SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF AIR CONDITIONING WORK FOR VGSOM BUILDING, IIT KHARAGPUR
2020_IITKG_600915_1
NIT No. IITKGP/IW/RAC/VGSOM/2020 21
Open Tender
Plant Protection Input/Equipment Works
Item Rate
100 days
IIT Kharagpur
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹1.9 L
Yes
ESTATE ( EaM), Head Office, 1st Floor, Old Buildin
29 Jan 2021
4 Dec 2020
18 Dec 2020
4 Dec 2020
17 Dec 2020
4 Dec 2020
10 Dec 2020
Amount
Supply, Installation, Testing & Commissioning of Air Cooled type outdoor units of VRF system having hermetically sealed inverter scroll/twin rotary compressor, condenser coil fabricated from Seamless Copper tube & Plate type Al. Fins of Multi Row, Axial Flow, top discharge throw condenser fan, Condenser fan - motor unit, insulated refrigeration piping, power / control wiring with TPN MCB & encloser, and earthing, external wiring between Indoor & Outdoor units, all system controls-safety. The system should have flexibility to handle total 280 Rmt of ref. piping. ODU shall be placed on structure with heavy duty anti vibrational pad to protect the system from any kind of unwanted vibration. The system shall have minmum COP of 3.7 at ARI condition as per CPWD guidelines. Each Outdoor units with High Pressure switch, Fan driver overload protector, Over current relay, Inverter Overload Protector & Fusible Plug. The unit shall be suitable for 415 ± 10 % volts, 50 Hz, 3 phase AC supply, and IP protection will be suitable for outdoor installation. The VRF System shall have green ref. gas only- R410A/ R407
Indoor Units Supply, Installation, Testing & Commissioning of Indoor units address setting and capacity as mentioned below. Multi speed motor, coil section with DX coil, outer cabinet, drain pan mechanism insulation, pipe connections, clamp metal, washer fixing plate, sealing pads, screws, clamps, washer for hanging bracket & insulation for fitting, fresh air intake connector for cassettes etc. of various capacities as per specifications. Power cabling (3mtr from unit) with conduit from power socket & plug top to indoor is inclusive of price.
Cassette Type Indoor Unit With Cordless Remote Control - Capacity – 1.5TR
Hi-Wall Type Indoor Unit With Cordless Remote Control - Capacity - 2.0TR
Hi-Wall Type Indoor Unit With Cordless Remote Control - Capacity – 1.5TR
Hi-Wall Type Indoor Unit With Cordless Remote Control - Capacity - 1.0TR
VRF Y JOINTS FOR BRANCH DISTRIBUTION REFRIGERENT PIPE JOINTS WITH PRECAST INSULATION
REMOTE CONTROLLER
Supply, installation, testing & commissioning of Cordlesss remotes for VRF indoor units
SITC of VRF Refrigerant Piping: Supply, installation, testing & commissioning of Seamless heavy gauge Copper piping of following size duly insulated with 13 mm/ 19mm thk. Nitrile Rubber Insulation covered with aluminium foil ( As per Specified with K Value of 0.027-0.029 K Cal/Hr.M Deg C at 0-16 Deg C) . Refrigeration piping will have to be taken in the piping rack / Support individually connecting to all indoor units for the respective floors. Even necessary supports, fittings, valves & ref. joints where ever required will be included. The exposed refrigerent insulated piping shall be covered with UV Resistance canvass coating.
44.5 mm O.D.(with 19 mm insulation )
41.3 mm O.D.(with 19 mm insulation )
38.1 mm O.D.(with 19 mm insulation )
31.8 mm O.D.(with 19 mm insulation )
28.6 mm O.D.(with 19 mm insulation )
25.4 mm O.D..(with 19 mm insulation )
22.2 mm O.D..(with 19 mm insulation )
19.05 mm O.D..(with 19 mm insulation )
15.88 mm O.D..(with 19 mm insulation )
12.7 mm O.D..(with 19 mm insulation )
22.2 mm O.D..(with 13 mm insulation )
19.1 mm O.D..(with 13 mm insulation )
15.9 mm O.D..(with 13 mm insulation )
12.7 mm O.D.(with 13mm insulation )
9.52 mm O.D.(with 13mm insulation )
6.35 mm O.D.(with 13mm insulation )
Supply, Installation and Testing of rigid PVC Drain Piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation.
50 mm dia
40 mm dia
32 mm dia
25 mm dia
SITC of GI perforated Cable Tray for the refrigerant pipe hanging & Covering
Supply & fixing of control cum transmission wiring of Copper conductor cable along with PVC conduit for looping between indoor & outdoor VRF system.
2 C X 1.5 Sq. mm
Supply, installation, testing & commissioning of Power Cabling with termination to individual Outdoor units. ( From Power Panel to VRF ODU )
Supply, Installation Testing & Commissioning along with all necessary cabling of Central Station with basic control system such as ON/OFF, Operation Mode & Temp , Air Quantity & ALARM CODE display incase of any error occur etc upto 160nos IDU
Decorative Pelmets of required size for IDUs with 16 mm thich anti termite laminated board.
Comprehensive AMC of the VRF system for four years after DLP.
Comprehensive AMC 1st Year after DLP
Comprehensive AMC 2nd Year after DLP
Comprehensive AMC 3rd Year after DLP
Comprehensive AMC 4th Year after DLP
Buy back of existing window/split Acs: Buy back of existing window/split Acs of various capacities. The price for dismentling, shifting of existing Acs to vendor's ware house shall be included in quoted price.
Window Acs
Split Acs
HVAC related Civil Work: Cutting holes up to 30x30 cm in walls including making good the same: On any height.
With common burnt clay F.P.S. (non modular) bricks
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge.In cement mortar.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to any level.
1:2:4 (1 cement : 2 coarse sand (zone-III) :4 graded stone aggregate 20 mm nominal size).
Half brick masonry with non modular fly ash bricks of class designation 10, conformingio IS :12894, in super structure above plinth and upto floor V level.Cement mortar 1 : 4 (1 cement : 4 coarse sand)
15 mm cement plaster on brick wall of mix :1:6 (1 cement: 6 coarse sand)
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion
Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15)
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface :Water thinnable cement primer.
Wall painting with acrylic emulsion paint, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour.
Two coats.
Supplying bubble free float glass of approved make and brand conforming to IS: 2835-1987. 5mm thick coloured / tinted / smoke glass.
ESSGEE ENTERPRISE
AIR Q SOLUTIONS
ALPHA GAMMA AIR SOLUTIONS PVT. LTD.
EVAC ENGINEERING PROJECTS PVT. LTD.
MEHO HCP AIR SYSTEMS PVT LTD
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .