Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹90.2 LAccepted-AOC | ₹90.2 L Quoted ₹90.3 L | L1 | Accepted-AOC LOWEST QUOTED BIDDER |
| 2 | L2₹95.8 L+₹5.5 L (6.11%)Rejected-Finance | ₹95.8 L+₹5.5 L (6.11%) | L2 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
| 3 | L3₹1.0 Cr+₹10.5 L (11.6%)Rejected-Finance | ₹1.0 Cr+₹10.5 L (11.6%) | L3 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
Tender Value
₹1.0 Cr
EMD Value
₹1.8 L
Closing Date
26 Nov 2020, 6:00 pmClosed
CWE AIR FORCE SECUNDERABAD
CWE AIR FORCE SECUNDERABAD, BOWENPALLY-POST, SECUNDERABAD-500 011
CERTAIN EXTERNAL SERVICES FOR EXPLOSIVE DECOMPRESSION CHAMBER (EDC) AND RAPID RECOMPRESSION CHAMBER (RRC) AT 2 AMTC AT AFA HYDERABAD
2020_MES_367444_2
86625/E8
Open Tender
Civil Works
Item Rate
270 days
GE (AFA) HYDERABAD
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
GE (AFA) HYDERABAD
₹1.8 L
Yes
5 Feb 2021
31 Oct 2020
28 Nov 2020
31 Oct 2020
26 Nov 2020
13 Nov 2020
31 Oct 2020 - 9 Nov 2020
Amount
Surface excavation not exceeding 30cm deep and averaging 15cm deep and getting out in soft/loose soil.
Removal of excavated soil material to a distance exc.250m but not exc 500 m and depositing as directed at a level not exceeding 1.50m above the starting point.
Excavating over areas, n exc 1.5m deep and getting out in soft/loose soil soil all as specified and as directed.
Rolling and consolidating of formation surfaces in cutting to the required gradient and camber incl filling in depression and hallows, levelling, watering and rolling using power roller 8 to 10 tonnes capacity all as specified.
Moorum/red bajri filling in side berms or pavings, laid in layers n exc 15 cm thick, spread, levelled and rammed incl watering all as specified and as directed.
Soling (or sub base) with broken boulders or quarried stone, interstices filled, surface formed and rolled to the spread thickness of 200mm and consolidated to required gradient and camber.
Wet Mix macadam (WMM) of 150mm thick compacted thickness in two layers of 75 mm thick each layer with coarse granite stone aggregate of specified grade spread using mechanical paver as specified, rolled and compacted using 8 to 12 tonne capacity vibratory power roller to required camber and gradient complete all as specified. Note: Quoted rate shall be for 150 mm thick consolidated thickness laid in two layers (each of 75 mm thick compacted thickness).
M&L for applying evenly a priming/tack coat with bituminous primer at 7.5 Kgs/10Sqm using slow setting cationic emulsion over WMM surfaces allow it to penetrate at least 5 to 10 mm from top surface of WMM all as specified and as directed.
Bituminous premix semi dense asphaltic dense concrete (SDAC) 40mm (consolidated thickness) in single layer using paving bitumen of grade VG-30 with 5.5% minimum binder content mixed by weight of total mix as wearing course, using hot mix plant and laid by using mechanical sensor paver, rolled and compacted to required camber and gradient complete all as specified Note :- (i) No extra payment shall be paid to the contractor for extra quantity of bitumen than mentioned in Sch "A" on plus side. However price adjustment shall be made for less quantity of binder content used in the work. (ii) Design mix for bituminous premix semi dense asphaltic concrete shall be got designed from approved lab/institution and approval of CWE shall be obtained. Hot mix plant shall also be inspected & approved by the rep detailed by Accepting officer.
M&L for Plain cement concrete 1:4:8, type D2 using 40mm graded stone aggregate as in foundation, filling and mass concrete etc., comeplete all as specified and directed.
M&L for Providing precast cement concrete Type B1 1:2:4 (using 20 mm aggregate) as in coping, kerbs, water troughs and and benching for manholes & haunching around manholes frame for setting the like including weathering slighting rounded or chamfered angles & throating and necessary form work complete all as directed.
Excavating in trenches, in soft/loose soil n exc 1.5m wide and n exc 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5m in depth and getting out
M&L Precast cement concrete block masonry exc 10cm in width with solid blocks type C1 1:3:6(20mm graded agg) and setting in cemetn mortar 1:4
M&L Rendering 15 mm thick in cement and sand mortar (1:4) mixed with water proofing compound as per manufacture's instructions on fair faces of brick or concrete surfaces, finished even and smooth without using extra cement, complete all as specified. Note: WPC shall be measured and paid at supply only rates under relavent item of BOQ Seperately
M&L Plain cement concrete (1:4:8) Type D-2 (using 40 mm graded stone aggregate) as in bed to drain pipes in trenches at any depth including packing under and completely surrounding 150mm bore NP2 pipe with concrete after pipe have been laid and tested complete all as specified and directed.
Supplying, laying jointing and testing 150 mm dia/nominal bore NP 2 cement concrete pipe in trenches in any depth complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm.
M & L Mild steel TMT bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips.
M & L providing pre cast reinforced cement concrete type B 1 1:2:4(20 mm graded aggregate) as in cover slabs set in cement mortar 1:6
Mild steel TMT bars 8 mm dia and over, cut to length, bent to shape required including cranking, bending spirally for hooping for cloumns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia as in stirrups and spacers and binders complete all as specified.
Extra for forming fair finished drain or channels of manholes inner girth not exceeding 30 cm in cement, including forms, mould, mitred/stopped ends etc. complete all as specified.
Supply only integral water proofing compound complete all as specified.
S&F Framed work such as grills, gratings, etc., with ends of bars shouldered and/or ri-veted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe 410-0 or Fe 310-0
Cutting into existing manholes for connecting new drain of dia 150 mm (Internal dia) making good to pipe and rendering, cutting out existing benching for and forming branch channel (1/2 round or 3/4 section) in cementt concrete 1:2:4 type B-1 smooth finished, and reforming benching as required.
RCC Septic tanks with an effective depth of 1.5m and over all depth of 3.00m for 50 users to carry sewage and sullage water, excavation in ordinary soft/loose soil, foundation in PCC 1:4:8, PCC block masonry in CM 1:4, RCC slab covers M-25 grade including RCC precast manhole cover having 6mm plate embedded all around/fibre reiforced coverwith angle iron frame vent shaft and sludge chambers etc all as shown on Drg No: AFB/TD/228/04 Sheet1/1
Soakage well of size 2.4M dia X 4.5 M deep, excavation in ordinary soft/loose soil, foundation in PCC 1:3:6, well of honey combed and solid in M-25 concrete, including intercepting chamber, screen chamber Brick work in CM 1:4, RCC cover slab in M-25 grade and Filling with brick bats complete as per standard Typical Drawing all as specified and directed
Precast cement concrete block masonry exc 10 cm in width Type C1 1:3:6 (Using 20 mm aggregate) and set in CM 1:6 complete all as specified and as directed
M&L for Providing precast cement concrete Type B1 1:2:4 (using 20 mm aggregate) in landings, cover slabs (for manholes,monsoon drain etc.) chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces (for use with masonry) including chamfers weatherings, throating etc. complete with joints to match
Mild steel TMT bars 6 to 8mm dia, cut to length, bent to shape required, including cranking, bending, spirally for hooping for columns, hooking ends and binding with and includng mild steel wirenot less than 0.9mm dia.
Rendring 15mm thick in CM 1:4 on fair faces of brick work or concrete surfaces finished fair and even complete all as specified and as directed.
Surface dressing not exceeding 30cm deep and averaging 15cm deep and getting out in soft/loose soil.
M&L for Rendering 15mm thick on fair faces of brick work or concrete surfaces in CM 1:6.
M&L for Providing, cement concrete type C1(1:3:6) using 20mm aggregate in, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded for chamfered angles and throating, as directed.
M&L for preparation of new surfaces and applying three coats of white wash on wall.
M&L for PVC (SWR) pipes 110mm single socketed, in any length with rubber ring joints laid in weep holes/ spout.
Excavating in post holes (or similar holes) each n exc 0.5 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25cm, watering, and removing surplus soil to a distance n exc 50 m and making good surface.
M&L for Cement concrete in foundations, filling and mass-concrete Type B2 1:2:4 (40 mm graded aggregate)
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provision of binding wire
Supply only Chain link MS galvanised fencing, any size or type
MS works in posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets ( for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe 410-0 or Fe 310-0
Mild steel bolts having dia 12mm,exc 30cm long, purpose made, with hexagonal or square head one end and screwed the other, or screw both ends; each screwed end to be fitted with washers and one hexagonal or square nut,
MS Round bars 08mm dia and over confirming to Fe-410-W (Gde.E-250) Quality-A cut to length bent to shape required incl bending hooking ends necessary to fix with angle iron post all as specified and directed
M&L for Preparation of new or old previously untreated surfaces of any description, over 10cm in width or girth not otherwise described with 2 coats of synthetic enamel paint over a coat of red lead.
M&L for Preparation of new or old previously untreated surfaces of any description, nexc10cm in width or girth not otherwise described with 2 coats of synthetic enamel paint over a coat of red lead.
M&L for Formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter.
Formwork to sides of pillars, posts, struts, piers, columns and stanchions.
RCC(design mix) M-25 in foundation, including raft, footing, foundation beam, plinth beam, bases for column etc, basement slabs, under-reamed piles and mass concrete.
RCC(design mix) M-25 in columns, pillars,piers, posts and struts and mass concrete.
Providing, cement concrete type C1(1:3:6) using 20mm graded aggregate in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates and the like including weathering, slightly rounded or chamfered an-gles and throating, as directed
Framed work such as for portions framed and hung as gates, including pintle hinges, stops, hand-made sliding bolts, etc. and similar work conforming to Fe 410-0 or Fe 310-0
M&L for preparation of newly plasterd surfaces with 3 coats of cement paint over walls complete all as specified
Dismantling wrought iron or mild steel work of any description not otherwise provided for like steel post embedded in concrete and chain link fencing secured to the steel post complete all as specifieda and as directed.
Excavating in trenches, in hard /dense soil n exc 1.5m wide and n exc 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5m in depth and getting out
All as per Item No. 55 but exc 1.5m but not exc 3.00 m depth
All as per Item No.55 but exc 3.0m but not exc 4.50 m depth
All as per Item No. 55 but exc 4.50 m but not exc 6.0m depth
PCC 1:3:6 type D2 using 40 mm graded stone aggregate Cement concrete as in foundations, filling and mass-concrete all as specified and as directed.
M&L for PCC (1:2:4) mix, type B-1 using 20 mm graded stone aggregate in splash stone set in CM (1:6)
Loose filling with boulder 80 to 150 mm size stone boulders in rain water harvesting pits all as specified
Loose filling with 40 mm to 80 mm size stone aggregate in rain water harvesting pits all as specified
Loose filling with 20 mm size stone aggregate in rain water harvesting pits all as specified
Sandfilling with coarse sand/pea size gravel in rain water harvesting pit including spreading and levelling
Supply and lay pipe DI pipes Class “K-7” ,100 mm (4”) dia with spigot and socket ends as per IS 8329,centrifugally cast Class LA in any length, laid in trenches all as specified and directed Note for Item No 65&67: Excavation earth work shall be measured and paid separately
Supply and fixing of DI special fittings bend/Tee up to 150mm dia any radius any angle , any type (straight bend, increasing, decreasing or double socket etc.) top pieces, double branch. "Y"junction, double branh, cross ( all sockets or spigot) collers caps and plugs etc
Supply and laying pipe galvanized Iron , “Medium grade ”, including all fittings of 50 mm (2”) dia including taping from existing pipe complete all as specified and directed by Engr in Charge.
Supply and fix Sliuce Valves, Sluice, flanged of class 1.0 PN,100 mm (4”)dia
Supply and fix Gun metal Gate Valve, 50mm (2”) dia pipe
Construction of brick masonry valve chamber of size 1200x1200x1200mm internal size in cement mortar 1:6 including base concrete (1:4:8) type D2, plastering with cement mortar 1:6 including provision of MS sheet of 3.15mm thickness complete with locking arrangement with 7 lever lock (01 Nos), lifting handle all as specified the item rate is deemed to be including excavation and earth work RFR and plastering in CM 1:4 all as specified and directed by engineering in charge.
Removing excavated material n.exc 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Supply, install, testing and commissioning of Transformer floor mounted capacity 500 KVA, step down, outdoor type11/0.433 KV,50 Hz, AC double copper wound, oil immersed, Oil Naturally Air Naturally (ONAN) cooled with external cooling tubes, transformer delta connection on HV side and star connection on LV side in accordance with vector symbol DyN-11 (vector group 4) and having tapping of + 5% to -10% in equal step of 2.5 % changed by means of off load tap changing arrangement. The voltage regulation shall be as per IS including first fill of transformer oil including all fittings /accessories as specified in SSR Part -I and IS -1180. The transformer should have cable box on both HT & LT side and brass bushing rod on both HT & HT side . The limit of temp rise after continuous full load run as specified in SSR part-I and IS -1180 shall be suitably adjusted to suit the maximum ambient temp prevailing at site all as specified comprising with and including the following specifications:-
(i) Type of connection arrangement :- MS cable termination box on both HT and LT side. Cable box on LT side consisting of 04 Nos porcelain bushing with brass bushing rods and nuts washerwith extended neutral terminal with bushing on the transformer body for terminating earthing strip and suitable for terminating of cable LT 1100 Volt grade XLPE insulated heavy duty Aluminium including gland joint complete
(ii) Cable terminal box HV grade suitable to make termination with 3 core 95 sqmm XLPE HT Cable.
(iii) Oil Conservator with filter type drain valve and oil level guage.
(iv) Thermometer Pocket
(v) Two Earthing Terminal on tank body to facilitate fixing of 32x6mm GI strip.
(vi) One No Thermometer Dial type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge : Max reading painted terminal.
(vii) Rating plate with terminal marking plate.
(viii) Oil level guage.
(ix) Oil drain filter valve.
(x) Oil filling port on top cover with plug.
(xi) Air release valve/plug.
(xii) First fill of transformer oil conforming to relevant IS and with dielectric strength more than 50 KV
(xiii) Inspection cover.
(xiv) Lifting lugs and jack lifting pad support.
(xv) Explosion vent with double diaphragm and sight glass.
(xvi) Silica gel breather or with connecting pipe, first fill of dehydrating agent.
(xvii) Hand hole of sufficient size to assess the interior of the tank.
(xviii) Cover lifting eyes.
(xix) Oil temperature indicator of approved range, including shut of valve between conservator and main tank.
(xx) Drain valve with threaded adaptor.
(xxi) Filter valve with threaded adaptor.
(xxii) Brick Platform of size 2.0m x 2.0m x 2.0m with PCC Bed 1:4:8 ) 150mm thick (1.5 m above Ground Level & 0.5m below ground level)
(xxiii) Extra bushing for neutral out side the LV side cable terminal box.
Note: 1. All routine tests/Pre commissioning tests to be carried out at site after Installation of transformer in presence of Rep of Accepting Officer. 2.OEM Test certificate shall be furnished by the contractor as per relevant IS. 3.GA drawing and Design drawing shall be submitted for approval of Accepting Officer before placing Order.
Supply, install, testing and commissioning 800 amps vacuum circuit breaker ( VCB) of 350 MVA rupturing capacity at 11 KV rated, fault level of 18.3 KA for 3 sec totally enclosed, air insulated metal clad housing, floor mounting, horizontal isolation, vermin proof, fully interlocked horizontal drawout type, IP-4X and with the following :
(i) Manually and motor operated, spring charged (release closing mechanism) trip free type, triple pole truck mounted draw out, vacum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indication ''OFF'' push buttons for emergency trip (shrouded) test/service position limit switches with min 6 NO/6 NC breaker auxilliary contact in service position, 30/24 volts DC shunt trip coil and strip heaters with thermostat switch. One heater in CT chamber and one heater at VCB chamber to prevent moisture absorption.
(ii) 800 amp air insulated but encapsulated copper bus bar tinned coated.
(iii) C.T chamber with double wound C.T's 35/5A, 25/5A, (separate core for metering and separate core for protection).
(iv) 15 VA burden for protection (Class 5P 10).
(v) 15 VA burden for instrumentation (Accuracy Class 0.5)
(vi) Voltage Transformer with 3 numbers 1 phase, 3 limbs connected in star, class 0.5 accuracy, 11 KV/ 3/110V/ 3 with drawable type with automatic shutters 100 VA burden on bus side and line side with primary & secondary fuses and isolating plugs. (confirming to relevant IS specification).
(viii) Following protection shall be provided:-
(a) Microprocessor based 3 Nos outer elements for over current and one middle earth - fault with IDMT self power relay with shunt trip on 30/24 Volts, DC, of Make Schnider/ABB/Siemens/L&T consisting 3 element overcurrent relay with setting from 50 to 200% and earth fault with setting from 10 to 80%.
(b) Anti pumping relay and Master trip relay
(c ) Buchalz Realy and including controle cables 4core 4Sqmm Coper conductoe armoured 1100Volts from relaty to transformer.
( d) Side Cable Box suitable for 3core 185 -95Sqmm with Copper busbar of 800Amps.
(ix) All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 1.5 sq mm copper wire where required.
(x) Test termninal box fuses/2A SP MCB, circuit labels, set of phases, indication lamps etc, as per standard practice as under.
(a) Red breaker closer (ON).
(b) Green breaker open (OFF)
(c) Amber-Auto trip
(d) Clear-trip circuit healthy
(e) White-3 Nos one per phase
(f) Blue spring charged
(g) The following meters are to be provided:-
(a) Digital type frequency meter range 45 to 55 Hz.
(b) Digital voltmeter range 0-15 KV and suitable for 110 AC square dial with shrouded terminal & protection fuses.
(c) Digital Ammeter 0-100A rating.
(d) Clear-trip circuit healthy
(e) White -3 Nos one paper phase.
(f) Blue spring charged
(g) Power factor meter-Range-0.5 lag to 0.5 lead.
(h) 6 Nos window annunciation panel with audio & visual indicator
(a) Over Current & earth fault-2 windows
(b) Spares-04 windows
(c) Power pack unit 220V AC to 24 Volt DC complete with battery back up (maintenance free) for operation of relays including charging equipment 01 set
(d) Control :- T-N-C (Trip, Neutral, Close) Breaker control switch with indication arrangement)
(e) Terminal box with single gland trifucating cable box suitable for 11 KV aluminium XLPE(E) cable of size 3x 185 to 95Sqmm for incoming and out going.
(f) HT Danger Plate (As per specification)
(g) 2 Runs of not less than 30x6mm earth bus bar shall be provided for full length of the panel.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm complete all as specified and directed. Note for Item No 74,75&76: Excavation earth work shall be measured and paid separately
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core complete all as specified and directed.
M&L for earthing complete with Galvanised steel earth plate eletrode 600 mm x 600 mm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filled in alternate layers and electrode connections by using Galvanised iron 32 x 6 mm strip connected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 15mm dia GI pipe medium grade for protection of GI earth strip and 20mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) type C1 chamber of size 45cm X 45cm X 45cm including, MS funnel, wire mesh, 50 mm thick RCC 1:2:4 type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 4 of schedule Part-I ( For VCB,Lt Panel, and Transformer)
M&L for earthing complete with Copper Earth eletrode 60 x 60 cm x 3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below GL) with top edge of earth plate not less than 1.5 Mtr below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filled in alternate layers and electrode connections by using Copper earthing strip as earthing lead of sise 20X3mm thick connected by means of bolts, nuts, check nuts and washer of galvanised iron or steel, provision of 40 mm dia GI pipe medium grade for protection of copper earth strip and 40mm dia GI pipe medium grade for watering arrangement and PCC (1:3:6) type C1 chamber of size 45cm X 45cm X 45cm including, MS funnel, wire mesh, 50 mm thick RCC 1:2:4 type B1 earth pit cover with 6 Nos, 8 mm dia high strength deformed steel TMT bars on both ways including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to distance n exc 50 mtr, provision of charcoal and salt complete all as shown in electrical plate No 3 of schedule Part-I (For Transformer neutral )
Supply and fix LED street light fitting of 90 watt capacity including fixing on pole with neccessary connection up to junction box with 2.5 sqmm 2 core copper cable and GI Pipe bracket made of 40mm dia pipe 1.2m long bent to shape fixed with MS clamps ,Screws etc complete all as specified and directed.
Supply and fix Gate Light/post top lantern light fitting 60 Watt LED lamp complete With all accessories with neccessary connection up to junction box with 2.5 sqmm 2 core copper cable complete all as specified and directed.
Supply and fix Steel tubular swaged pole with M.S base plate, finial tapper plug, bolts, nuts, and screw as specified type 410 SP- 31 (9 mtrs long ) complete as directed by Engr-in-Charge Note: Excavation & earthwork, PCC foundation, coping etc will be measured and paid separately.
Supply and fix Steel tubular swaged pole with M.S base plate, finial tapper plug, bolts, nuts, and screw as specified type 410 SP- 22 (8.5 mtrs long ) complete as directed by Engr-in-Charge Note:Excavation & earthwork, PCC foundation, coping etc will be measured and paid separately.(For Solar Light)
Supply and fix cable junction box 130X180X77 mm in size made out of thermoplastic sheet having IP 65 protection for out door installation fixed with 4 way bakelite cable terminals with one MCB SP 6 Amps to be fixed inside the box including 03 Nos polynide gland with checknut (M-32 - 3 Nos) fixed on pole with flat iron clamps of size 25 x 3 mm , nuts , bolts, washers etc., including two coats of synthetic enamel paint over a coat of redoxide zinc chrome primer all as directed by Engineer-in-charge . Make: Cat No. DK 1010G Hansel or equivalent models in Spelsberg/ Rittal.
The panel board shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The panel board shall be provided with ventilation facility in the form of louvers for better heat dissipation.The panel should be suitable to accomidate with and including the following swtich gears :-
LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, overload protection, no-volt release with necessary CTs,meter and cable boxes of rating upto 1000 Amps-01 No
4 Pole MCCB 32 Amp, 50 Hz, 415 V with rupturing capacity 16 KA -03 Nos
Supply and fix 4 Pole MCCB 100 Amp, 50 Hz, 415 V with rupturing capacity 25 KA-02 No .
Supply and fix 4 Pole MCCB 160 Amp, 50 Hz, 415 V with rupturing capacity 25 KA -02 Nos .
Supply and fix 4 Pole MCCB 200 Amp, 50 Hz, 415 V with rupturing capacity 35 KA-02 Nos
Supply and fix 4 Pole MCCB 250 Amp, 50 Hz, 415 V with rupturing capacity 35 KA.-01 No
Supply and fix Solar smart LED Street Lights 90 Watt with 20 Hrs backup with built in SCC, SPV Panel with lithenium battery in built in panel, cable and GI Pipe bracket made of 40mm dia pipe 1.2m long bent to shape fixed with MS clamps ,Screws etc complete all as specified.
Material and labour for dry clean river sand for cushioning of cable in trenches for cable protection including spreading, leveling and gently punning complete all as specified in SSR Part-I and as directed. Note :- punned thickness of sand shall be measured for payment purpose .
Supplying and laying un-reinforced precast concrete cable cover, class HV Type I, flat, size 300 mm x 180 mm x 40 mm. laid in trenches complete all as specified and directed.
M&L brick sub class B locally available best quality laid in trenches as in cable protection complete all as specefied and directed.
M & L for GI Tubes ISI marked light grade of size 40 mm bore laid in trenches for cable protection pipes complete all as specified and as directed by the Engineer-in-Charge
M & L for GI Tubes ISI marked light grade of size 80 mm bore laid in trenches for cable protection after removing the unserviceable pipes complete all as specified and as directed by the Engineer-in-Charge
M & L for GI Tubes ISI marked light grade of size 100 mm bore laid in trenches for cable protection after removing the unserviceable pipes complete all as specified and as directed by the Engineer-in-Charge
M & L for boring of holes under road pavment hard standing by using trenchless technology using ultrasound technique and necessary machine to insert light grade GI pipe of 50mm to 100mm for cable protection
S & F synthetic insulating mate of size 2m X 1m X 2.5mm thick as per Is 15652-2006 complete all as specified and directed.
S & F Cable jointing end kit for 11 Kv (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing materials and accessory suitable for 3 core XLPE armoured aluminium conductor cable of size 3 core 95sqmm all as specified and directed.
B R C CONSTRUCTIONS
Dwarka Pershad Radhey Ramanlal
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .