Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 LAccepted-Finance | ₹7.3 L | L1 | Accepted-Finance L1 Quoted Bidder. |
| 2 | L2₹7.7 LRejected-Finance | ₹7.7 L | L2 | Rejected-Finance L2 Quoted Bidder. |
| 3 | Rejected-Technical | - | - | Rejected-Technical Technically Disqualified |
| Sl No | Description | Qty | Unit | VISION CATALYST CONSTRUCTION PRIVATE LIMTE L2 | R.K.ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00Fan Section (Ventilation) Unit | |||||
| 1.20 | DOUBLE SKIN CASING:
Outer skin: 0.6 mm Pre- coated GI, Inner Skin: 0.6 mm Plain GI, Framework: Hollow Al profile, Thickness of insulated panels: 23 mm, CFC Free PUF injected (Density: 40-42 kg / Cu. m.), Unit Base: G.S.S base channel (applicable for floor mounted units only),
FILTERS:
Media of Filters: Synthetic non-woven type, Efficiency of Pre-filters (EU-4): 90 % down to 10 microns, Make Of Filters: THERMADYNE/ DRYCOOL/MECHMAARK.
FAN & MOTOR:
Fan & Motor Base: GI, Vibration Isolators: Rubber mount, Fan make: NIOCTRA /KRUGER/FANAIR/BLOWTECH: Motor make: ABB / CROMPTON /BHARAT BIJLEE/HAVELLS
Specifications of Unit:
AIR QTY (CFM): 5000CFM, SP (MM WG): 55, SIZE – LXWXH IN MM limited to: 1300X1700X1045, FAN TYPE: Forward Curved, KW RATING: 3.7, FAN RPM: Above 493, VELOCITY (M/S): 9.2, PRE FILTER AREA (SQ.FT.) @ 500
FPM: Yes | 2 | Nos | 1,90,000 ₹3,80,000 | 1,81,000 ₹3,62,000 Lowest |
| 2.00AIR DISTRIBUTION SYSTEM FOR VENTILATION ( SHEET METAL & ALLIED WORKS ) | |||||
| 2.10 | Site fabricated GSS sheet metal rectangular ducting as per IS 655 2006 for 0.63 mm thick | 150 | Sqmtr | 1,345 ₹2,01,750 | 1,100 ₹1,65,000 Lowest |
| 2.20 | Site fabricated GSS sheet metal rectangular ducting as per IS 6552006 for 0.8. mm thick | 50 | Sqmtr | 1,140 ₹57,000 Lowest | 1,250 ₹62,500 |
| 3.00Grills | |||||
| 3.10 | Supply, Installation, Testing and Commissioning of AL powder coated Linear Supply Grill with dampers with all side Flanges & as per technical specifications.Supplying, Fixing, installation, testing and commissioning of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers in confirmation to SMACNA/IS and as per specifications complete etc. as required. | 5 | Sqmtr | 10,053 ₹50,265 | 8,600 ₹43,000 Lowest |
| 3.20 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required. | 5 | Sqmtr | 7,000 ₹35,000 | 4,500 ₹22,500 Lowest |
| 4.00Electrical Work | |||||
| 4.10 | Supply installation of 5HP Three Phase 415 Volt Dol Control Panel with over load relay protection (4-9A) ,on/off indication, ameter voltmeter indication & with compleate control and power wiring. | 2 | Each | 2,100 ₹4,200 Lowest | 22,500 ₹45,000 |
Tender Value
₹7.7 L
EMD Value
₹15,494
Closing Date
8 Jul 2026, 3:00 pmClosed
DIRECTOR HBCH AND RC MUZAFFARPUR
DIRECTOR OFFICE HBCH AND RC MUZAFFARPUR BIHAR
SITC of Ventilation Fan Fresh Air Fan AND Exhaust Air Fan at Underground Pump Room for HBCH AND RC Muzaffarpur Bihar 842004
2026_TMC_914819_1
HBCHRC/ENGG/VENT/FAN/26/NIT/06
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
HBCH AND RC MUZAFFARPUR BIHAR
AS PER NIT
2 documents required · 2 mandatory
₹0
₹15,494
Yes
ENGINEERING DEPARTMENT HBCH AND RC MUZAFFARPUR
23 Jul 2026
25 Jun 2026
9 Jul 2026
25 Jun 2026
8 Jul 2026
1 Jul 2026
26 Jun 2026 - 29 Jun 2026
30 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Fan Section (Ventilation) Unit | |||||
| 1.2 | DOUBLE SKIN CASING:
Outer skin: 0.6 mm Pre- coated GI, Inner Skin: 0.6 mm Plain GI, Framework: Hollow Al profile, Thickness of insulated panels: 23 mm, CFC Free PUF injected (Density: 40-42 kg / Cu. m.), Unit Base: G.S.S base channel (applicable for floor mounted units only),
FILTERS:
Media of Filters: Synthetic non-woven type, Efficiency of Pre-filters (EU-4): 90 % down to 10 microns, Make Of Filters: THERMADYNE/ DRYCOOL/MECHMAARK.
FAN & MOTOR:
Fan & Motor Base: GI, Vibration Isolators: Rubber mount, Fan make: NIOCTRA /KRUGER/FANAIR/BLOWTECH: Motor make: ABB / CROMPTON /BHARAT BIJLEE/HAVELLS
Specifications of Unit:
AIR QTY (CFM): 5000CFM, SP (MM WG): 55, SIZE – LXWXH IN MM limited to: 1300X1700X1045, FAN TYPE: Forward Curved, KW RATING: 3.7, FAN RPM: Above 493, VELOCITY (M/S): 9.2, PRE FILTER AREA (SQ.FT.) @ 500
FPM: Yes | 2 | Nos | - | - |
| 2AIR DISTRIBUTION SYSTEM FOR VENTILATION ( SHEET METAL & ALLIED WORKS ) | |||||
| 2.1 | Site fabricated GSS sheet metal rectangular ducting as per IS 655 2006 for 0.63 mm thick | 150 | Sqmtr | - | - |
| 2.2 | Site fabricated GSS sheet metal rectangular ducting as per IS 6552006 for 0.8. mm thick | 50 | Sqmtr | - | - |
| 3Grills | |||||
| 3.1 | Supply, Installation, Testing and Commissioning of AL powder coated Linear Supply Grill with dampers with all side Flanges & as per technical specifications.Supplying, Fixing, installation, testing and commissioning of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers in confirmation to SMACNA/IS and as per specifications complete etc. as required. | 5 | Sqmtr | - | - |
| 3.2 | Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete in confirmation to SMACNA/IS and as per specifications complete etc. as required. | 5 | Sqmtr | - | - |
| 4Electrical Work | |||||
| 4.1 | Supply installation of 5HP Three Phase 415 Volt Dol Control Panel with over load relay protection (4-9A) ,on/off indication, ameter voltmeter indication & with compleate control and power wiring. | 2 | Each | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
NITDOCUMENTS.pdf
Tender Documents • 2.51 MB
BOQ_961393.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].