Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.7 LAccepted-Finance | L1 | Accepted-Finance The lowest offer of M/s Subhendu Dash, Dhenkanal is reasonable and justified as per current market rates. | |
| 2 | L2₹3.3 L+₹64,741 (24.2%)Rejected-Finance | L2 | Rejected-Finance The offer of M/s Prachi Electricals, Bhubaneswar is on the higher side in comparison to the L1 bidder. |
Tender Value
₹6.9 L
EMD Value
₹6,935
Closing Date
22 May 2023, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer(E), BSNL ED, Cuttack
BSNL Electrical Division, 15 Cantonment Road, SSPO Building, 2nd Floor
Repairing of 2 nos HPAC units of Schneider(Uniflair) make
2023_BSNL_153522_1
NIT No- 26/BSNL/ED/CTC/2023-24
Open Tender
Electrical Works
Item Rate
30 days
Telephone Bhawan, Bajrakabati Road
3 documents required · 3 mandatory
₹590
A.O. Cash,BSNL,Office of PGMTD, Cuttack
₹6,935
Yes
26 May 2023
8 May 2023
24 May 2023
8 May 2023
22 May 2023
8 May 2023
8 May 2023 - 15 May 2023
Amount
Attending the break down call i/c inspection the Precision Package AC units ,testing the units ,detecting the fault & assessing the list of materials for repairing the units i/c rectification of minor faults ( i.e. without materials ) and restoration of PAC unit etc as reqd.
Dismantling of the indoor unit of the existing 7TR HPAC units installed in the 3rd Floor NGN Switch Room after disconnection of power supply, removing the sucction and discharge refrigirant copper pipes, electrical cables, watering pipes etc complete as required.
Shifting of the indoor unit of the HPAC unit i/c all accessories from the third floor NGN Room to 3 rd Floor NIB Room after dismantling of the Aluminium partition the help of required tools, plant and labour i/c making good the damages etc complete as required.
Installation,testing and commissioning of 7 TR Microprocessor controlled high Precision Package AC units complete with all associated accessories & components , Controls, vaccumization ,leak detection,nitrogen pressure testing etc complete as per required.
Providing and laying of seam less copper refrigerant pipe lines of following size having wall thickness not less than 1.2mm (18SWG) for liquid line and gas line, leak testing and pressure testing of refrigerant lines, vaccumising, and painting with red & yellow colour,fixing on existing on existing MS tray /wall suitable size clamp etc. complete as per specification as required.
Installation of existing 150 mm width x 50mm depth x 1.6mm thickness size of perforated M.S cable trays including horizontal and vertical bends ,reducers, Tees ,cross members and other accessories for laying of refrigerant pipes and cables and duly suspended from the ceiling/ on floor with M.S suspenders/angle iron supports on floor/wall including painting etc complete as required.
Laying following size of PVC insulated PVC sheathed armoured cable of 1.1 KV grade on the wall/existing trench, existing cable tray i/c interconnections end termination etc comlplete as required.
a)Three core 2.5 sq.mm copper conductor cable (PAC indoor unit to out door unit)
Providing and laying of following size UPVC pipe )along with all accessories for condensate drain water etc complete as required.
a) 40mm dia UPVC
Supplying & fixing of 7.0 TR scroll hermetic sealed type compressor in place of faulty compressor of make: DANFOSS, Model -HCM 109T4LC6/Emerson copeland having independent refrigerant circuit suitable for R407C refrigerant & suitable for operation on 3 phase 415V +10% Volts, 50Hz, AC supply etc. as reqd.
Supplying & fixing of Condenser Fan motor axial fan with Blade suitable for Uniflair/Schneider make HPAC units, 1350-1380 RPM, suitable for operation on 225-250 watt, 230Volt, 50 Hz AC supply with class F insulation i/c connection and testing etc. as required. ( Make -EBM PAPST, model: S4E450AQ5/REX model-RX4E-450S/High cool )
Supplying and charging / top up of refrigerant gas (R -407C) to the units complete etc. as required.
Replacement of Liquid line Filter Drier by new one i/c fixing and testing etc, as required. (Make- Danfos, Model-DCL 165 (5/8'/ Equivalent)
Replacement of High Pressure Release Switch by new one i/c fixing, connection and testing etc. as required. (Make: Danfoss-KP1 OR Equivalent: Auto Reset)
Thorough general servicing, checking, cleaning of evaporator filter /cooling coil and condenser coil of precision PAC units with recommended cleaning liquid and finally cleaning with water, drying etc. i/c re-fixing of cooling coil filters in the existing place etc complete as required.
M/S PRACHI ELECTRICALS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .