump house Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
Providing, carriage, installation, testing and commissioning of 3 phase, 100 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 14 gauge container chamber alongwith allied works. Job includes providing of 100 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 240mm2 from electric pole to 300 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of 50mm2 copper cable from 300 ampere main switch to voltage stabilize and further upto bus bar approximately 30 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc.
RETROFITTING OF WSS PINGER (OLD)
STAGE-0
Providing, installation, testing and commissioning of 4000 GPH x 225 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions) by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces, Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 25mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 35mm2 copper cable upto MCCB-bus bar in three leads approximately 20 meters in length ire conforming to ISI standards with proper thimbling and insulation material. Job covers providing and fitting of 160 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of sump outlet pipe with suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
Providing, carriage, installation, testing and commissioning of 3 phase, 63 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 14 gauge container chamber alongwith allied works. Job includes providing of 63 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 120mm2 from electric pole to 200 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of 35mm2 copper cable from 200 ampere main switch to voltage stabilize and further upto bus bar approximately 30 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc.
STAGE-1ST
Providing, installation, testing and commissioning of 4000 GPH x 225 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions) by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces, Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 25mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 35mm2 copper cable upto MCCB-bus bar in three leads approximately 20 meters in length ire conforming to ISI standards with proper thimbling and insulation material. Job covers providing and fitting of 160 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of sump outlet pipe with suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
Providing, carriage, installation, testing and commissioning of 3 phase, 63 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 14 gauge container chamber alongwith allied works. Job includes providing of 63 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 120mm2 from electric pole to 200 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of 35mm2 copper cable from 200 ampere main switch to voltage stabilize and further upto bus bar approximately 30 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc.
STAGE-2ND
Providing, installation, testing and commissioning of 4000 GPH x 225 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions) by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces, Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 25mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 35mm2 copper cable upto MCCB-bus bar in three leads approximately 20 meters in length ire conforming to ISI standards with proper thimbling and insulation material. Job covers providing and fitting of 160 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of sump outlet pipe with suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
Providing, carriage, installation, testing and commissioning of 3 phase, 63 KVA voltage stabilizer copper wound, first quality CRGO silicon steel core, naturally- oil cooled, manually operated, 14 gauge container chamber alongwith allied works. Job includes providing of 63 KVA voltage stabilizer complete with mineral insulating oil, MCCB, change over switch complete with safety and protection devices etc. Job includes providing and fitting of single core armoured Al. cable of 120mm2 from electric pole to 200 ampere main switch in four leads approximately 50 meters length of each lead and further Providing and fitting of 35mm2 copper cable from 200 ampere main switch to voltage stabilize and further upto bus bar approximately 30 meters in length complete with insulation and thimbling. The voltage stabilizer should have 5 upwards steps and 2 downwards steps (or as per the specified voltage range) from the line voltage i.e. it should work from 180V to 400+5%. Proper chemical earthing of the equipment shall be done. Complete Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools and tackles etc.
RETROFITTING OF WSS PINGER (NEW)
STAGE-0
Providing, installation, testing and commissioning of 6000 GPH x 250 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions) by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces,Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 35mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 50mm2 copper cable upto MCCB-bus bar in three leads approximately 20 meters in length conforming to ISI standards with proper thimbling and insulation material.Job covers providing and fitting of 250 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of bus bar arrangement complete with frame and insulation work on the wall of the pump room. Job includes providing, laying and fixing of insulation rubber mats around electro mechanical machinery on the floor of the pump house Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
STAGE-1ST
Providing, installation, testing and commissioning of 6000 GPH x 275 meter head HC pump set with suitable rating prime mover in compliance with the technical conditions and allied works by way of surveying of site, designing of pump machinery and prime mover in conformity with site conditions. Laying of M-20 grade RCC foundation block for each pump of size 6’x3’x4’ (or as per pump-motor base frame dimensions) by using reinforcement steel of 10mm dia. The foundation block as per size of pump set should have additional margin of 6” on all sides. The foundation block may be combined for all the pumps which must includes space on all sides of pump set and space between the pump sets. Providing, fabrication and laying of 80mm dia MS suction pipe line to the pump set of length as per site conditions condition and upto maximum of approximately 6 meters each including 80mm dia MS bends, MS flanges, expanders/reducers / dismantling joints / saddles/ pipe extension pieces, 80mm dia Cast Iron sluice valve-1no., gaskets, nuts, bolts, washers as per site requirement. Providing, fabrication and laying of 80mm dia MS delivery pipe as per site conditions including MS bends, MS flange, expanders/reducers / dismantling joints/ saddles/ pipe extension pieces,Cast steel Sluice valve 80mm dia and NRV 80mm alongwith by pass arrangement (class 300 accompanied with manufacturer’s in house test certificate)gaskets, nuts, bolts, washers. Job includes greasing work, P/F of graphited gland packing and thereafter testing on no load and then on full load and commissioning thereof. Job includes providing / fitting and laying of copper cable 50mm2 from motor to panel in six leads approximately 36 meters for each motor, then p/f and laying 70mm2 copper cable upto MCCB-bus bar in three leads approximately 20 meters in length conforming to ISI standards with proper thimbling and insulation material.Job covers providing and fitting of 250 ampere MCCB of 50KA breaking strength. Proper chemical earthing of the equipment should be done for safety of machinery. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handing equipments etc.
Making connection of suction lines through 100mm dia MS pipe manifold. Making connection of delivery lines with rising main through 100mm dia MS pipe manifold. Job includes providing and fitting of bus bar arrangement complete with frame and insulation work on the wall of the pump room. Job includes providing, laying and fixing of insulation rubber mats around electro mechanical machinery on the floor of the pump house Job includes providing and fitting of overhead MS girder of required size so as to sustain the load of material / equipment / machinery while lifting / shifting of the material / equipments / machinery alongwith chain pulley block (1no.) 3 ton.Job includes providing of maintenance tool kit as per enclosed annexure. Job includes cost of machinery, equipments and material, transportation charges, manual carriage charges, labour charges, loading /unloading charges, hire charges of tools, tackles, and material handling equipment etc.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .