| Sl No | Description | Qty | Unit | Mahindra Electric Stores L2 | SHREE VAIBHAV ELECTRICALS L3 | PURVA ELECTRICALS AND ENGINEERS L9 | SKS Electricals L4 | Priyanka Power line L8 | SHRI PLACEMENT AND CONSULTANCY SERVICES L5 | Aziz Traders L1 | Adinath Technical Services L7 | AMAN ENGINEERING AND ELECTIRICALS WORKS L6 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply, install testing and commissioning in repair factory made out door type LT panel board of size not less than 1.2 mtrX1.4 mtrX0.450 mtr, 440 volts , 3 phase , 4 wire system with powder coating provided to make it dust /vermin proof manufactured from CPRI approved manufacturer, The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCA sheet,double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, TPN, Change over, copper bus and extension links. Copper bus bar of capacity 500 Amps- 4Nos, including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resin insulator all housed in suitable bus bar chamber. All control wires shall be as per the OEM recommendations and shall be properly bunched,tied, ferrulled for proper indentification and crimped with adequate size of lugs and provision and fixing of Voltmeter,Ammeter with built in selector switch, CTs of suitable ratio, and pilot indication lamps complete along with provision of necessary cable entry/exit boxes for all incoming and out going cables with suitable size of cable glands etc. Computer cut shelf adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. including necessary excavation /refilling for dismantling and reconnecting the existing incoming and outgoing cable complete alla s specified and directed. The panel shall consists of following accessories:- (Location :- Near Primary school) | 1 | Each Job | 1,50,000 ₹1,50,000 | 1,50,000 ₹1,50,000 | 1,50,000 ₹1,50,000 | 1,75,000 ₹1,75,000 | 1,65,000 ₹1,65,000 | 1,63,000 ₹1,63,000 | 1,34,000 ₹1,34,000 Lowest | 1,70,000 ₹1,70,000 | 1,70,000 ₹1,70,000 |
| 1.01Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminium lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50x50x6mm with bottam of panel having minimum 60cm height from existing ground/floor level. | ||||||||||||
| 1.02Copper bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete. | ||||||||||||
| 1.03Indicator Lamp-02 Set (Set of three) for Incoming and out going supply | ||||||||||||
| 1.04Incommer MCCB 4P 315 Amp, 415V, 36 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No. | ||||||||||||
| 1.05Outgoing, MCCB 3P 200 amp, 415V, 25 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No | ||||||||||||
| 1.06Outgoing, MCCB 3P 100 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No | ||||||||||||
| 1.07Outgoing, MCCB 3P 63 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 03 No | ||||||||||||
| 1.08Digital MFM with LED display cat no- 4149 92 model PMX 7300 of Make :- Legrand or equvilant in L&T/HPL 01 nos | ||||||||||||
| 1.09Connection with copper bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles. | ||||||||||||
Tender Value
Refer Docs
EMD Value
₹86,866
Closing Date
14 Aug 2025, 6:00 pmClosed
GE MH AND RH KHADKI
Military Engineer Services Garrison Engineer MH and Range Hills Range Hills Road Khadki, Pune 411003
SPECIAL REPAIR TO LT OVERHEAD LINES TO UNDERGROUND CABLE FROM BLDG NO T 10 AND T 15 TO BLDG NO T 03 NEAR BDE CDR HOUSE AT AUNDH MILITARY STATION PROVN OF POWER BACKUP AND ALLIED INFRA AT HQ 330 INF BDE AND PROVN OF AC FOR CONF HALL OPS ROOM AND SAND
2025_MES_722394_1
8736/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE MH AND RH KHADKI
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
Yes
GE MH AND RH KHADKI
₹86,866
6 Oct 2025
24 Jul 2025
16 Aug 2025
24 Jul 2025
14 Aug 2025
7 Aug 2025
24 Jul 2025 - 14 Aug 2025
Amount
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminium lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50x50x6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Copper bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-02 Set (Set of three) for Incoming and out going supply
Incommer MCCB 4P 315 Amp, 415V, 36 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No.
Outgoing, MCCB 3P 200 amp, 415V, 25 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No
Outgoing, MCCB 3P 100 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No
Outgoing, MCCB 3P 63 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 03 No
Digital MFM with LED display cat no- 4149 92 model PMX 7300 of Make :- Legrand or equvilant in L&T/HPL 01 nos
Connection with copper bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
On Load Changeover Switch 415 Volts, 400 Amp 4 pole -01 No
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminium lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50x50x6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Copper bus bar strips with proper colour code -04 No, 320 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-02 Set (Set of three) for Incoming and out going supply
Incommer MCCB 4P 160 Amp, 415V, 36 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No.
Outgoing, MCCB 3P 40 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 04 No
Digital MFM with LED display cat no- 4149 92 model PMX 7300 of Make :- Legrand or equvilant in L&T/HPL
Connection with copper bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
On Load Changeover Switch 415 Volts, 160 Amp 4 pole -01 No
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminium lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50x50x6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Copper bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-02 Set (Set of three) for Incoming and out going supply
Incommer MCCB 4P 315 Amp, 415V, 36 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No.
Incommer MCCB 4P 160 Amp, 415V, 36 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No.
Outgoing, MCCB 3P 40 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No
Outgoing, MCCB 3P 63 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 04 No
Digital MFM with LED display cat no- 4149 92 model PMX 7300 of Make :- Legrand or equvilant in L&T/HPL
Connection with copper bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
On Load Changeover Switch 415 Volts, 400 Amp 4 pole -01 No
Note : (i) Electrical connection from switchgear to bus bar would be through copper cable of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminium lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 50x50x6mm with bottam of panel having minimum 60cm height from existing ground/floor level.
Copper bus bar strips with proper colour code -04 No, 320 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-02 Set (Set of three) for Incoming and out going supply
Incommer MCCB 4P 160 Amp, 415V, 36 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No.
Outgoing, MCCB 3P 63 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 02 No
Outgoing, MCCB 3P 40 amp, 415V, 16 KA Ics = 100% Icu Fixed thermal maganetic type - 01 No
Digital MFM with LED display cat no- 4149 92 model PMX 7300 of Make :- Legrand or equvilant in L&T/HPL
Connection with copper bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
On Load Changeover Switch 415 Volts, 160 Amp 4 pole -01 No
Supply, Fixing and Testing warm light LED flood light fitting of 150 Watt, Luminaire fitting of IP 66 protection comprises of Pressure die cast Aluminium housing powder coated, toughened glass,LED's provided with secondary lens optics,luminaire efficacy not less than 110 lm/w provided with SPD 10 KV included complete all as specified and directed. Make - Halonix/Crompton/Wipro
Material & Labour for earthing complete in repairs with galvanised steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to 4.0 mm dia galvanised earth lead wire by means of nuts bolts check nuts and GI washers including PCC pit in PCC 1:2:4 type B-1 (20mm graded stone aggregate) RCC cover 20 mm dia (medium grade) GI watering pipe with funnel wire mesh and protection pipe of GI of suitbale size upto 7.5 mtr length including charcoal black cotton soil as required at site to achieve the earthing result and common salt, excavation earth work etc in any type of starta complete all as shown in electrical plate No 3 as specified, GI wire suitable size and length for continuity earth wire from test point to main distribution Board and complete all as specified and directed. Note: (i) Rate for achieving required depth by compressor machine if required is deemed included in item unit rate. (ii) After earthing contractor should test the earth value and submit register for earth resistance result to Engr-in-Charge.
Supplying, laying, jointing, commissioning and testing XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches/ducts/wall / floor / pipes/ poles including cable glands and aluminium lugs of appropriate size, pvc sleeve etc complete all as directed by Enginner in -Charge for following sizes . Make :- Havells / Gloster / Finolex / Polycab
185 Sqmm 3.5 core
120 sq mm 3.5 core
70 sq mm 3.5 core
35 sq mm 3.5 core
10 sq mm 4 core
NOTE :- Earth work , bricks , riddled earth , GI pipe for protection of cable will be measured & paid under under relevant items of schdule .
Excavation in trenches not exceeding 1.5mtr wide and not exceeding 1.5mtr in depth for foundation of poles stays laying of electric cables, pipes etc and getting out in soft/loose soil complete all as specified and directed.
Ditto item no 8 but in hard/dense soil.
Removing excavated material soil to a distance not exceeding 50mtr and depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as specified and directed
Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25cm in soft/loose soil complete all as specified and directed.
Material and Labour for riddled earth for cushioning to under ground electric cable including spreading , levelling and hand punning complete all as specified and directed. Note - Punned thickness shall only be measured & paid .
Material and Labour for road cutting / foot path and making good with PCC 1:3:6 TYPE C-2 ( using 40 mm graded stone aggregate ) of 150 mm depth complete all as specified and directed.
Supply and laying un-reinforced precast concrete cable cover LV, Type I, flat, size 250mm x 150mm x 40mm for Under ground cable complete all as specified and directed.
Supply and laying GI tubes light grade, galvanized, 40 mm bore in repair ,laid in trenches or under floor or fixed with poles/walls for protection of electric cable complete all as specified and directed.
Ditto item no -15 but 80 mm bore.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size 6 to 16Sqmm 3.5/4 core cable complete all as specified and directed.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size 25 to 50Sqmm 3.5/4 core cable complete all as specified and directed.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 70 to 120 sq mm 3.5/4 core cable complete all as specified and directed.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 150 to 185 sq mm 3.5/4 core cable complete all as specified and directed.
Taking down ACSR Conductor from pole including taking down cross arm and any type Pin / shackel / disc insulator and removing materials to store for keeping in safe custody or for taking into credit (credit for above items shall be made as per condition laid down under schedule of credit seprately ) and making good disturbed surfaces/ area near the poles complete all as specified and directed. Note : Single conductor measured as length of conductor
Taking down old unserviceable LT UG cable of size 35 Sq mm 3.5 core from trenches/ pole/ ducts to bldg DB complete all as specified and directed by Engr in Charge.
Supply installation testing and commissioning Silent type Diesel Engine Generating set 415 volts 58.5 KVA/ 60 KVA, 3 phase 0.8 power factor, 50 Hz, 1500 RPM self exicited self regulated brushless AC generator installed including AMF panel, suitable for ambient condition at Pune (Maharastra) and confirming to condition under ISO 3046, IS 10002, BS 5514/5000 with capacity of 10% overloading for one hour in every twelve hour duration compliance with as per latest CPCB norms for emission limits in consonance with the enviroment (protection) thrid ammendment vide GSR 232(E) dt 31 Mar 2014 GSR 789(E) dt 11 Nov 2014 abd GSR 105(E) dt 17 Feb 2015 at ser no 05 issued by ministry of environment and forests GOI and noise level shall be 75 db(A) at 1 meter from the enclosure surface and including the following accessories :- (A) Alternator :- Synchronous alternator rated at 58.5/60 KVA suitable for continuous operation at 1500 RPM generating 415 volts at 0.8 PF (lag) suitable for 50 Hz, three phase, 4 wire system. The alternator shall be brushless, self excited & self regulated with an AVR .The alternator will be suitable for tropical climate and shall generally confirm to IS: 4722 : 2001 B5 :2613 The salient features of the alternators are :- (a) +-1% voltage regulation (max) in static conditions. (b) IP: 23 protections with class ‘H’ insulation. · (c) Permanent lubricating bearing. · (d) Permissible overload of 10% for one hour in 12 hours of operation.
(B) Diesel Engine: - Adquate capacity of Diesel engine water cooled to drive independently above alternator and after considering de-rating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant IS/BS complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under :- i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts. iii) Cooling Water pump : - Centrifugal type belt driven. iv) Exhaust System :- Exhaust System complete with exhaust piping of suitable dia with MS pipe as per OEM medium grade including Turbo charger type Exhaust manifold Silencer - Residential type. v) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by governer electric operated/ (as recommended by OEM) for 1% speed /frequecy regulation. Fuel filters.
vi) Lub oil System :- Lubricating oil filter , Lubricating oil pump vii) Air Intake System :- Air intake Manifold, Air cleaner dry type viii) Governer mechanical type ix) Starting System :- Electric Self starter with and including battary charging alternator 12 Volts DC. x) Batteries :- Batteries of maintenance free of capacity 12 V, 120 AH- 01 No (or as provided by OEM) complete with copper conductor multistranded leads of suitable length from self starter to the battary terminals complete with initial charge and initial fill of electrolyte all as specified. Start and stop push button Ignition key / Switch Radiator with blower fan & first fill of coolant oil Corrosion inhibitor coolant Direct fuel injection system through governer mechanical type (xi) Noise level shall be 75 db(A) at 1 meter from the enclosure surface.
xi) Generator Monitoring Panel : - Comprising of all standard items as per standard manufacturing, iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolant temperature indicator, Battery volt display. xii) Safety Controls : - Engine low lube oil pressure high water temperature and over speeding of engine. xiii) Coupling arrngement : - Flexible coupling xiv) Accessories :- AVM Pads built- in or separtely mounted to manufactrer base frames. xv) Base Frame : - Base frame is fabricated either in ISMC channel or in sheet metal. The base frame will be primer coated and painted. The base frame is rugged in construction and designed for mounting Diesel engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure & control panel on it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator. xvi) MS/Steel flexible pipe line to and from the fuel tank to the DG Set. xvii) Battery Charger shall be provided as per manufacturer guidelines. xviii) 1 No battery of 12 V in charged condition with its leads.
C) ACOUSTIC ENCLOSURE : Acoustic enclosure shall be powder coated and fabricated out of 16 SWG CRCA MS sheet. The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Powder coating is done after seven-tank surface preparation process of sheet metal. Canopy panel and doors shall have inside lining of FIRE-RETARDANT foam as acoustic material & Rock wool for hot zone.Adequate hinged doors shall be provided to canopy, one door shall have glass window for control panel visibility. (i) Manufactured by OEM suitable for 58.5/60 KVA DG Set. (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board. (iii) The generating set battery should be inside the enclosure. (iv) Fuel tank :-Daily service fuel tank of 8 hours of continuous operation, fabricated form 14/16 SWG sheet metal complete with drain, inlet and outlet connection and fuel gauge. (v) Construction Details/specification are as follows : - (a) Outer body :- CRCA Sheet of 1.6mm thick.
(b) Doors :- CRCA sheet of 1.6 mm thick. (c) Sound Insulation :- 100 mm thick rock wool (minimum density 64kg/Cum)/ fire resistance foam/puff as per OEM/ as per standard manufacturing to achieve desired decibel level. vi) The acoustic should be composite in construction and fully assembled integral unit. vii) The DG Set should be provided with external Emergency stop push button. viii) The enclosure should be suitably internally illuminated by LED Lamp fittings. ix) The noise level should be 75 dB at 1mtr under free field conditions as per the current CPCB norms. x) The acoustic enclosure parts shall be of powder coated after pre treatment process. The base frame should be painted with epoxy based black shade. Note :- (i) The complete DG Set shall be procured from authorised OEM of the manufacturer of engine. A certificate in this connection shall be submitted to the GE. (ii) Circulation system to achieve desired inside temperature of acoustic enclosure, if required shall be provided as per OEM recommendation.
(iii) The quoted rate shall be deemed to be inclusive of 12 hours test run at site as specified in PS and IS requirements in presence of E/M Offr detailed by HQ CEPZ, Pune. All testing arrangements/ equipments shall be made available by the contractor for tests. (iv) The quoted rate shall be deemed to be inclusive of first fill of lubricant oil, DHPP 'N' for 12 hours testing and final successful acceptance test. (v) Anything missed out above but technically required for efficient working of DG Set is deemed to be included in quoted rates. vi) Design / drawing of the AMF panel & DG SET showing the dimensions is to be obtained from DG SET/ panel board manufacturer / supplier & is to be got approved from Engr-in-charge/GE before placing final order to the manufacturer. (vii) The electrical connection of digital Multi Functional Meter in the AMF panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc can be done of both SEB mains & DG mains. viii)The quoted rate shall be deemed to be inclusive of first fill of engine oil & final successful acceptance test.
D) Control Panel :- Control panel shall be fabricated from 16/14 SWG sheet and powder coated after seven tank treatment process: (i) Microprocessor based generator set monitoring and control system consists of LCD display and to monitor operator interface, fault history, alternator data, Engine data, porvision for service adjustement and caliberation of DG control functions, Engine controls, engine protective functions, alternative protective functions etc. (ii) Instrument fuses and control wiring. (iii) Indication lamps for set running and load on. (iv) Bus bar including suitable capacity of MCB, including CTs, cable etc.
E) AMF Panel :- Automatic Mains Failure (AMF) Panel made of CRCA sheet 2 mm thick including necessary arrangement to Install, Testing and Commissioning & connecting to load cable up to changeover switch, suitable capacity of 4 pole MCCB complete all as per OEM recommendation.
F) Civil Works :- All civil works required is included in the quoted rates. Note:- The contractor shall arrange for artificial load resistive for testing of DG Set at site and the cost is deemed to be included in the quoted rates.
MAKES :- Make of Engine : CUMMINS/KIRLOSKAR GREEN/ASHOK LEYLAND/GREAVES COTTON Make of Alternator : KIRLOSKAR ELECTRIC/ALSTOM/CROMPTON GREAVES/SIEMENS Make of Battery : Exide/AMCO/AMARON. AMF PANEL SPECIFICATIONS : AS PER MANUFACTURER SPECIFICATIONS
Material and Labour for Mild steel trolley complete as per drawing approved by OEM suitable for mounting DG Set of capacity upto 100 KVA on the trolley duly painted with two coats of Synthetic enamel paint over a coat of red oxide primer on metal parts of trolley including the following accessories :- (a) Four Nos cover outer, tube inner and wheel rim suitable for cover outer size 700 x 16 -12 Make MRF/Appolo / Dunlop (b) Front wheels provided with turning table. (c) Towing hook and attachment as per drawing. (d) Hand break arrangement for front wheels. (e) Four Nos 5 Ton capacity vertical jacks fixed on trolley of suitable trawersi to have 80mm clearance for tyres from ground level for ideal period for lifting. (f) Detachable type side panels
Supplying laying and fixing along the poles or passing through pipes or laid under floor or through walls etc jointing and testing LT Cross Linked Polythene Insulated (XLPE insulated) galvanized steel strip armored electric cable 1100 volt grade heavy duty ISI marked with aluminium conductor and overall served with an outer sheath of PVC, of cross sectional area 50 Sqmm 3.5 core complete all as specified and directed.
Supply , installation , testing & commissioning of inverter based wall mounted type splt air conditioner of capacity 02 TON ,(Copper coil) 3 Star rating ,electric driven single phase , 240 volts, 50 Hz AC supply , complete with indoor & outdoor unit , remote control ,including all accessories like brackets , MS stand made out from suitable size of MS angle iron, copper tubbing with nitrile rubber insulation including brazing , suitable size of pvc drain pipe , pvc insulated multistranded copper cable of suitable size from indoor unit to outdoor unit , and making good to disturbed surface to match with the existing surface complete all as specified and directed. Make Hitachi/carrier / Voltas /Blue star/'O' General Note :- All cooling /condensing coil should be copper material
Supply only copper tubing 5/8" for 1.0/1.5/2.0 TR split AC with proper insulation of suitable size and taking out old one as directed by Engr-in-Charge.
Supply only copper tubing 1/4" for 1.0/1.5/2.0 TR split AC with proper insulation of suitable size and taking out old one as directed by Engr-in-Charge.
Supply and fixing incl connecting sheet metal encosure with two pin and earth plug and socket complete, with one double pole MCB 20 Amp 240 Volts AC complete all as specified and directed. Make: L & T/Hager/Schnedier
Material and Labour for submain wiring with approved colour code/as per IS (Red, black & green for single phase) circuit with two single core PVC insulated cable with multistranded copper coductor of nominal cross sectional area of 4.0 Sq mm (FRLS) in and including PVC casing & capping non metallic including one run of PVC insulated multistranded copper conductor nominal cross section area of 4.0 Sq mm (FRLS) of continuous earth wire green in colour including taking down old u/s sub-main wiring complete all as specified and directed by Engineer-in-charge.
Mahindra Electric Stores (BID ID -3392961)
SHREE VAIBHAV ELECTRICALS (BID ID -3393064)
SKS Electricals (BID ID -3393185)
SHRI PLACEMENT AND CONSULTANCY SERVICES (BID ID -3393869)
AMAN ENGINEERING AND ELECTIRICALS WORKS (BID ID -3393897)
Adinath Technical Services (BID ID -3393316)
Priyanka Power line (BID ID -3393581)
PURVA ELECTRICALS AND ENGINEERS (BID ID -3393167)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .