Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.2 LAccepted-AOC 37 222 BUNDU KATRA AGRA UP | AGRA | UP | L1 | Accepted-AOC L1 | |
| 2 | L2₹37.4 L+₹2.3 L (6.61%)Rejected-AOC | L2 | Rejected-AOC L2 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
13 Sept 2024, 6:00 pmClosed
GE Bharatpur
GE Kanjoli line Bharatpur-321026
Repair maintenance of summer and winter cooling appliances and central air cooling system and repair to security light street light and connected items at RMS Dholpur under GE Bharatpur
2024_MES_667627_1
8404/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE Bharatpur
As per NIT
7 documents required · 7 mandatory
₹500
GE Bharatpur
₹80,000
Yes
16 Oct 2024
24 Jul 2024
16 Sept 2024
24 Jul 2024
13 Sept 2024
8 Aug 2024
25 Jul 2024 - 5 Aug 2024
Amount
Taking out and servicing of window/split type air conditioner cap- 1.5/2.0 Ton incluiding cleaning/removing all dust/mud, oil and other foreign particle with compressed air/water jet from grill, screen filter at indoor unit and condenser fin, evaporator fin at outdoor unit using detergent solution or chemical solution complete all as specified and directed . Note: Spare parts shall be measrured & paid separately under respective items.
M&L for flushing, pressurising the system , leakage testing, vacuumization and charging with refrigerant R -410/R-22 (suitable as per requirement) after rectifying leakage in the system vaccumising and dehydration as per standard practice including testing in all respect for folowing capacity split type air conditioner complete all as specified and directed.
1.5 Ton Capacity
2.0 Ton Capacity
S & F in replacement of following items for window/ Split AC of any capacity: (a) Compressor for AC Capacity- 1.5 Ton for window/split AC (as per site requirement) as per existing
Compressor for AC Capacity- 2.0Ton for window/split AC (as per site requirement) as per existing
Starting Capacitor 80-100 / 100-120 MFD,
Running Capacitor 36 MFD/ 45 MFD,
Screen filter of air conditioner of cap - 1.5 / 2.0 TR as per existing make.
Starting relay suitable for window and split type AC.
Thermostatic switch suitable for window/split type AC 1.5/2.0 Ton capacity of existing make.
Fan motor with fan blade unit suitable for 1.5 Ton capacity window /split type air conditioner of existing make.
Condenser's fan motor with blade suitable for split type air conditioner
Electronic panel board / PCB with display of Airconditioner cap- 1.5TR/2TR .
Plastic water drain hose pipe, 15mm dia and 2mtr long for spit type AC .
Remote control operating device for Window/Split type AC of 1.5/2.0 Ton with 02 Nos of pencil battery of existing make.
Copper tubes of size 4/8, 1/2 inch with aerofoam NBR rubber insulation tube .
Copper tubes of size 3/8,5/8, 1/4 inch with aerofoam NBR rubber insulation tube . (Note for Srl item No 5 to 5.2 here in before: Fixing shall be measured and paid under respective item)
stand for outdoor unit of existing size complete all as specified and directed.
Taking out old unsv and S & F indoor unit complete of existing make and size for split AC 1.5 TR complete all as specified and directed
Taking out old unsv and S & F outdoor unit complete of existing make and size for split AC 1.5 TR complete all as specified and directed
Shifting of AC of any type of AC capacity 1.5/2.0 Ton complete in & out door unit including taking out brackets, pipe line and fixing insulating pipelines including brazing of copper tubes, testing/commissioning complete, the shifting of service connection and voltage stabilizer to the new location complete all as specified and directed Note: The rates shall also include transportation, civil work and making good to the disturb surfaces.
Taking out and servicing of electric driven single phase water cooler of any cap incluiding cleaning/removing all dust/mud, oil and other foreign particle with compressed air/water jet using detergent solution or chemical solution ,leakage testing of refrigerant,storage tank leakage testing complete all as specified and directed . Note: Spare parts shall be measrured & paid separately under respective items.
Painting of water coolers of Cap - 80/120 Ltrs by cleaning old deteriorated exterior surface and necessary prepartion of surface by scrapping rust, grease, dirt etc before applying two coats of synthetic enamel paint of Make : Asian Paints Ltd ( Ist quality) or equivalent of approved colour by using spray painting technique to match with existing colour at existing location complete all as specified and directed
All as per Srl Item No 8 here in before but of Water cooler capacity 60/40 Ltrs.
M & L for flushing, pressurising the system , leakage testing vacuumization and charging with refrigerant R-134a at apprporiate pressure after rectifying leakage in the system vaccumising and dehydration including testing as per standard practice at site for water cooler of cap 80/120 ltrs complete all as specified and directed
All as per serial item No-10 above but of Water cooler capacity 80/40 Ltrs.
S & F in replacement of following items for water cooler of any capacity:
Compressor unit for water cooler 120/80 Ltrs of existing make or any other make apporved by GE mentioned in Appx.
Compressor unit for water cooler 60/40Ltrs of existing make or any other make apporved by GE mentioned in Appx.
Condenser fan motor with fan blade for water cooler of any Cap of existing make or any other make apporved by GE mentioned in Appx.
Capacitor 25/35 MFD, ISI marked.
Thermostat with knob as per existing size and make.
Relay with overload protection assembly
Magnetic rubber gasket of top cover as per existing size and make
Drain water tray of stainless steel by brazing/soldering the joints, vent pipes, outlet etc as per existing size and make
Pencil type strainer alongwith capillary tube suitable as per existing size and make.
Float valve PVC 15mm bore, heavy duty. complete all as specified and directed
chromium plated push cock size 15 mm suitable complete all as specified and directed
PVC flexible pipe size 40 mm dia with necessary clamping with jubli clips for drain water tray
PVC connection of size 15 mm dia 450mm long
M&L for storage tank leakage repair through brazzing/welding/silicon gel fiiling of any capacity water cooler complete all as specified
Taking out and servicing of electric driven single phase refrigerators and deep freezer of any cap incluiding cleaning/removing all dust/mud, oil and other foreign particle with compressed air/water jet using detergent solution or chemical solution ,leakage testing of refrigerant,freezer storage leakage testing complete all as specified and as directed . Note: Spare parts shall be measrured & paid separately under respective items.
M&L for flushing, pressurising the system , leakage testing, vacuumization and charging with refrigerant R -22/R-134a (suitable as per requirement) after rectifying leakage in the system vaccumising and dehydration as per standard practice including testing in all respect for Refrigerator/deep freezer of Cap - 170/190 Ltrs complete all as specified and as directed.
All as per serial item No 15 above here –in before but of capacity 265/280 Ltrs
All as per serial item No 15 above here –in before but of capacity 300-400 Ltrs
S & F in replacement of following items for refrigerator/deep frezer of any capacity:
Compressor unit for Regrigerator of cap 165-195Ltrs of existing make or any other make apporved by GE mentioned in Appx.
Compressor unit for Regrigerator of cap 200-320Ltrs
Compressor unit for Regrigerator/Deep freezer of cap 200-400Ltrs
Starting relay suitable for existing refrigerator. Make: SRIRAM or equivalent make approved by GE
Thermostatic switch auto defrost type with knob suitable for existing refrigerator
Bulb inside the refrigerator suitable for existing refrigerator
Magnetic rubber door gasket suitable for existing refrigerator
Push type door switch suitable for existing refrigerator
Door lock with two keys suitable for existing refrigerator
Overload protector suitable for refrigerator .
Strainer pencil type alongwith capillary tube suitable for refrigerator as per existing capacity
Electronic PCB for 260-400 Ltr refrigerator /Deep freezer
Taking out and servicing of desert cooler of any capacity i.e. checking of desert cooler fan motor, submersible pump, socket point, PVC connections,Fan blade, wooden chips etc including noting the complaints in compliant register complete all as specified and directed Note: Spare parts shall be measrured & paid separately under respective items.
Cutting burnt winding of fan motor of size upto 450mm sweep and rewinding with super enamelled copper winding wire and replacing gun metal bush shaft.complete
M&L for painting of desert cooler inner and outer surface with spray gun using one coat of red oxide and two coat of anti corrosive synthetic enamaled paint of approved brand as directed by Engr-in-charge
S & F of Fan Motor copper wound 16/18" sweep, 3 Speed single phase 230V AC supply complete with Blade complete all as specified and directed.
M & L for MS Bracket with mounting ring of cooler fan motor and mounting clamps/legs of existing size/model
S & F of PVC submersible Pump complete single phase 230V AC supply for desert cooler, 1 meter head or suitable to existing desert cooler. complete all as specified and directed
M & L for Side panel/shutter made out of 20 SWG GI sheet as per existing design and approved including handles (2 Nos.) duly welded / riveted
M & L for Bottam tank made out of 20 SWG GI sheet as per existing unserviceable tank
M & L for Top of the Desert Cooler made of 20 gauge GI Sheet riveted /bolted to match with existing.
S & F of PVC water distribution cup with PVC elbow and pipe for any size of cooler
S & F of Capacitor cap- 4/6 MFD, suitable for desert cooler as per existing size..
S & F in repair of Piano switch 5 amps one way
S & F in repair of 3 pin plug top 5 Amp.
M & L in repair for twin core 1.5 Sqmm copper conductor wire for internal wiring
S & F in repair of Float valve PVC 15mm bore, heavy duty. (Make: Prayag, Surya)
S & F in repair of PVC connection 45 cm long. (Make: Prayag)
S & F in repiar of PVC connection 60 cm long. (Make: Prayag)
M & L for Wooden chips pad of suitale size for desert cooler min 600gm in weight.
M&L for grass cooling pad 600gm each side for dessert coolers of suitable size with iron meshes all as specified and directed
M & L for PVC insulated and sheathed flexible 1100 volts grade 3 core multistranded copper conductor of size 2.5 sqmm.
S & F of 3 pin plug top 15 Amp single phase 230 volt complete all as specified and directed.
S & F of brass stop cock Stop valves, cast copper alloy, screwed down, high pressure,with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed suitable for 15 mm bore pipes complete
S & F of brass stop cock Stop valves, cast copper alloy, screwed down, high pressure,with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed suitable for 20 mm bore pipes complete
Taking out old unsv parts from Desert cooler and supply & fix new parts of desert cooler to make functioning of the same. (a) Desert ccoler body complete with front grill made out of GI sheet of overall dimension of desrt cooler 690X690X1020mm with mounting frame for fixing of cooler fan motor ,Air grill of suitable size made out of 0.5mm PGI sheet including GSS arrangement with a knob for easy and smooth movement, Front & Side panel made out of 1mm thick PGI sheet of suitable size and shape, Water tank height should not less than 11 inch made out of 1mm thk PGI sheet, wooden chips pad for three side shutters,Service cord of 3 Core copper wire 1.5 Sqmm with plug top 5 Amp length not less than 2 metres, Electronic fan dimmer 1000 watts AC 230 Volt for controlling the fan speed.
Supply & Fixing plywood 6mm thick with white mica sheet duly fixed in windows with screws for ventilation opening for desert cooler as per existing size complete all as specified and directed
M&L for fixing and grouting of MS Stand (adjustment type) suitable for desert cooler of cap 3000/4000CFM made out of angle iron section complete with two coats of synthetic enammled black paint over a coat of red oxide primer complete all as specified and directed
S&F in replacement GI pipe, 15 mm bore, medium grade, ISI marked with fittings laid in trenches or fixed to walls, ducts, floors etc incluiding necessary excavation and earth work complete for desert cooler/water cooler connections complete all as specified and directed
All as per Srl Item No 47 above here in before but of 20mm bore
S&F modular enclosure of single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 25 Amps, 240 volts. complete all as specified and directed
M&L concealed submain wiring complete with 6 Sqmm single core multi standred PVC insulated and sheathed cable FRLS copper conductor two runs and one run of 6 Sqmm copper cable for earth continuity conductor in and including drawn through PVC conduit size not less than 20 mm dia with all PVC accessories complete all as specified and directed
M&L concealed submain wiring complete with 4 Sqmm single core multi standred PVC insulated and sheathed cable FRLS copper conductor two runs and one run of 4 Sqmm copper cable for earth continuity conductor in and including drawn through PVC conduit size not less than 20 mm dia with all PVC accessories complete all as specified and directed
M & L for cleaning and removing dust particles inside the chamber of air washer container, disconnecting all electrical wires with proper termination and insulating the naked wires if any, removing unsv FASD starters etc and refitting the all removed and items after repairing/replacing at site as per the existing position complete all as specified and directed
M&L for dismantling the joints of each compartment of duct and cleaning of duct from air washer outlet to cadet's room opening of any length by using anti scaling spray, scrapping the foreign materials deposited on internal wall of the duct, opening the outlet grills, blowing air with high pressure through duct to get the deposited foreign materials by using external heavy duty compressor, applying oil spray inside the duct to prevent the sheet from corrosion with very thin layer, connecting all the compartments as per existing position, replacing gasket at all joints, complete all as specified and directed
M&L for replacing insulating layer over the duct to prevent from heat or any extreme weather by using synthetic foam or synthetic rubber and wrapping with garnison net or square threaded net around the insulation by using suitable solvent or compound to stick permanenty after dismantling the old UNSV insulation layer and scrapping the surface and cleaning properly before applying the new insulation layer complete all as specified and directed
M&L for checking all the water pipeline connections, repairing leakages from PVC storage tank to air washer system storage tank, welding the cracks or hole or fabricating with new sheet for 40mm GI drain out pipes, replacing end plug of drain system and over f;low system of bottom mount tank, checking the condition of float valves, cleaning the valve and refitting, leakage testing and rectifying in all respect in pipeline and existing tank and making fucntional at all cost complete all as specified and directed
S&F in repairing the following accessories of Air Washer:
DOL Starter of capacity 5HP suitable for three phase 3HP motors complete with on off push buttons and over current relay.
Rewinding 3/5HP motor of blower fan motor by using super enamelled copper conductor wire solid in nature, grade 1 quality, incl dismantling/assembling and transporting etc. and refixing after repairing and replacing of UNSV parts such as housing/nuts bolts etc
S&F bearing of motor suitable for 5HP Make CG, in repairing incl taking out old UNSV , applying suitable grease and test run etc all as specified and directed.
supply and fix in repair cassete filter of size 2x2 feet 50 mm thick complete all as specified
Supply and fix motor fan belt of suitable size genuine part from the Air systems all as specified and directed.
Supply and fix in repairing compartment door of Mild Steel of size 27.5 inch x 55.5 inchx 1 inch, with AHU door locking arrangements, hand lock and key, painting of metal primer and two coat super enamel paint with existing colour and finish includng removing of UNSV door etc complete all as specified and directed
Supply and fix submersibble pump set of 32/40 watt of output 3200 L/H , 220V, 50 Hz for a height of min 2.8 mtr complete all as specified and directed
S&F PVC float valve of size 25mm/20mm as required on site including rod and ball in replacement of old UNSV one and testing complete all as specified and directed
S&F PVC pipe in replace ment of UNSV and broken of size 25mm with suitable compound for jointing over the pump outlet including all kind of accessorie complete all as specified and directed
S&F of PVC valve 25mm size along with PVC union in replacement of old UNSV one complete all as specified and directed
S&F in replacement of air filtration pad( compact honey pad), 1.22m x 1.22m corrugated, thin sponge layer consisting, of paper membrane as one layer, net cloth as second layer and foam as third layer suitable to filter the inlet air entering into the air washer system while running the plant of dimension 1.22m x 1.22m of thichness 8 inch or as per existing size suitable for air washer system including fixing pad, nuts bolts and accessories etc complete all as specified and directed
S&F 3 HP fan motor 3ph i.e. having operating voltage of 415V with super enamel copper winding metal body as per existing make complete all as specified and directed
M&L for PCC (1:2:4) type B2 with using 40mm graded aggregate as in foundation and mass filling concrete for poles/Stay wires/ LT panel boards and in addition where ever directed by Engr-in-Charge .
S&F Voltage stabilizer for automatic operation, single phase, naturally air cooled indoor type, designed for input variation between 170V to 250V with output voltage stabilized at 230V, with accuracy +/- 2.5% of capcity 5KVA fixed on wall or any location as directed including connected accessories complete all as specified and directed
S&F Voltage stabilizer for automatic operation, single phase, naturally air cooled indoor type, designed for input variation between 170V to 250V with output voltage stabilized at 230V, with accuracy +/- 2.5% of capcity 4KVA fixed on wall or any location as directed including connected accessories complete all as specified and directed
labour only for day to day complaints of all cooling appliance AC,water cooler ,refrigerator,desert cooler,deepfreezer etc including servicing any type and size complete all as specified and directed
Taking out old Existing U/S MCCB from LT panels/ Feeder piller of following capacity and replace with new MCCBs without damaging the LT panel board or any assets associated with the installation. (a) Supply and fix MCCB 4 Pole, 415 V, with Microprocessor release 160 Amps with breaking capacity 36 KA complete all as specified and directed
Supply and fix MCCB 4 Pole, 415 V, with Microprocessor release 250 Amps with breaking capacity 36 KA complete all as specified and directed
Supply and fix MCCB 4 Pole, 415 V, with Microprocessor release 63 Amps with breaking capacity 36 KA complete all as specified and directed
Supply and fix MCCB 4 Pole, 415 V, with Microprocessor release 100 Amps with breaking capacity 36 KA complete all as specified and directed
Taking out old UNSV LT UG cable of any make & sizeof 10/16 sqmm 2 core complete all as specified and directed
Taking out old UNSV LT UG cable of any make & size of 25/50sqmm 4 core complete all as specified and directed
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel stripped or wire armoured electric cable heavy duty with stranded aluminium conductor , 1100Volts grade of size 50 Sqmm 3.5core for air cooling system complete all as specified and directed
All as per Item No-64 here-in-before but of size 25 sqmmx 4 core
All as per Item No-64 here-in-before but of size 16 sqmmx 4 core
All as per Item No-64 here-in-before but of size 10 sqmmx 2 core
Excavation in trenches not exc 1.5 m in depth and not exc 1.5 m wide for taking out/laying LT UG cable, and getting out in hard disintegrated layer complete all as specified and directed.
Excavation in trenches, exc1.5 Mtr wide but n. exc 3Mtr in depth for foundation/laying of cable and getting out in soft disintigrated rock/any type of soil complete all as specified and directed.
Removing excavation soil at a distance not exc 50 m and deposited where directed complete all as specified and directed.
Returning,filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
Supply and laying of unburnt Sub class B Bricks in trenches over the LT/HT cables for the protection of cables, laid across the length complete all as specified and directed.
M &L local river sand for bedding and sand cushioning of all HT/LT UG cable complete all as specified and directed.
Labour for cleaning of solar plate(2x1m) complete all as specified and directed.
M&L for top up of distilled water in battery complete all as specified and directed.
M&L pipe galvanized iron medium grade of 25 mm dia complete with all fittings and fixed complete to wall or ceiling or laid in floor jointed tested and commissioned including taking down old pipe line complete all as specified and directed.
Material and labour for rotational moulded polyethylene water storage tank 1000ltrs (cylindrical vertical with closed top ) hoisted including taking out old pvc tank and fixed in position including float valve complete all as specified and directed.
Supply and install in replacement and commissioning and testing factory made and tested (includng CPRI certified) LT panel box (KIOSK) out door type platform mounted suitable for 415 volt , 3 phase, 4 wire , 50 Hz AC supply system all as specified and directed having busbar chamber with insulated AL bus bars 400 amps rating installed on percelain insulators, the panel shall be dust and vermin proof double door made of 3.15 mm CRCA MS sheet outer & inner 3.15 mm thick and individual compartment for MCCB/MCB & volt/Amps meter and 40 x 40 x 6 mm thick angle iron for base frame work.including change over 160amp.The complete feeder pillar box should be power coated including internal wiring with PVC insulated solid copper conductor FRLS cables appropriate size but not less than 4 Sqmm. Front opening type with approx for cable entry with double door shutter including locking arrangement as per manufacturers with 2 Keys. The scope of work includes provn of the followings :- Incoming:- (a) MCCB TPN- 250 Amps - 01 Nos. (b) Bus bar Al TPN 400 Amps - 01set. Outgoing (a) MCCB TPN 100 AMP 25KA -04 nos
M&L for PCC (1:3:6) type C1 using 40mm grade stone aggregate in foundation and mass concrete for poles including necessary form work complete all as specified and directed by Engg in charge.
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate in coping of existing/new poles / foundation for poles, struts, posts etc including necessary form work, finished the exposed surfaces fair and even without using extra cement complete all as specified and directed.
Supplying, errecting and fixing steel tubular swaged poles with cast iron base plate of size 300mm x 300mm x 6mm, finial taper plug, bolts, nuts & screws for type 410 SP-31 (9.0 metres long) including painting with two coats of aluminium paint over one coat of redoxide primer on all exposed surfaces and tarring with black bituminous paints to embedded portion in PCC and providing 3 Nos of 30cm wide circular bands alternate with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide including taking down old unserviceable PCC poles of any type complete all as specified and directed. Note: Excavation, earth work, PCC in foundation and coping shall be measured and paid separately under relevant item of this schedule.
Supply only LED surge protector multiple type 2 surge arrestors with thermal monitaring device and connector,dual visual fault indicator for the discharge path of the supply voltage and control the phase
Supply only LED drivers rated voltage 12/24 volt max out put power Panel Driver 15 W / 18 W
Supply only LED drivers rated voltage 12/24 volt max out put power 45 W
Supply only LED drivers rated voltage 12/24 volt max out put power 70 W
Supply only LED drivers rated voltage 12/24 volt max out put power 90 W
Servicing of existing solar lights panels of any capacity , removal of dust , cleaning of solar panels thoroughly , tighening of any loose fixing arrangement, opening of main body and cleaning of debris , replacement of burnt wire , repainting the outer body with camouflage complete all as specified and directed. Add Note:- Cost of small spare parts required for servicing shall be included in quoted note.
S & F street light GI bracket of 1.5 mtr long made out of 40mm dia light grade GI pipe bend to shape of 120 degree end welded at required including 02 Nos MS clamp of FL 40 x 6mm including nuts bolts & washers complete necessary fixing arrangements on pole and including Dismantling old U/S GI bracket of any size & length.as directed.
S & F in replacement 4 sqmm solid conductor 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed twin core cable flat or circular from junction box to fitting complete all as specified and directed by Engg in charge.
Taking out old UNSV GI Pipe of any make & size complete all as specified and directed by Engg in charge.
S & F or laying in replacement galvanised steel tubing Light grade (ISI marked) for protection of under ground cable on poles/walls under road crossing of size 40 mm borecomplete all as specified and directed by Engg in charge.
S&F in replacement of 50 mm dia steel tubes (light grade) galvanised with fittings, laid in trenches / wall for protection of underground cable when crossing the road complete all as specified and directed .
Supply, install, test and commissioning factory made THERMOPLASTIC/HDPE CABLE JUNCTION BOXES IP 66/67 “weather proof”, with terminals for outdoor installation (with knockouts for cable entry) of size 280 x 170 x 105 mm depth with cable entry size of 10-25 sqmm with 4 No. busbar of capacity 63 Amp and MCB SP 6 Amp-1 No.of make sintex each, with flat iron clamps of size 30 x 6mm, nuts and bolts complete including taking down all as specified and directed.
S&F in repair on existing location including taking out of existing MCCBs of following capacity :-
MCCB 415 volts 125 Amps 04 pole 16 KA
MCCB 415 volts 100 Amps 04 pole 16 KA
MCCB 415 volts 63 Amps 04 pole 16 KA
S&F in replacement of 3 Pole 40 Amp power contactor, AC 3 rating, fixed in existing panel & connecting complete all as specified and directed.
S&F of "lithium based Energy Efficient Integrated Solar Street Light of 40 Watt"in Single FRP body with duly Polyurethane coating , encases with Monocrystaline Solar PV Panel of 65-67 Wp, Lithium Battery 11.1/12.8V, 33/36AH with inbuilt BMS, IP 65, high brightness, CRI>70, Color temperature 5700-6500K, Microcontroller based charge controller cum driver, automatic dimming function, Dusk to Dawn Operation, suitable to working temperature:(-) 10 degree celcius to (+) 55 degree celcius, weight not more than 16- 18 Kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protection: Short Circuit, overload, Reverse polarity and battery protections complete including taking down complete all as specified and directed.
Re-stringing ACSR conductor of street light feeder (1ph and neutral) any type size stringing properly on insulator and binding with aluminium tape/connectors, jumpers etc drawing as OH/LT line including dismantling/taking down old u/s ACSR conductor from poles including jumper and cable connection etc complete all as specified and directed.
S&F in replacement timer switch 24Hrs Analog dial type suitable for street lights and high mast lights with complete assembly 63Amps capacity, comprising one contactor of 40Amp and one MCB TPN of 40Amp, outdoor type with enclosure and clamping arrangements including taking out the old UNSV one any size and type complete all as specified and directed.
Material and labour for renewal of copper Earthing complete with copper earth plate electrode of size 60x60cmx5mm thick buried directly in ground (earth pit should not less than 4 mtr deep below normal ground level ) with top edge of the plate not less than 2.95 mtr deep below normal ground connected to and included copper earth strip 20mmx 3mm by means of copper bolts nuts check nuts and washer returning and filling the pits with excaviated vsoil mixing with charcoal 250 kg crystal salt 200 kg magnisiun sulphate of 100 kg and vegitable soil all around the plate up to 350 mm above from top edge of plate and balence portion filling with excaviated soil in layers not exc 25 mm thick 25 mm bore galvanised iron medium grade watering pipe up to top of plate 50mm bore galvanised iron light grade pipe for earth strip protection including all excavation earth work in any type of soil pcc 1;3;6 type c1 ....for chamber of internal size 300mmx 300mmx300mm with 120mm thick wall and 700mmx700mmx150mm thick bed concreat RCC 1:2:4 ,type b1 for precast chamber cover 50mm thick reinforced with welded steel wire fabric orxPM jali (weight not less than 4.00 kg/sqmm) ,funnel,with wire mesh complete all as specied and directed. Note (i) Quoted rate shall be deemed to include for earth strip with protection pipe up to 7.5 M length
M&L of painting of pole intially with single coats of primer paint on exposed surfaces after scraping old deterirorated paint and after that providing 3 Nos of 30cm wide circular bands with black & yellow paint starting from plinth level at a gap of 30 cm in between 2 bands and numbering of poles, in yellow paint over black painted back ground at a height of 2m from bottom of pole with 5 cm large bold letters 2" (inch) wide complete all as specified and directed by Engg in charge.
Taking down and S&F 200 watts LED flood light fitings new generation energy saving, environmental friendly, long life, versatile pressure die cast aluminium IP66 with 10KV surge protection road way, luminaire with high power LED as light source and suitable drivers etc to complete all as specified and directed.
S&F 70 watts LED street light fitings new generation energy saving, environmental friendly, long life, versatile pressure die cast aluminium IP66 with 10KV surge protection road way, luminaire with high power LED as light source and suitable drivers etc including taking down to complete all as specified and directed.
Taking down and S&F 60 watts LED street light fitings new generation energy saving, environmental friendly, long life, versatile pressure die cast aluminium IP66 with 10KV surge protection road way, luminaire with high power LED as light source and suitable drivers etc to complete all as specified and directed.
M&L for road cutting in 300mm width & 450 mm depth & repair to existing with bitumen premixed incl 150 mm BM complete all as specified and directed.
M&L for Cutting, trimming and prunning of trees, branches of any girth all around existing LT over head lines including cleaning the disturbed area beneath the LT overhead lines/LT Poles and removing the creepers/climbers tree branches and debris from site and depositing where directed at site. .
M&L for Servicing of complete high mast of any make any model, cap, height by greasing of wire rope, winch, motor with complete function, proper connection of light fittings in lantern carrage, cleaning & proper connection of High mast panel complete all as specified and directed.
Supply and fix / draw PVC insulated and sheathed trailing cable copper conductor cable of size 2.5 Sqmm 5 core, EPR PCP round cable 1100 volt grade. Including taking down old cables complete all as specified and directed.
Dismanting and taking down of U/S electric motor of cap 01 HP AC 3 Phase of high mast light repairing including cutting and taking out the old winding wires, cleaning the slots, rewinding the motor with appropriate size of super insulated copper conductor winding wire of same gauge, and varnishing complete including replacing the worn out bearing reassembling the motor fixing in same position and testing complete all as specified and directed.
Supply only wire rope of high mast light from winch to top made out of stainless steel grade AISI 316 sutable for taking min 750 kg load / as per existing rope size including taking down complete all as specified and directed.
Supply and fix MCB’s tripple pole & neutral 63 Amps, 415 volts with ‘C’ curve, fixed in sheet metal board complete including taking down complete all as specified and directed.
Supply and fix MCB’s single pole 6-32 Amps, 230 volts with ‘C’ curve, fixed in sheet metal board complete including taking down complete all as specified and directed.
Supply jointing connecting in repair and testing, straight through joint, epoxy based complete with jointing material and all standard accessories suitable for XLPE insulated armoured aluminium conductor cable, LT 1100 Volts, aluminium conductor of 10/16/25 Sqmm suitable for 3.5/ 4 core complete all as specified and directed.
M/S MAKHIJA TRADERS (BID ID -3092072)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .