| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.4 LAdmitted-Finance | ₹13.4 L | L1 | Admitted-Finance |
| 2 | L2₹14.6 LAdmitted-Finance | ₹14.6 L | L2 | Admitted-Finance |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not Qualified |
| Sl No | Description | Qty | Unit | GIRI ELECTRICAL & SONS L1 | SHAH BROTHERS L2 |
|---|---|---|---|---|---|
| 1.00Creation of 2x100 KVA at Stage 1 & Stage 2 under WSS Surranda Thatharka under U T Capex 2025-26 (SASCI) under the Jurisdiction of Electric Division, JPDCL Batote. | |||||
| 1.01 | 100 kVA (11/0.433-0.250KV;50Hz), Aluminium Wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS1180 Part-l; 2014 as per latest upto date
amendment with externally fitted MCCB with cable box and4x4 Mtrs. suitable
cable of ratings. | 2 | No | 2,60,000 ₹5.2 L | 2,20,000 ₹4.4 L |
| 1.02 | Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type | 2 | Set | 8,000 ₹16,000 | 3,000 ₹6,000 |
| 1.03 | 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical | 2 | Set | 8,000 ₹16,000 | 8,000 ₹16,000 |
| 1.04 | 11 kV Horn Gap Fuse Set 3 Phase 200A | 2 | Set | 7,000 ₹14,000 | 3,000 ₹6,000 |
| 1.05 | 185 mm² Single-Core Cable (1ckt),1.1kV Grade, PVC Insulated Stranded Conductor FRLS type | 88 | mtr | 400 ₹35,200 | 300 ₹26,400 |
| 1.06 | 9 Mtr. Long Pole( ST-410 SP33) | 4 | No | 20,000 ₹80,000 | 20,000 ₹80,000 |
| 1.07 | 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm | 6 | No | 200 ₹1,200 | 350 ₹2,100 |
| 1.08 | GI Channel/Angle/Flat of sizes including clamps | 600 | Kg | 60 ₹36,000 | 100 ₹60,000 |
| 1.09 | Galvinized Nuts and Bolts. | 16 | Kg | 50 ₹800 | 100 ₹1,600 |
Tender Value
Refer Docs
EMD Value
₹39,500
Closing Date
18 Feb 2026, 2:00 pmClosed
Executive Engineer, ED JPDCL Batote
Office of Executive Engineer, ED JPDCL Batote
Supply survey erection testing and commissioning including LT HT laying after creation of five 25 KVA substations at Gam Chachihal Digdole Bajimasta and Paristan to provide power to BSNL 4G sites under ED JPDCL Batote
2026_PDD_302715_1
ENIT 41 of 2025-26
Open Tender
Electrical Works
45 days
Ramban Banihal
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
Executive Engineer, ED JPDCL Batote
₹39,500
7 Mar 2026
10 Feb 2026
19 Feb 2026
10 Feb 2026
18 Feb 2026
10 Feb 2026
Cost of Bid Document (DD No/Date/Validity/Amount)
Earnest Money Deposit (No/Date/Validity/Amount)
Validity of Offer (in days)
Registration certificate from Chief Electrical Inspector / relevant issuing authority enclosed (Yes/No)
Previous Executed Orders of work of similar nature along with satisfactory performance certificates enclosed (Yes/No)
Details of Work experiences enclosed in the form of work completion certificate and LOA (No./Dated/Year of works/Amount)
Annual Turnover in the form of Balance Sheet/P&L Statement audited by CA enclosed (Yes/No)
PAN copy enclosed (Yes/No)
Valid Tax Clearance certificate of last quarter enclosed (Yes/No)
Details about financial resources enclosed (Yes/No)
Affidavit for firm not blacklisted as per relevant format enclosed(Yes/No)
Indemnity Bond as per relevant format of SBD enclosed (Yes/No)
TECHNICAL Documents Check List
Description
Whether the material quoted by the Bidders correspond to the relevant I.S./IEC
Whether the material fully correspond to e-NIT specifications (Yes/No)
Whether Type test reports enclosed (Yes/No)
If not, have the deviations been pointed out in relevant Schedule (Yes/No) 5
Relevant Drawings enclosed (Yes/No)
Duly filled and signed GTP enclosed (Yes/No)
Item Rate
Item Description
Creation of 2x100 KVA at Stage 1 & Stage 2 under WSS Surranda Thatharka under U T Capex 2025-26 (SASCI) under the Jurisdiction of Electric Division, JPDCL Batote.
100 kVA (11/0.433-0.250KV;50Hz), Aluminium Wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS1180 Part-l; 2014 as per latest upto date amendment with externally fitted MCCB with cable box and4x4 Mtrs. suitable cable of ratings.
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
185 mm² Single-Core Cable (1ckt),1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
9 Mtr. Long Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
11 KV polymeric composite Pin insulator, 12kv, 5 kn, lightening impulse 75 KV Positive and 80 KV Negative, creepage distance 320mm
Galvanized stay set with 50*8 m stay clamp, guy insulator (2 nos), anchor plate (200*6mm), nuts-bolts, 2 Nos turn buckets, 1.8m long, 1 6 mm diameter solid GS stay rod & 7/15 mm dia GI strandard wire complete.
Wedge connectors/PG Clamps
Danger plates with clamps
Gl Barbed wire for Anti Climbing
3-phase 4 wire Trivector meter with CT
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole
LT Distribution Box for 25 KVA DTR with MCCB for incomer and SFU's for outgoing Circuits.
Painting of sT poles 9 mtr of substation including crossarm, clamps with 1 coat of Red Oxide (Asian/Nerolac make)
Painting of ST poles 9 mtr of substation including cross arm, clamps with 2 coat of Aluminium Paint (Asian/Nerolac make)
Sundry Item like aluminium lugs, jumpers, binding tape.
Laying of HT Line with ACSR Weasel Conductor on ST Poles 9 mtr long at Stage 1 & Stage 2 under WSS Surranda Thatharka under U T Capex 2025-26 (SASCI) under the Jurisdiction of Electric Division, JPDCL Batote.
9 Mtr. Long Pole( ST-410 SP33)
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
30 mm² ACSR Conductor
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvanized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Aluminium Paint
Red Oxide
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Cement bottoming 1:2:4 mix as per REC standards 0.5cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Laying of LT Line on ST Poles 8 mtr long with ACSR Weasel Conductor Stage 1 & Stage 2 under WSS Surranda Thatharka under U T Capex 2025-26 (SASCI) under the Jurisdiction of Electric Division, JPDCL Batote.
8 Mtr. Long Pole(ST-410 SP15)
ACSR Weasel
Shackle Insulator
M Clamp
Galvanized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Aluminium Paint
Red Oxide
Danger Plates
Anti-Climbing Device with Clamps
Cement bottoming 1:2:4 mix as per REC standards 0.45cum /pole
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.21 MB
SBDeNIT41pdf.pdf
Tender Documents • 0.72 MB
BidderAdressFormat.xls
Additional Documents • 0.03 MB
Checklist.xls
Additional Documents • 0.03 MB
BOQ_982507.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid