GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
GE UTILITY PLANT AND MACHINERY KIRBY PLACE DELHI CANTT-10
COMPREHENSIVE MAINTENANCE OF FIRE SUPPRESSION SYSTEM AND ADDRESSABLE FIRE ALARM SYSTEM ALIED ACCESSORIES FOR NEW/OLD SERVER ROOM DIPAC UNDER GE (U) PM DELHI CANTT-10
2021_MES_435158_3
GE(U)/PM/D-01/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
DELHI CANTT
MES contractor enlisted under class E category c(vi) having deposited standing security of Rs 50000 with department. Contractor not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category.
6 documents required · 6 mandatory
₹500
GE UTILITY PLANT AND MACHINERY DELHI CANTT-10
₹34,800
Yes
12 Aug 2021
18 Jun 2021
10 Jul 2021
18 Jun 2021
8 Jul 2021
25 Jun 2021
Amount
Section-I
Comprehensive maintenance of Gas based fire suppression system comprising 2X60 Kgs seamless cylinder with valves and all connected electromagnetic actuators and kit complete including MS seamless pipes as ASTMA 106-250 etc in old server room Automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. etc.and all as directed by Engr-In-Charge. The system comprising of following items as specified & directed by Engr-in-Charge. (a) Gas suppression system control panel (make Agni) - 01 No. (b) Gas Cylinder 60 Kg capacity - 02 Nos. (c) Solenoid valve - 02 Nos. (d) Smoke detectors - 12 Nos. (e) Gas Nozzle - 06 Nos. (f) Hooter - 01 No. (g) Gas abort push button - 01 No. (h) Gas release push button - 01 No. (j) SMF Battery 7AH - 02 Nos. (k) Steel hose pipe - 1 Lot. (l) Control wiring complete.
Comprehensive maintenance of Gas based fire suppression system SINOREX 1230 system comprising 2 X 90 Kgs seamless cylinder with valves and all connected electromagnetic actuators and kit complete including MS seamless pipes as ASTMA 106-250 etc in New server room Automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. etc. and all as directed by Engr-In-Charge. The system comprising of following items as specified & directed by Engr-in-Charge. (a) Gas suppression system control panel (make Ravel RE120GR) - 01 No. (b) Gas cylinder 90 kg capacity - 02 Nos. (c) Solenoid valve - 01 No. (d) Gas Nozzle - 03 Nos. (e) Hooter - 01 No. (f) Gas abort push button - 01 No. (g) Gas release push button - 01 No. (h) SMF Battery 26 AH - 02 Nos. (j) Steel hose pipe - 01 Lot. (k) Control wiring complete.
Comprehensive maintenance of microprocessor based net workable analogue adderssable type 1-2 fire alarm control panel expandable to 10 loops each loop are connected 252 analog addressable devices in one loop each loop are loaded to 90% of its full capacity including comprising hooter cum stoable red colour with 99 db sound output vesda detector for new server room. Automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required. etc. For New server room. The system comprising of following items as specified & directed by Engr-in-Charge. (a) Fire alarm system control panel (make Notifier) 01 No. (b) Smoke detectors - 18 Nos. (c) Response indicator - 13 Nos. (d) Hooter - 01 No. (e) Manual call point - 01 No. (f) VESDA panel - 01 No. (g) SMF Battery 26 AH - 02 Nos. (h) Air aspirator - 01 Lot. (j) Control wiring complete.
NOTE FOR ITEM NOS. 1.01 to 1.03 :- (a) Working Hrs: Monday to friday .Timings: 0900 Hrs to 1700 Hrs for monthly preventive maintenance. (b) If there is any complaint at day/night (including sunday & holidays) contractor / Auth rep of contractor /supervisor should rectify the same within four hours,failing which a penalty @ Rs.3000/-per day shall be imposed upon the contractor. (c) Weekly preventive maintenance will be carried out by qualified thechnician should least ITI holder and approved by Engr-in-charge and with minimum three years experience in the same field. (d) Monthly inspection & testing report shall be maintained. report shall be signed by MES representative & user weekly. (e) Items required for replacement /repairs shall be supplied by the contractor & cost of minor items such as nuts,bolts screws including replacement of spare parts of control panel ICs/rectifiers/LED etc and internal wiring of control panel are deemed to be included in the quoted rate. (f) Except filling of gas NAFS-125. (Gas filling by the department after refilling of cyclinder all electrical/solinied valve connections including of testing and commissioning deemed to be included in abovequoted rates.
Supply and fixing of intelligent addressable photoelectric type optical smoke detector including taking down old unserviceable one complete all as specified and as directed along with comprising the following:- Operating Voltage : 15-27 V DC Current : 200µA Alarm Current : 1mA Smoke sensitivity : 0.5-3.5& obscuration/ foot Operating temperature : 0o C – 49o C Humidity : 0-95% RH (Non condensing) Colour : White Housing : Polycarbonate Contact clamps : Stainless Steel Indications Normal : Green LED (Blinks during scan) Alarm : Red LES (Glow steady) (Make: Edward EST Model No SIGA2-PS or equivalent of SYSTEM SENSOR/ APPOLO/ HONEYWELL / NOTIFIER)
Rajindera Enterprises
GARG TRADERS
Continental Engineers and contractors
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .