| Sl No | Description | Qty | Unit | Gee Sab Electricals L2 | AJAY KAPOOR L1 | M/S CLEAR LINE ENGINEERS CONTRACTOR L5 | M/S SURAJ PARTAP SINGH L4 | M/S RATHER CONSTRUCTIONS AND TRADERS L6 | POWER SOLUTIONS L7 | VEENA CONSTRUCTION CO. L3 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00Creation of 25KVA Distribution Substations (Supplying including Transportation , Carriage, Erection, Testing & Commissioning Complete Job) | ||||||||||
| 1.01 | 11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors fully Efficient Energy Level-2 (i.e actual Efficient energy level 3 redesignated as Efficient Energy Level 2 as per amendment no.4 of relevant IS ) , (Aluminium wound) | 9 | No | 73,786 ₹6,64,074 | 93,000 ₹8,37,000 | 73,000 ₹6,57,000 Lowest | 1,10,000 ₹9,90,000 | 1,25,000 ₹11,25,000 | 1,25,400 ₹11,28,600 | 1,02,000 ₹9,18,000 |
| 1.02 | 9 mtr long Pole ST-410, SP33 | 18 | Nos | 14,786 ₹2,66,148 Lowest | 17,750 ₹3,19,500 | 18,500 ₹3,33,000 | 19,900 ₹3,58,200 | 17,000 ₹3,06,000 | 18,500 ₹3,33,000 | 16,000 ₹2,88,000 |
| 1.03 | Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type | 9 | Set | 1,000 ₹9,000 Lowest | 3,000 ₹27,000 | 6,000 ₹54,000 | 2,000 ₹18,000 | 6,000 ₹54,000 | 3,150 ₹28,350 | 4,000 ₹36,000 |
| 1.04 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type | 9 | Set | 5,500 ₹49,500 | 9,000 ₹81,000 | 10,000 ₹90,000 | 6,000 ₹54,000 | 11,000 ₹99,000 | 5,250 ₹47,250 Lowest | 7,500 ₹67,500 |
| 1.05 | 11kV Horn Gap Fuse set 3-phase, 200 Amp | 9 | Set | 3,500 ₹31,500 | 3,000 ₹27,000 Lowest | 6,000 ₹54,000 | 3,000 ₹27,000 Lowest | 5,000 ₹45,000 | 3,150 ₹28,350 | 4,500 ₹40,500 |
| 1.06 | 50sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type | 396 | Mtr | 300 ₹1,18,800 | 115 ₹45,540 | 130 ₹51,480 | 160 ₹63,360 | 120 ₹47,520 | 85 ₹33,660 Lowest | 150 ₹59,400 |
| 1.07 | 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with GI Disc fitting | 27 | No | 300 ₹8,100 | 275 ₹7,425 | 430 ₹11,610 | 250 ₹6,750 | 600 ₹16,200 | 195 ₹5,265 Lowest | 400 ₹10,800 |
| 1.08 | GI Channel/Angle/Flat of different sizes including clamps | 2,250 | Kg | 135 ₹3,03,750 | 120 ₹2,70,000 | 130 ₹2,92,500 | 110 ₹2,47,500 Lowest | 130 ₹2,92,500 | 130 ₹2,92,500 | 135 ₹3,03,750 |
| 1.09 | Galvanised Nuts & Bolts | 72 | Kg | 135 ₹9,720 | 110 ₹7,920 Lowest | 130 ₹9,360 | 110 ₹7,920 Lowest | 150 ₹10,800 | 140 ₹10,080 | 120 ₹8,640 |
Tender Value
₹2.5 Cr
EMD Value
₹5.0 L
Closing Date
8 Sept 2025, 6:00 pmClosed
EXECUTIVE ENGINEER
0FFICE OF THE EXECUTIVE ENGINEER ED REASI
Creation of 25KVA substations along with allied HT LT Lines on 8mtr ST Poles for electrification of un electrified households in Bhomag Arnas Blocks of District Reasi
2025_PDD_284260_1
E-nit 13 of 2025-26 dated 14.08.2025
Open Tender
Electrical Works
Turn-key
120 days
ED REASI
As per SBD
3 documents required · 3 mandatory
₹3,000
EXECUTIVE ENGINEER
₹5.0 L
0FFICE OF THE EXECUTIVE ENGINEER ED REASI
26 Sept 2025
18 Aug 2025
9 Sept 2025
18 Aug 2025
8 Sept 2025
18 Aug 2025
18 Aug 2025 - 1 Sept 2025
1 Sept 2025
Amount
Creation of 25KVA Distribution Substations (Supplying including Transportation , Carriage, Erection, Testing & Commissioning Complete Job)
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors fully Efficient Energy Level-2 (i.e actual Efficient energy level 3 redesignated as Efficient Energy Level 2 as per amendment no.4 of relevant IS ) , (Aluminium wound)
9 mtr long Pole ST-410, SP33
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
50sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with GI Disc fitting
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation of Earthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover/chemical earthing
Galvanised Stay Set, stay clamp, guy insulator, anchor plate, nut-bolts, turn-buckles, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
LT Fuse set (complete)
Danger Plates with clamps
Painting of Poles Aluminium Paint of reputed make
Laying of 11 KV on 8 meter ST Pole with ACSR Weasel Conductor (Supplying including Transportation , Carriage, Erection, Testing & Commissioning Complete Job)
ST Pole 8 mtr ST 410 SP15
GI V cross-arm with top Bracket including clamp and GI Channel/Angle Iron including clamps and braces
11kv GO AB Switch set 3-Phase, 3-Pole, 200Amp
ACSR Weasel Conductor
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with GI Disc fitting
Galvinized Nuts and Bolts
Danger Plates with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3)mm.
Aluminium Paint of reputed make
Galvanised Stay Set, stay clamp, guy insulator, anchor plate, nut-bolts, turn-buckles, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Laying of LT Line (3-Phase, 4-Wire)/ (1 Phase, 2-wire) on ST Poles 8.0 Mtr long with ACSR Weasel (Supplying including Transportation , Carriage, Erection, Testing & Commissioning Complete Job)
8 Mtr. Long Pole( ST-410 SP15)
GI M Clamp for shackle Insulator
16KN Polymer shackle Insulator
ACSR Weasel Conductor
Galvanised Nuts & Bolts
Danger Plates with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3)mm.
Aluminium Paint of reputed make
Galvanised Stay Set, stay clamp, guy insulator, anchor plate, nut-bolts, turn-buckles, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Supply of material
Supply of 11KV, Pin Insulator (Polymer type)
Supply of 11KV, Disc Insulator with Gi Disc fitting (Polymer type)
Supply of GI channel Iron (75x40x6)mm / (100x50x6)mm
Supply of GI Mukhi clamps with LT shackle Insulator
Supply of GI Nuts & Boltsof various sizes
Supply of Telescopic Aluminum ladder (20 mtr long)
Supply of GI Angle Iron (40x40x6)mm
Safety Helmet with Torch Light as per IS standard
Gee Sab Electricals (BID ID -2482340)
VEENA CONSTRUCTION CO. (BID ID -2478927)
M/S SURAJ PARTAP SINGH (BID ID -2467614)
M/S CLEAR LINE ENGINEERS CONTRACTOR (BID ID -2487144)
M/S RATHER CONSTRUCTIONS AND TRADERS (BID ID -2484830)
POWER SOLUTIONS (BID ID -2485415)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .