Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹29.1 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹37.0 L+₹7.2 L (24.1%)Rejected-Finance NEAR AVON PUBLIC SCHOOL DABHANW POST DANDI NAINI PRAYAGRAJ 211008 | PRAYAGRAJ | PRAYAGRAJ | UTTAR PRADESH | 211008 | L2 | Rejected-Finance Being Higher Bidder | |
| 3 | L3₹41.1 L+₹11.4 L (38.1%)Rejected-Finance | L3 | Rejected-Finance Being Higher Bidder | |
| 4 | L4₹45.0 L+₹15.2 L (51.1%)Rejected-Finance | L4 | Rejected-Finance Being Higher Bidder | |
| 5 | Rejected-Technical | - | Rejected-Technical No, as per WLR |
Tender Value
₹47.8 L
EMD Value
₹95,500
Closing Date
12 Feb 2022, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
REPAIR/MAINT AND SERVICING OF VARIOUS CAPACITY OF DG SETS AND CONNECTED WORKS AND INTERNAL WIRING, FITTINGS, SECURITY LIGHTS AND OTHER RELATED WORKS AT VARIOUS DG SETS INSTALLATIONS IN THE AREA OF AGE E/M EXT (ELECT) UNDER GE E/M LUCKNOW
2021_MES_498462_2
8200/74/EM/Ext(Elect)/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Lucknow
Class D or above category b (i)
8 documents required · 8 mandatory
₹500
GE E/M Lucknow
₹95,500
Yes
14 Mar 2022
29 Jan 2022
14 Feb 2022
29 Jan 2022
12 Feb 2022
31 Jan 2022
Amount
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 250/350 KVA such as injector & valve tappet setting, checking of vibration damper, turbocharger, oil leakage, tightening mounting screws & nuts, filters & oil, inlet & Exhaust manifold capscrews, fan hub & water pump, radiator inside with solution i.e restore plus, outside thoroughly with solution(castic soda with water), and removing the old unserviceable defective parts & engine oil, coolant with and including trial & testing complete all as specified and directed. (Note- (i) New parts & oil shall be measured and paid separately under respective items as supply only. (ii) If required any other checking as per manufacturer' instruction and materials which are not mentioned here-in-after shall be included in the unit rate )
(a) Supply only lubrication oil filter for 250/350 KVA DG sets as per existing make/model/type
(b) Supply only paper bypass filter for 250/350 KVA DG sets as per existing make/model/type
(c)Supply only fuel filter for 250/350 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 250/350 KVA DG Sets as per existing make/model/type
(e) Suply only air cleaner outer for 250/350 KVA DG Sets as per existing make/model/type
(f) Supply Filter screen for 250 /350 KVA DG Sets as existing make/model/type
Material and Labour for checking of fan hub including minor repairs if any for 320/250 KVA DG set and checking for alignment complete all as specified and directed.
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 200 KVA such as injector & valve tappet setting, checking of vibration damper, turbocharger, oil leakage, tightening mounting screws & nuts, filters & oil, inlet & Exhaust manifold capscrews, checking of fan hub & water pump, radiator inside with solution i.e restore plus, outside thoroughly with solution(castic soda with water), and removing the old unserviceable defective parts & engine oil, coolant with and including trial & testing complete all as specified and directed. (Note- (i) New parts & oil shall be measured and paid separately under respective items as supply only. (ii) If required any other checking as per manufacturer' instruction and materials which are not mentioned here-in-after shall be included in the unit rate )
(a) Supply only lubrication oil filter for 200 KVA DG sets as per existing make/model/type
(b) Supply only paper bypass filter for 200 KVA DG sets as per existing make/model/type
© Supply only fuel filter for 200 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 200 KVA DG Sets as per existing make/model/type
(e) Supply only air cleaner outer for 200 KVA DG Sets as per existing make/model/type
(f) Supply only Filter screen for 200 KVA DG Sets as per existing make/model/type
Material and Labour for checking of fan hub including minor repairs if any for 200 KVA DG set and checking for alignment complete all as specified and directed.
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 100/110/125 KVA such as injector & valve tappet setting, checking of vibration damper, turbocharger, oil leakage, tightening mounting screws & nuts, filters & oil, inlet & Exhaust manifold capscrews, fan hub & water pump, radiator inside with solution i.e restore plus, outside thoroughly with solution(castic soda with water), and removing the old unserviceable defective parts & engine oil, coolant with and including trial & testing complete all as specified and directed. (Note- (i) New parts & oil shall be measured and paid separately under respective items as supply only. (ii) If required any other checking as per manufacturer' instruction and materials which are not mentioned here-in-after shall be included in the unit rate )
(a) Supply only lubrication oil filter for 100/110/125 KVA DG sets as per existing make/model/type
(b) Supply only paper bypass filter for 100/110/125 KVA DG sets as per existing make/model/type
© Supply only fuel filter for 100/110/125 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 100/110/125 KVA DG Sets as per existing make/model/type
(e) Supply only air cleaner outer for 100/110/125 KVA DG Sets as per existing make/model/type
(f) Supply only Filter screen for 100/110/125 KVA DG Sets as per existing make/model/type
Material and Labour for checking of fan hub including minor repairs if any for 100/110/125 KVA DG Sets and checking for alignment complete all as specified and directed.
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 62.5/63/82.5 KVA such as injector & valve tappet setting, checking of vibration damper, turbocharger, oil leakage, tightening mounting screws & nuts, filters & oil, inlet & Exhaust manifold capscrews, fan hub & water pump, radiator inside with solution i.e restore plus, outside thoroughly with solution(castic soda with water), and removing the old unserviceable defective parts & engine oil, coolant with and including trial & testing complete all as specified and directed. ((Note- (i) New parts & oil shall be measured and paid separately under respective items as supply only. (ii) If required any other checking as per manufacturer' instruction and materials which are not mentioned here-in-after shall be included in the unit rate )
(a) Supply only lubrication oil filter for 62.5/63/82.5 KVA DG sets as per existing make/model/type
(b) Supply only paper bypass filter for 62.5/63/82.5 KVA DG sets as per existing make/model/type
© Supply only fuel filter for 62.5/63/82.5 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 62.5/63/82.5 KVA DG Sets as per existing make/model/type
(e) Supply only air cleaner outer for 62.5/63/82.5 KVA DG Sets as per existing make/model/type
(f) Supply only Filter screen for 62.5/63/82.5 KVA DG Sets as per existing make/model/type
Material and Labour for checking of fan hub including minor repairs if any for 62.5/63/82.5 KVA DG Sets and checking for alignment complete all as specified and directed.
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 30/40 KVA such as injector & valve tappet setting, checking of vibration damper, turbocharger, oil leakage, tightening mounting screws & nuts, filters & oil, inlet & Exhaust manifold capscrews, fan hub & water pump, radiator inside with solution i.e restore plus, outside thoroughly with solution(castic soda with water), and removing the old unserviceable defective parts & engine oil, coolant with and including trial & testing complete all as specified and directed. (Note- (i) New parts & oil shall be measured and paid separately under respective items as supply only. (ii) If required any other checking as per manufacturer' instruction and materials which are not mentioned here-in-after shall be included in the unit rate )
(a) Supply only lubrication oil filter for 30/40 KVA DG sets as per exissting make/model/type
(b) Supply only paper bypass filter for 30/40 KVA DG sets as per existging make/model/type
© Supply only fuel filter for 30/40 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 30/40 KVA DG Sets as per existing make/model/type
(e) Supply only air cleaner outer for 30/40 KVA DG Sets as per existing make/model/type
(f) Supply only Filter screen for 30/40 KVA DG Sets as per existing make/model/type
Material and Labour for checking of fan hub including minor repairs if any for 30/40 KVA DG Sets and checking for alignment complete all as specified and directed
Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 15/20/25 KVA such as injector & valve tappet setting, checking of vibration damper, turbocharger, oil leakage, tightening mounting screws & nuts, filters & oil, inlet & Exhaust manifold capscrews, fan hub & water pump, radiator inside with solution i.e restore plus, outside thoroughly with solution(castic soda with water), and removing the old unserviceable defective parts & engine oil, coolant with and including trial & testing complete all as specified and directed. (Note- (i) New parts & oil shall be measured and paid separately under respective items as supply only. (ii) If required any other checking as per manufacturer' instruction and materials which are not mentioned here-in-after shall be included in the unit rate )
(a) Supply only lubrication oil filter for 15/20/25 KVA DG sets as per existing make/model/type
(b) Supply only paper bypass filter for 15/20/25 KVA DG sets as per existing make/model/type
© Supply only fuel filter for 15/20/25 KVA DG Sets as per existing make/model/type
(d) Supply only air cleaner inner for 15/20/25 KVA DG Sets as per existing make/model/type
(e) Supply only air cleaner outer for 15/20/25 KVA DG Sets as per existing make/model/type
(f) Supply only Filter screen for 15/20/25 KVA DG Sets as per existing make/model/type
Material and Labour for checking of fan hub including minor repairs if any for 15/20/25 KVA DG Sets and checking for alignment complete all as specified by Engineer-in-Charge
Taking down radiator from Gen set of capacity 200/250/320 KVA after disconnecting the water connecting pipe and descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete with and including replacement of coolant solution and hose radiator with clips complete all as specified and directed.
Taking down radiator from Gen set of capacity 100/110/125 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete with and including replacement of coolant solution and hose radiator with clips complete all as apecified and directed.
Taking down radiator from Gen set of capacity 62.5/63/82.5 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as directed.
Taking down radiator from Gen set of capacity 30/40 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete with and including replacement of coolant solution and hose radiator with clips complete all as specified and directed.
Taking down radiator from Gen set of capacity 15/20/25 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as directed .
Dismantling and taking out Dynamo/alternator assembly of 12 Volts/24 Volts from the DG sets replacing the spare parts such as carbon brushes, springs, spring holders, brushes, bearings or any other part required for full functioning of machine and fixing and testing complete as specified and directed.
Dismantling and taking out dynamo/alternators from DG set for rewinding and taking out the old coil, cleaning thoroughly and wound with new super enameled copper cord of existing size and gauge, varnishing, drying, heating as per manufacturer norms and fixed with dynamo/alternator properly testing and commissioning cpmplete all as specified and directed.
S&F in replacement of radiator hoses of any size and any capacity of DG set and fixed properly with new jublee clips, clamps, nuts and testing complete as specified and directed.
Dismantling and taking out the FIP (PT Pump Assy) for repairing by replacing the worn out gasket, filter, suction valve, discharge valve and fixing the same after calibration and testing of capacity 200 KVA / 250 KVA/320KVA DG set. complete all as specified and directed.(Note : Repairing & Calibration shall be carried out by authorised dealers only)
As per item No 57 above but for DG set of capacity 125KVA/110KVA /100KVA
As per item No 57 above but for DG set of capacity 82.5KVA/63KVA /62.5KVA
As per item No 57 above but for DG set of capacity 40KVA/30KVA/25KVA /20KVA /15KVA
M&L in repair overhauling/calibration of injector assembly for any make/model/capacity of DG sets including renewal of wornout parts such as copper gasket, injector nozzle and testing complete all as specified and directed.(Note :- Repairing/Calibration shall be carried out by authorised dealer only).
S&F in replacement of oil pressure gauge as per existing make/model/ capacity of any type of DG sets complete as specified and directed,.
S&F in repair AVR unit /CVR –II for 320/250/200 DG Set & testing etc of existing make complete as specified and directed.
S&F in repair AVR unit /CVR –II for 125KVA/110KVA/100KVA DG Set and testing etc of existing make complete as directed by Engr-in-charge.
S&F in repair AVR unit /CVR –II for 82.5KVA/63KVA/62.5KVA DG Set and testing of existing make complete as directed .
S&F in repair AVR unit /CVR –II for 40KVA/30KVA/25KVA/20KVA/15 KVA DG Set and testing etc of existing make complete as directed.
Dismantling and taking out of defective water pump assembly from the the DG sets and supply and fix new water pump assembly for the DG sets of capacity 320/250KVA/200KVA with and including testing complete all as specified directed.
Dismantling and taking out of defective water pump assembly from the the DG sets and supply and fix new water pump assembly for the DG sets of capacity 125KVA/110KVA/100KVA incl testing complete all as specified and directed.
Dismantling and taking out of defective water pump assembly from the the DG sets and supply and fix in repairs new water pump assembly for the DG sets of capacity 82.5KVA/63KVA/62.5KVA iwith and including testing complete all as specified directed.
Dismantling and taking out of defective water pump assembly from the the DG sets and supply and fix in repairs new water pump assembly for the DG sets of capacity 40KVA/30KVA/25KVA/20KVA/15 KVA iwith and including testing complete all as specified directed.
Dismantling and taking out the water body pump assembly complete from the DG set upto capacity 62.5 KVA at site and transporting to the work shop for repair and refixed the same after repiar & testing complete after replaement of the following parts:-. (a) Over hauling of water body pump complete - 01 Job, (b) Supply and fix water body kit complete- 01 Set, (c) water body bearing - 02 Nos, (d) water body Hose- 01 Set,
Dismantling and taking out the water body pump assembly complete from the DG set upto capacity 82.5 KVA to 125 at site and transporting to the work shop for repair and refixed the same after repiar & testing complete after replaement of the following parts:-. (a) Over hauling of water body pump complete - 01 Job, (b) Supply and fix water body kit complete- 01 Set, (c) water body bearing - 02 Nos, (d) water body Hose- 01 Set,
Dismantling and taking out the water body pump assembly complete from the DG set upto capacity 200 to 320 KVA at site and transporting to the work shop for repair and refixed the same after repiar & testing complete after replaement of the following parts:-. (a) Over hauling of water body pump complete - 01 Job, (b) Supply and fix water body kit complete- 01 Set, (c) water body bearing - 02 Nos, (d) water body Hose- 01 Set,
S&F in replacement battery terminals made of brass superior quality etc complete all as specified and directed.
Dismantling and taking out the dfective self starter assembly of any capacity (12V/24V) form the DG set and re-fixing the same after repair works including replacing the spare parts such as carbon brushes, springs, spring holder bushes, bearings, or any other spare part not mentioned herein but essentially required for proper functioning of the starter assembly complete all as specified and directed.
Dismantling and taking out self starter from DG set and taking out unserviceable old coil , cleaning thoroughly slot and rewinding the starter with super enameled copper conductor of existing size and gauge incl varnishing drying, heating and re-fixing the same after repair with and including testing complete all as specified directed.
S&F in replacement flexible pressure hose for lubricant oil and fuel for any size/capacity/model/make of DG set complete all as specified and directed.
S&F in replacement PVC heavy duty transparent pipe of size 10 mm dia for Diesel tank indicator with suitable clamps fixed on any type of tank complete all as specified and directed.
S&F in replacement belt fan drive for DG sets of 320/250/200 KVA capacity complete all as specified directed.
S&F in replacement belt fan drive for DG sets of 125/110/100 KVA capacity complete all as specified and directed
S&F in replacement belt fan drive for DG sets of 82.5/62.5/63 KVA capacity complete all as specified and directed.
S&F in replacement belt tensioner for DG sets of 320/250/200 KVA capacity complete all as specified and directed
S&F in replacement belt tensioner for DG sets of 125/110/100 KVA capacity complete all as soecified and directed.
S&F in replacement belt tensioner for DG sets of 82.5/62.5/63 KVA capacity complete all as specified and directed
S&F in replacement oil pressure cut out suitable for any model/make of DG set upto 250 KVA complete all as specified and directed.
S&F in replacement water temperature cut out suitable for any model/make of DG set upto 250 KVA.icomplete all as specified and directed.
S&F in replacement ignition switch and key for DG sets of 250/200 KVA capacity complete all as specified and directed.
Dismantling the radiator of 320/250/200 KVA DG set its position and soldering of copper pipes, where leakage with and including complete repair and rectifying leaks & cleaning radiator and PVC hose and fitting the same place and testing complete all as specified and directed.
Dismantling the radiator of 125/110/100 KVA DG set its position and soldering of copper pipes, where leakage with and including complete repair and rectifying leaks & cleaning radiator and PVC hose and fitting the same place and testing complete all as specified and directed.
Dismantling the radiator of 82.5 to 15 KVA DG set its position and soldering of copper pipes, where leakage incl rectifying leaks & cleaning radiator and PVC hose and fitting the same place and testing complete as specified
M&L for draining out old engine/lubrication oil from chamber of the DG sets, cleaning of chamber thoroughly and filling new engine/lubrication oil of grade 15W40 complete all as specified and directed.
M&L for draining out old engine/lubrication oil from chamber of the DG sets, cleaning of chamber thoroughly and filling new engine/lubrication oil of grade 20W40 complete all as specified and directed.
Supply and fixing in repair rotating rectifier assembly for 320/250/200 KVA DG set of any make and model complete all as specified and directed.
Supply and fixing in repair rotating rectifier assembly upto 125/110/100 KVA DG set of any make and model complete all as specified and directed.
Supply and fixing in repair rotating rectifier assembly upto 82.5/63/62.5 KVA DG set of any make and modelcomplete all as specified and directed.
Dismatling defective coupling assembly from the alternator & engine any capacity and make of DG set and carrying out the required repair works/renewal of spare for proper functioning of the alternator and re-fixing the same complete all as specified and directed.
M&L for in repairing/renewal of the existing broken/leaking PVC fuel over flow pipe of the DG sets of any capacity upto fuel tank placed externally from the DG sets complete all as specified and directed.
S&F in replacement rectifier diode for 250/200 KVA DG sets as per exising make/model/ size complete all as specified and directed
S&F in replacement rectifier diode for 125/110/100 KVA DG sets as per exising make/ model /size complete as specified and directed
S&F in replacement rectifier diode for DG sets upto 82.5 KVA capacity as per exising make/size/ model complete as specified and directed
S&F in replacement voltmeter square/ round upto 500 Volts of existing size. Make : MECO/AE complete all as specified and directed
S&F in replacement ammeter 0-300A as per existing size/make/model complete all as specified and directed
S&F in replacement indicator lamp assembly 230/110 Volts as per existing make/model/size etc complete as specified and directed
S&F in replacement battery leads 95 Sqmm copper cable 1.5 Mtr long with brass terminals etc complete as specified and directed.
S&F in replacement techometer as per existing size/make/model complete all as specified and directed.
S&F in replacement techometer cable in and out with adopters etc complete as per exisiting size/make/model complete as specified and dirrected
S&F in replacement asbestos rope 20mm dia for tightly covered the silencer exhaust pipe etc complete as specified and directed
Supply only coolant concentrate Pert No SK 802 OIC Make : Valvoline
M&L for dismantling and taking out the alternator upto 40 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holder and re-assembling the rotor & stator complete with applying suitable greasing & oiling of bearing & moving parts and refixing the same on existing position and testing complete all as specified and directed.
M&F for dismantling and taking out the alternator above 40 KVA but upto 82.5 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holder and re-assembling the rotor & stator complete including applying suitable greasing & oiling of bearing & moving parts and refixing the same on its position and testing complete all as specified and directed.
M&L for dismantling and taking out the alternator and taking out above 82.5 KVA but upto 125 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holder and re-assembling the rotor & stator complete including applying suitable greasing & oiling of bearing & moving parts and refixing the same on its position and testing complete all as specified and directed.
Material and labour for dismantling and taking out the alternator above 125 KVA but upto 250 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holder and re-assembling the rotor & stator complete including applying suitable greasing & oiling of bearing & moving parts and refixing the same its position and testing complete all as specified and directed.
S&F in replacement fuel feed pump for DG set of capacities upto 250 KVA including testing complete all as specified and directed.
S&F in replacement lead acid battery 12 volts, 180 AH suitable for DG set including initial charging (Model No. FXPO-MHD1800 Exide New express or Amaron of other specified make) including connection & testing complete all as specified and directed.
S&F in replacement lead acid battery, 12 volts, 150 AH suitable for DG set terminals including initial charging (Model No. FXPO-MHD1500 Exide New express or equivalent of other specified make) including connection & testing complete as specified and directed,
S&F in replacement lead acid battery, 12 volts, 110 AH with lead acid suitable for DG set including initial charging (Make- EXIDE / AMRON ) including connction and testing i complete as specified and directed .
Supply only distill water for batteries in 5 lts packing.
S&F in replacement battery charger heavy duty type with volteter and ammeter, with copper wound transformer, suitable for charging 12 Volts 180 AH battery complete all as specified and directed.
S&F in replacement battery charger heavy duty type with volteter and ammeter, with copper wound transformer, suitable for charging 02 Nos 12 Volts 180 AH battery complete all as specified and directed.
S&F in replacement of V-Belt as per exissting size/model and testing complete etc as specified and directed of the following capacity of the DG sets :-(a) 320/250/200 KVA DG Set
(b) 125/110/100 KVA DG Set
(c ) 82.5/63/62.5 KVA DG Set
(d) 40/30/20/15 KVA DG Set
S&F in replacement turbo kit suitable for 250/200 KVA DG sets.
S&F in replacement turbo kit suitable for 62.5 to 125 KVA DG sets.
S&F in replacement turbo kit suitable for 15 to 40 KVA DG sets.
Supply, fixing in replacement and testing Self Starter 12 Volt, DC for DG Set of capacity upto 125 KVA (Make of DG Set as per existing size and make) complete all as specified and directed.
Supply, fixing in replacement and testing Self Starter 24 Volt, DC for DG Set of capacity upto 320 KVA (Make of DG Set as per existing size and make) complete all as specified and directed.
Supply only DC 6/12 VOLT battery cell tester upto 180 AH battery all as specified and directed.
Supply only DC 6/12 VOLT battery hydrometer upto testing oof elecrolite specific grevity 180 AH battery all as specified and directed.
Supply & chelating cleaner Restore Plus solution Part No. AX1001098 Make : Cummins for engines cooling system all as directed.
Dismantling the defective, unserviceable Radiator opening as inlet/outlet water cooling system connection and Supplying & fixing new one Radiator Part No. 123200521096 for Engine DG Set Cap 125 KVA, Engine Model - TBD2 V8 MkI, Make : Greaves including all required accessories/hoses with tightening clamps etc as required inlet & outlet cooling system complete all as specified and as directed.
S&F in replacement Exhaust Manifold as per exisitng make/model/type of capaicty 250/200 KVA DG set complete as specified and directed
S&F in replacement Exhaust Manifold as per exisitng make/model/type of capaicty 100/110/125 KVA 100/110/125 KVA DG set complete as specified and directed
S&F in replacement Exhaust Manifold as per exisitng make/model/type of capaicty 62.5/63/82.5 KVA DG set complete as specified and directed
S&F in replacementg Exhaust Manifold as per exisitng make/model/type of capaicty 30/40 KVA DG set complete as specified and directed
S&F in replacement Exhaust Manifold as per exisitng make/model/type of capaicty 15/20/25 KVA DG set complete as specified and directed
S&F in replacement Exhaust Gasket as per existing make/model/type of capacity of DG set 250/200 KVA DG Set complete as specified and directed
S&F in replacement Exhaust Gasket as per existing make/model/type of capacity of DG set 100/110/125 KVA 100/110/125 KVA DG Set complete as specified and directed
S&F in replacement Exhaust Gasket as per existing make/model/type of capacity of DG set 62.5/63/82.5 KVA DG Set complete as specified and directed
S&F in replacement Exhaust Gasket as per existing make/model/type of capacity of DG set 30/40 KVA DG Set complete as specified and directed
S&F in replacement Exhaust Gasket as per existing make/model/type of capacity of DG set 15/20/25 KVA DG Set complete as specified and directed
S&F in replacement Pipe water pipe of manifold A bank of capacity of DG set 250 to 15 KVA as per existing make/model/type complete as specified and directed
S&F in replacement Pipe water pipe of manifold B bank of capacity of DG set 250 to 15 KVA as per existing make/model/type complete as specified and directed
Taking down carefully copper/aluminium point wiring (light, fan, socket, bell or power) complete including all electrical fittings & fixtures(DBs, submain,cables etc) and making good disturbed surfaces of wall , floor etc and matching wth original colour of wall, complete, all as specified & directed.
M&L Point wiring with 1.5 sq mm copper conductor FRLS (multistrand) PVC insulated ISI marked unseathed cable 1100 volt grade in and including concealed/surface , non metalic rigid pvc medium grade ISI marked conduit not less than 19 mm with all fittings & other accessories and also including PVC insulated ISI marked unseathed FRLS cable 1100 volts grade of size 1.5 sq mm copper conductor as earth wire to common earth dolly including concealed in wall/ceiling, MS box 1.6 mm thick with hylum sheet 3 mm thick (approved colour) suitable size for switches, sockets, fan regulator etc for the following :- (Note - (i) Colour code of cable Phase-Red Neutral- Black and Earth -Green) (ii) MS box painted with two coat of synthetic enamelled paind and over coat of red oxide both side.) (a) One light/fan point controlled by one way switch 6 amps 240 volts
(b) One 3 pin 6 Amps switch socket out let point on independent Board
(c) One 3 pin 6 Amps switch socket out let point on same board
M&L Point wiring with 2.5 sq mm copper conductor FRLS (multistrand) PVC insulated ISI marked unseathed cable 1100 volt grade in and including concealed/surface , non metalic rigid pvc medium grade ISI marked conduit not less than 19 mm with all fittings & other accessories and also including PVC insulated ISI marked unseathed FRLS cable 1100 volts grade of size 2.5 sq mm copper conductor as earth wire to common earth dolly including concealed in wall/ceiling, MS box 1.6 mm thick with hylum sheet 3 mm thick (approved colour) suitable size switches, sockets 16 Amps, 240 volts. ( Note - Colour code of cable Phase-Red Neutral- Black and Earth -Green) (ii) MS box painted with two coat of synthetic enamelled paind and over coat of red oxide both side.)
S&F switch piano flush type single pole, one way 6 Amps 240 ISI marked etc complet as specified and directed.
S&F socket outlet 2 in 1, 3 pin 5 A flush type ISI marked 240 volts ISI marked etc complete as specified and directed.
S&F switch socket combination 2 in 3 pin 5 and 15 Amps flush type ISI marked universal suitable for 240 volts etc complete as specified and directed.
M&L for ceiling rose with three terminal as per relevant IS complete as specified and directed .
Supply and fix decorative box type fitting with blue colour end cap for LED tube 20 watt luminaire for 230 volt AC incl LED tube 20 watt including taking down complete all as specified and directed.
Supply & fix decorative box type fitting with blue colour end cap for LED tube 10 watt luminaire for 230 volt AC incl LED tube 10 watt including taking down complete all as specified and directed
S&F stepped type fan electronic fan regulator flush type ISI marked on the existing fenolic laminated sheet etc complete as specified and directed
S&F epoxy powder coated or polystrene insulated material sheet metal enclosure factory made (double door) 8 way SPN suitable for MCB DB's 240 Volts with 200 Amps rated busbar, neutral & earthing link bar, flush/surface mounting including taking down complete all as specified and directed.
S&F epoxy powder coated or polystrene insulated material sheet metal enclosure factory made (double door) 4 way TPN suitable for MCB DB's 415 Volts with 200 Amps rated busbar, neutral & earthing link bar, flush/surface mounting including taking down complete all as specified and directed.
S&F MCB SP ISI marked `C' series working on 240 Volts 50 HZ AC supply for out going controlling cercuit of capacity 6-32 Amp breaking capacity 10 KA etc including taking down complete all as specified and directed.
S&F MCB SP ISI marked `C' series working on 240 Volts 50 HZ AC supply for out going controlling cercuit of capacity 40-63 Amp breaking capacity 10 KA etc including taking down including all as specified and directed.
S&F MCB SPN ISI marked `C' series working on 240 volts 50HZ AC supply for incomming controlling system of capaicty 40-63 Amps 10 KA breaking capacity etc including taking down complete all as specified and directed.
S&F MCB TPN ISI marked `C' series working on 240 volts 50HZ AC supply for incomming & out going controlling system of capaicty 40-63 Amps 10 KA breaking capacity etc including taking down complete all as specified and directed.
M&Lfor sub main wiring with two single core, 6 Sqmm and single core of earth wire (2x6.0 sqmm + 1x6.0 sqmm earth wire), PVC insulated,ISI marked, unsheathed, 1100 volts grade multistranded copper conductor FRLS cable drawn into and including suitable size non metalic rigid pvc conduit (ISI marked) concealed/surface with all accessories and including one single core pvc insulated multistranded unsheathed 1100 volts grade copper conductor FRLS cable as earth wire complete all as directed & specified.
S&F LED flood light 150 watt IP 66 high power flood light with pressure die cast aluminium housing (Balast Pen) including taking down complete all as directed & specified.
S&F decorative post top lantern for 360 C indirect light resistant to impact and corrosion, Glare free and better uniformity IP-65 protection miliky version with all accessoreis including taking down complete all as directed & specified.
M&L new generation energy saving and environmental friendly long life 45 W LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded pc cover having top opening separate driver compartment with IP 66 protection of IK07 in taking old one etc complete as specified and directed
S&F in replacement fire retardant electric insulation synthetic mat INSULATICA 2000" for 11 KV 3.0 mm thick +10% conforming to BIS DOC No ETD -02 (5231) P dt 2003. meeting requirement of IS 3043, IS: 5216 (Part 1,2,3) IS : 8437 and IEC 479 pub-1 IEC 61111 & 61112 tested for brake down strength tensile /elongation ageing properties. Insulation resistance, affects of acid , alkaline, Diesel & transformer oil, leakage current test fire test etc. having min width of 1000m + 20 mm complete as required suitable and using adhesive and allied chemical and scaling of all joints and border ends and fixing decorative taps the installed sheet complete as specified and directed.
Taking down existing heavy duty exhuast fan 600 mm, 900 rpm turbo force model three phase and re-fixing the same after servicing & repair with and including necessary packing materials, greasing, oiling, suitable size 4 core pvc insulated unseathed copper cable cable from ceiling rose to connector of fan, testing complete as specified and directed.( Note - spare parts/materials shall be measured and paid as supply only under respective items as shown below )
(a) Rewinding of fan motor with enameled copper wire of existing size/gauge including necessary packing materials etc complete all as specified and directed.
(b) Replacement of metalic fan blade of existing size complete all as specified and directed.
(c) Replacement of bearing of existing size & existing make.
(d) Replacement of condenser of existing capacity
(e) Replacement of bushes of existing size
Taking down existing heavy duty exhuast fan 450 mm, 900 rpm turbo force model three phase and re-fixing the same after servicing & repair with and including necessary packing materials, greasing, oiling, suitable size 4 core pvc insulated unseathed copper cable cable from ceiling rose to connector of fan, testing complete as specified and directed.( Note - spare parts/materials shall be measured and paid as supply only under respective items as shown below )
(a) Rewinding of fan motor with enameled copper wire of existing gauge/weight of copper coils size/gauge including necessary packing materials etc. complete all as specified and directed.
(b) Replacement of metalic fan blade of existing size complete all as specified and directed.
(c) Replacement of bearing of existing size & existing make.
(d) Replacement of condenser of existing capacity
(e) Replacement of bushes of existing size
Taking down existing ceiling fan 1200 mm sweep of any make and re-fixing the same after servicing & repair with and including necessary packing materials, greasing, oiling, suitable size 3 core pvc insulated unseathed copper cable cable from ceiling rose to connector of fan, testing complete as specified and directed.( Note - spare parts/materials shall be measured and paid as supply only under respective items as shown below )
(a) Rewinding of fan motor with enameled copper wire of existing gauge/weight of copper coils size/gauge including necessary packing materials etc. complete all as specified and directed.
(b) Replacement of metalic fan blade of existing size complete all as specified and directed.
(c) Replacement of bearing of existing size & existing make.
(d) Replacement of capacitor/condenser of existing capacity
(e) Replacement of bushes of existing size
S&F in replacement flood light 30 watt LED flood light engergy saving, environmental friendly long life exclusive innovative die cast aluminium alloy flood light with high power led as light source suitable for highlighting architectural feature or area lighting also suitable to rough services /installation incl taking down old one etc complete as specified and directed .
S&F in replacemen driver suitable for LED light fitting 36 to 45 watt any height etc complete as specified and directed
S&F in replacemen LED driver suitable for LED light fitting 100 watt any height etc complete as specified and direcrted.
S&F in replacemen LED driver suitable for LED light fitting 120/150 watt at any height etc complete as specified and directred .
Supplying, fixing in repair maintenance free tubular battery suitable for solar light, 12 volts, 110 AH or equivalent as per existing including initial charging (Make- EXIDE / AMRON/LUMENS) and connction and testing complete as specified and directed .
Servicing of solar light and solar battery after taking down unserviceable solar light and battery from pole and refixing the same after repair and filling the destile water in battery as required on site etc complete all as specified and directed.(Note. Driver and cable will be measured and paid respective items )
Cleaning the sub station in side and out side building/fencing/two/four pole structure ,and also aroun 2 m radius out side the fencing every three month duly taking out unwanted material grass/vegitable/roots of tree/small tree incl spray the chemical (roundup) in the permises of the sub station in the ratio 1:15 for burning the grasses at every three months etc complete as specified and directed
Disconnecting the all electrical connection from battery bank and taking out unserviceable part with and including replacement new parts as required for functioning of equipment, serviceing, connecting ,tighting, greasing, wiring & testing as required voltage including cleaning and painting with one coat of synthetic enamelled paine complete as directed.( Note - if any parts not included in the specification of works, contractor will provide own cost and deem to quoated cost if requied for functioning of equipment .
(a) Supply only transformer suitable for 12/110 volts
(b) Supply only voltmeter as per existing size and capcity
(c ) Supply only Ammeter as per existing size and capacity
(d) Supply only slector switch as per existing make and capacity
(e) Supply only push button as per existing size amd make
Supply only 2.0 volts rechargeable lithium battery suitable for 24/30 volts battery bank includig other matterials as per manufacturer norms incl connection and testing complete as per existing make/model/capacity
Supply and fix in repair shine wave invertor with 80 % efficiency upto 1 KW with 12 volt 180 AH maintenance free battery incl connection and testing complete as directed. Make-lumens/ exide/amron
Supply and fix in repair battery bank of capacity 24 V HBS make, consisting of (12 Nos) of 02 Volts 110 AH maintenance free lithium battery including disconnection/connedtion and testing complete as directed etc complete all as specified and directed.
Supply and fixing only off load changeover switch 63 Amps TPN with sheet metal enclosure ,side handle operated, 50 Hz, fixed to walls/ panels with suitable size clamps, nuts, bolts and washers complete all as specified and directed including making connections and testing of following capacities:- Make - L&T/Schneider/C&S/indoasian/HPL
All as per Item No 203 above but 100 Amps
All as per Item No 203 above but 200 Amps
Supply & Fixing in repairs "ON LOAD" type Change over switch 630 Amps TPN front handle operated, on existing LT/AMF Panels, suitable for three phase, 415V, 50 Hz AC supply of following ratings :- Make - L&T/Schneider/C&S/indoasian/HPL
All as per Item No 206 above but 315 Amps
All as per Item No 206 above but 250 Amps
All as per Item No 206 above but 200 Amps
All as per Item No 206 above but 100 Amps
All as per Item No 206 above but 63 Amps
Supply and fix in repairs 4 pole power contactor MCX44 auxilary contacts 2NO + 2NC suiable for 320 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/model for AMF panel boards etc complete all as specified and directed.
Supply and fix in repairs 4 pole power contactor MCX42 auxilary contacts 2NO + 2NC suiable for 250 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
Supply and fix in repairs 4 pole power contactor MCX41 auxilary contacts 2NO + 2 2NC suiable for 200 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
Supply and fix in repairs 4 pole power contactor MCX33 auxilary contacts 2NO + 2NC suiable for 100 to 125 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
Supply and fix in repairs 4 pole power contactor MCX22 auxilary contacts 2NO + 2NC suiable for 63 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
Supply and fix in repairs 4 pole power contactor MCX12 auxilary contacts 2NO + 2NC suiable for 30-40 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
Supply and fix in repairs 4 pole power contactor MXC4 auxilary contacts 2NO + 2NC suiable for 15-25 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
Supply,laying, jointing, testing, XLPE insulated PVC sheathed stranded aluminium conductor, heavy duty, conforming to IS 1554 Part I / ISI marked, including suitabe size cable glands & lugs, cables to be laid in trenches, fixed along the poles /or through GI pipe laid under floors road etc complete of sizw 300 sqmm 3.5 core incl taking down old one as specified and directred
All as per Item No 219 above but 240 Sqmm 3.5 Core
All as per Item No 219 above but 95 Sqmm 3.5 Core
All as per Item No 219 above but 70 Sqmm 3.5 Core
S&F in replacement MCCB 4 Pole of capacity 125 Amps, 50 Hz, 415V with rupturing capacity of 16 KA with thermal magnetic protection including spreader terminals complete all as specified and directed.
S&F in replacement MCCB 4 Pole of capacity 160 Amps, 50 Hz, 415V with rupturing capacity of 25 KA with fixed thermal magnetic settings including spreader terminals complete all as specified and directed.
S&F in replacement MCCB 3 Pole of capacity 200 Amps, 50 Hz, 415V with rupturing capacity of 35 KA with fixed thermal magnetic settings including spreader terminal complete all as specified and directed.
S&F in replacement MCCB 3 Pole of capacity 250 Amps, 50 Hz, 415V with rupturing capacity of 35 KA with fixed thermal magnetic settings including spreader terminals complete all as specified and directed.
S&F in replacement MCCB 3 Pole of capacity 400 Amps, 50 Hz, 415V with rupturing capacity of 50 KA with fixed thermal magnetic settings including spreader terminals complete all as specified and directed.
M&L for fabrication of trolley (chakery system) to accommodate 30 KVA DG set with panel, including LT cables and with over all size not less than 2.00 mtrs × 3.00 mtrs using MS channel of size 100 × 50 mm and angle iron 50 × 50 × 6 mm and MS flat wherever required including base of MS sheet 10 gauge fixed properly welded on chassis and duly painted with two coats of synthetic enamel paint over a coat of red oxide steel primer, with towing hook of channel/angle iron, fixed with trolley for easy movement from one place to another place. It shall not be less than 0.80 mtr length from the body of trolley and shifting the DG set from existing to new including taking down old one complete all as specified and directed by the EIC with the following:- ' (a) Supply & fixed tyre tubes of size 7.50 × 16 on suitable size of wheel drum - 04 Nos (Make-MRF / CEAT) (b) Supply & fix leaf spring set of 13 Nos with U clamps - 04 set suitable to take full load of trolley and transformer. (c) Supply & fix axle - 02 Nos between front & rear wheel (d) Supply & fix danger notice plate/board on each side of trolley - 04 Nos (e) The cost of any MS work required for fixing of DG set, panel shall deemed to include the rate Note:- (i) Any other work/item not mentioned above but necessary for smooth functioning of the trolley shall be included in the rate quoted by the contractor.
M&L for dismantling the defective alternator of any capacity from the existing foundation and Engine after removing all electrical connections transporting to workshop, removing the old wornout burnt wiinding and rewinding the stator assembly with super enameled copper wire, applying insulating varnishing of ‘F’ class baking in oven re-assembling the alternator after transporting back to site re-installing the same carrying out alignment of complete DG set connecting up all electrical connections testing and commissioning complete. Note : - (a) The rates quoted by the contractor shall deemed to include any other item/spare not mentioned herein but essentially required for fully functional of the alternator. (b) Rate quoted shall be deemed to be inclusive of making good the disturbed surfaces of foundations. (c) The DG set shall be tested for the duration of 4 hours to the entire satisfaction of Engineer- in- Charge.
NEXT POWER ENTERPRISES
Magneoflux
M/S Nav Jyoti Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .