SEES NCTPS-II
OFFICE OF SEES NCTPS-II
Sp. 46NCTPS II ES circle EM I Dn U II Turbine Motor Bearing inspection of HT motor for Boiler Feed Pump MDBFP 12MW 11KV Make Ms BHEL in Unit II and replacement of bearings with a new one if necessary and motor painting
2024_EB_453620_1
CE NCTPS II SEES EM I SPEC NO 46 24to25
Open Tender
Electrical and Maintenance Works
Works
45 days
NCTPS-II
AS PER TENDER SPECIFICATION
2 documents required · 2 mandatory
₹0
₹1,800
Yes
25 Jun 2024
11 Jun 2024
19 Jun 2024
11 Jun 2024
18 Jun 2024
11 Jun 2024
Amount
Charges for dismantling the top cover of 11KV/12KW MDBFP motor. Releasing the terminal cover and detailed inspection, cleaning, repairing, taping and tightness checking of 12MW/11KV MDBFP motor take off leads & CT terminals, bushings, bushing rods and Epoxy seperators and to replace the bushing set if damages found. Assembling the top cover with new gaskets and refixing the terminal cover.
Charges for dismantling the 12KW/11KV MDBFP motor driven end and Non driven end journal bearing assembly for detailed inspection, blue matching the bearing for perfect contact, checking the oil top, side & bottom clearance and refixing the bearings after inspection. If necessary to replace with new bearing with proper inspection at DE or NDE side if any damages found in existing bearings. Bearing will be supplied by TANGEDCO.
Charges for cleaning using emery and applying two coats of painting with Enamel paints for 11KV/12MW MDBFP motor top cover outer & inner side,water pipe line and all other areas, drying and assembling of top cover with new gaskets including paint & thinner charges.
Charges for shifting of 02 Nos. spare bearings with housing from stores to TG floor.
Charges for replacement of 4 Nos. 80 NB rubber bellows that are provided at the left side (2 Nos) and right side (2 Nos.) of the water cooler line beneath the MDBFP motor and bolts & washers to be replaced with new one.
Charges for frabrication & moulding of 4 Nos. 80 NB rubber bellows that are provided at the left side (2 Nos) and right side (2 Nos.) of the water cooler line beneath the MDBFP motor.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .