Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.1 CrAdmitted-Finance | ₹12.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹13.6 CrAdmitted-Finance | ₹13.6 Cr | L2 | Admitted-Finance |
| 3 | L3₹13.7 CrAdmitted-Finance | ₹13.7 Cr | L3 | Admitted-Finance |
| 4 | Rejected-Technical OFFICE NO 201 2ND FLOOR MAGNOLIA BUSINESS CENTER BANER PASHAN LINK ROAD PUNE 411021 | PUNE | PUNE | MAHARASHTRA | 411021 | - | - | Rejected-Technical As per scope of work, required Duly Signed Documents not submitted before due date |
| 5 | Rejected-Technical | - | - | Rejected-Technical As per scope of work, required Duly Signed Documents not submitted before due date |
| Sl No | Description | Qty | Unit | MAK ENTERPRISES L1 | CHAITRA ELECTRICALS AND ENGINEERING L2 | HIGHWAY CONSTRUCTION CO L3 |
|---|---|---|---|---|---|---|
| 1.00Modification & Improvement of medical facilities at Dr. R. N. Cooper Hospital, Vile Parle (West), Mumbai. | ||||||
| 1.01 | S & I of 80 mm PPGI sheet Panel along with accessories | 450 | SqM | 13,685 ₹61.6 L | 14,141 ₹63.6 L | 14,266 ₹64.2 L |
| 1.02 | S & I of 50 mm thick both side PPGI sheet with PUF insulation | 350 | SqM | 11,311 ₹39.6 L | 11,689 ₹40.9 L | 11,792 ₹41.3 L |
| 1.03 | SITC of aluminium coving. The aluminium coving size shall be 50 x 50 x 1mm of epoxy polyester powder coated. Aluminium coving shall match the color of ceiling & partitions, at the junction of ceiling & partition, partition & partition including press fit arrangement with & over pvc/aluminium base member, staging, scaffolding, etc. | 325 | Mtr | 2,174 ₹7.1 L | 2,246 ₹7.3 L | 2,266 ₹7.4 L |
| 1.04 | SITC of aluminium 3D corner. The Aluminium 3D Corner shall match the color of ceiling & partitions and at the junction of ceiling & partition. | 32 | Nos | 1,270 ₹40,640 | 1,312 ₹41,984 | 1,324 ₹42,368 |
| 1.05 | SITC OF Antistatic Conductive/ Dissipative Flooring:Seamless with perfectly curved flush-covings, resistance to mechanical stresses and dynamic loads and having conductive protection characteristics, 2 mm thick, washable | 350 | SqM | 5,706 ₹20.0 L | 5,896 ₹20.6 L | 5,948 ₹20.8 L |
| 1.06 | SITC of fireproof double door with frame 1500x2100 mm. The Doors shall be designed to fit flush into the wall panel system on both sides and shall be supplied in different dimensions. The Doors shall be fabricated from galvanized iron sheets duly powder coated, The Shutter shall have sheet thickness of 0.8mm with the frame of 1.2mm. The Standard 50 mm panel shall have frame width of 50 mm and shutter width of 46mm. | 7 | Nos | 2,03,294 ₹14.2 L | 2,10,077 ₹14.7 L | 2,11,927 ₹14.8 L |
| 1.07 | SITC of fireproof double door with frame 900x2100 mm. The Doors shall be designed to fit flush into the wall panel system on both sides and shall be supplied in different dimensions. The Doors shall be fabricated from galvanized iron sheets duly powder coated. The Shutter shall have sheet thickness of 0.8mm with the frame of 1.2mm. The Standard 50 mm panel shall have frame width of 50 mm and shutter width of 46mm. | 7 | Nos | 1,22,285 ₹8.6 L | 1,26,365 ₹8.8 L | 1,27,478 ₹8.9 L |
| 1.08 | SITC of windows double glazed.
Flush view/Glazing panels on the wall shall be designed to fit flush into wall panel with 5 mm thick glasses.
The size of the windows shall be 1500 x 1200 mm. | 23 | SqM | 49,712 ₹11.4 L | 51,371 ₹11.8 L | 51,823 ₹11.9 L |
| 1.09 | S & I of G.I. Powder Coated Rectangular Riser (Wall riser) | 20 | Nos | 1,11,202 ₹22.2 L | 1,14,913 ₹23.0 L | 1,15,925 ₹23.2 L |
Tender Value
Refer Docs
EMD Value
₹16.3 L
Closing Date
28 Feb 2026, 4:00 pmClosed
Dean Dr. R. N. Cooper Mun. Gen. Hospital
Dr. R. N. Cooper Mun. Gen. Hospital
Modification and Improvement of medical facilities at Dr R. N. Cooper Hospital, Vile Parle (West), Mumbai.
2025_MCGM_1259997_1
HO/1661/RNCH/DTD. 12.12.2025
Open Tender
Electrical Works
180 days
Dr. R. N. Cooper Mun. Gen. Hospital. Vile Parle W
Please refer Tender documents.
3 documents required · 3 mandatory
₹21,417
₹16.3 L
Dean office Dr. R. N. Cooper Mun. Gen. Hos
30 Apr 2026
7 Feb 2026
2 Mar 2026
7 Feb 2026
28 Feb 2026
7 Feb 2026
12 Feb 2026
Modification & Improvement of medical facilities at Dr. R. N. Cooper Hospital, Vile Parle (West), Mumbai.
S & I of 80 mm PPGI sheet Panel along with accessories
S & I of 50 mm thick both side PPGI sheet with PUF insulation
SITC of aluminium coving. The aluminium coving size shall be 50 x 50 x 1mm of epoxy polyester powder coated. Aluminium coving shall match the color of ceiling & partitions, at the junction of ceiling & partition, partition & partition including press fit arrangement with & over pvc/aluminium base member, staging, scaffolding, etc.
SITC of aluminium 3D corner. The Aluminium 3D Corner shall match the color of ceiling & partitions and at the junction of ceiling & partition.
SITC OF Antistatic Conductive/ Dissipative Flooring:Seamless with perfectly curved flush-covings, resistance to mechanical stresses and dynamic loads and having conductive protection characteristics, 2 mm thick, washable
SITC of fireproof double door with frame 1500x2100 mm. The Doors shall be designed to fit flush into the wall panel system on both sides and shall be supplied in different dimensions. The Doors shall be fabricated from galvanized iron sheets duly powder coated, The Shutter shall have sheet thickness of 0.8mm with the frame of 1.2mm. The Standard 50 mm panel shall have frame width of 50 mm and shutter width of 46mm.
SITC of fireproof double door with frame 900x2100 mm. The Doors shall be designed to fit flush into the wall panel system on both sides and shall be supplied in different dimensions. The Doors shall be fabricated from galvanized iron sheets duly powder coated. The Shutter shall have sheet thickness of 0.8mm with the frame of 1.2mm. The Standard 50 mm panel shall have frame width of 50 mm and shutter width of 46mm.
SITC of windows double glazed. Flush view/Glazing panels on the wall shall be designed to fit flush into wall panel with 5 mm thick glasses. The size of the windows shall be 1500 x 1200 mm.
S & I of G.I. Powder Coated Rectangular Riser (Wall riser)
MS STRUCTURE
25 mm.- Only PVC Conduits
SITC of double decker AHU, SA-7500 cfm, 125mm static & EX - 8500 cfm, 80mm static - pre & post op, corridors & change room. The 48 mm thick PUF insulation shall have density of 38 kg/cm3 double skin Air handling units with 0.6mm thick precoated outer G.I. skin and 0.6mm thick plain inner G.I. skin in ONCE THROUGH configuration, with extruded Aluminium Thermal break profile, with backward curved Plug Fan. The Chilled water Coil shall be made out of 6/8 row deep coil having 1/2” OD copper tube – tube thickness 27 WG and Aluminium fins thickness 0.15mm, 10 to 12 fins per inch Flexible canvas connection and cushy foot mounting for fan, Combination Filter (prefilter10µ+Fine filter section(03μ). The Manual control damper shall be for Supply and return. The Marine Light and limit switch shall be for the exhaust Thermal break profile, with backward curved Plug Fan. The Flexible canvas connection shall be for cushy foot mounting for fan, Filter Semi HEPA filter section (0.3μ).AHU shall be provided with low leakage aluminium damper for both supply and return side
VRF / VRV AC EQUIPMENTS 20 HP
Supply, Installation, Testing and Commissioning of Refnets as specified of pipe sizes from 1/4 " to 2"
Supply Installation Testing & commissioning AHU Controller / distribution kit of suitable capacity for connecting multi VRF ODU to DX AHU, with a) built in auto restart function, c) with necessary electrical wiring & remote controller.
SITC of Seamless heavy gauge REFRIGERATION COPPER PIPING for VRF/ VRV system in 18 gauge, duly insulated with 13 mm/19 mm thickness. Nitrile Rubber Insulation. Refrigeration piping will have to be taken in the piping rack / Support individually connecting to Indoor units, including necessary supports, fittings, valves, Cable tray for exposed piping where ever required will be included.. The pipe sizes from 1/4 " to 1".(13 mm insulation) and 1-1/8 " to 2"(19 mm insulation) shall be used.
2C X 1 sqmm Communication shielded Cable
250 mm diameter with insulation of 38mm thk nitrile rubber insulation
GSS Ducting:- 24 SWG
GSS Ducting:- 22 SWG
GSS Ducting:- 20 SWG
Providing thermal insulation to supply air ducting with 19mm.thickness nitrile rubber
Providing thermal insulation to return air ducting with 12mm.thickness nitrile rubber
Providing aluminium supply air diffusers & return air grills with volume control dampers
Supply and installation of volume control dampers, bypass dampers.
SITC of fusible link fire damper. The fire damper with Fusible Links shall be rated for 72°C of approved make of at least 90-minute fire rating. The fire dampers shall be provided at all fire rated crossovers (shafts/walls etc.) Damper shall have one limit switch with two NC contactors.
SITC of Main Power Panel. The Main Power Panel shall be of 3phase and Neutral 440V, 4 wire Free Standing, Floor mounted LV panel made out of 2mm thick CRCA sheet after seven tank process and Epoxy powder coating. The panel shall consist of suitable rating TPN Aluminium bus bar (at the rating of 0.8A per Sq.mm) supported with DMC/ SMC barriers and colour coded with Heat shrinkable sleeves. The panel shall have short circuit with standing capacity and shall consist of the switch gear. The panel shall be fabricated from manufacturers with CPRI Test certificate only. The Panels shall be mounted on ISMC-75. The MCC panel shall have the following;500Amp incomer 4P MCCB, 25KA aluminium busbar, metering and outgoing feeders for 7 Nos AHU Control Panels, Lighting DB's- 3Nos, Power DB's-3Nos 160Amp 4P MCCB.
2nd category Cu armoured cables FRLS outer sheathed- 4C x 1.5 Sq.mm
SITC of aluminium insulated powder coated terminal boxes with filter holding arrangement to hold the filters of H14 filters of size 600x600. The H14 HEPA Filter with Housing & Damper (Bottom Discharge Module Type) shall be made of extruded aluminium anodized material with low leakage aluminium collar damper with operating gear arrangement. The Housing shall be suitable for fixing the Gel Seal type (Polyurethane gel) terminal HEPA filter (H-14 as per EN1882 Class) with Protective Screen. The Filter Housing shall have provision for smoke aerosol test point and differential pressure measuring point.
Validation & documentation charges The Validation and documentation charges shall cover the comprehensive testing, certification, and record preparation for the entire modular OT setup. This shall include HVAC performance validation, HEPA filter testing, FM etc. These charges shall ensure the OT meets all regulatory and functional requirements before handover.
IP 42 Wall/column Mounted distribution board with one Nos of DP 16/32A MCB as incomer and 8 Noss 6A/10A SP MCB as outgoing (12 way SPN DB)
IP 42 Wall/column Mounted distribution board with one Nos of 63A 4P MCB and 3 Noss 16A TP MCB / 9 Noss. 16A SP MCB as outgoing (4 way TPN DB)
IP 43 4 Way MCCB DB (125/160A MCCB + 4Way TP MCB /12 Way SP MCB)
1st category Al armoured cables FRLS outer sheathed- 3.5C x 300 Sq.mm
1st category Al armoured cables FRLS outer sheathed- 3.5C x 120 Sq.mm
1st category Al armoured cables FRLS outer sheathed- 3.5C x 70 Sq.mm
1st category Al armoured cables FRLS outer sheathed- 3.5C x 50 Sq.mm
1st category Al armoured cables FRLS outer sheathed- 3.5C x 35 Sq.mm
1st category Al r armoured cables FRLS outer sheathed- 4C x 16 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 4C x 16 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 3C x 10 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 3C x 6 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 3C x 4 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 3C x 2.5 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 4C x 1.5 Sq.mm
1st category Cu armoured cables FRLS outer sheathed- 4C x 6 Sq.mm
Cat 6 Gigabyte
Cable End Termination For Aluminium Cables – 3.5C x 300 Sq.mm
Cable End Termination For Aluminium Cables – 3.5C x 120 Sq.mm
Cable End Termination For Aluminium Cables – 3.5C x 70 Sq.mm
Cable End Termination For Aluminium Cables – 3.5C x 50 Sq.mm
Cable End Termination For Aluminium Cables – 3.5C x 35 Sq.mm
Cable End Termination For Aluminium Cables – 4C x 16 Sq.mm
Cable End Termination For Copper Cables – 3C x 16 Sq.mm
Cable End Termination For Copper Cables – 3C x 10 Sq.mm
Cable End Termination For Copper Cables – 3C x 6 Sq.mm
Cable End Termination For Copper Cables – 3C x 4 Sq.mm
Cable End Termination For Copper Cables – 3C x 2.5 Sq.mm
Cable End Termination For Copper Cables – 4C x 6 Sq.mm
Cable End Termination For Copper Cables – 3C x 25 Sq.mm
PVC box & cover plate with RJ-45 for LAN access only
PVC box & cover plate with RJ-11 for Telephone access only
50 pair M.S.Junction Box for EPABX
Switch BOX point for computers through PVC Conduit Description of Item 8Modular SURFACE BOX - 1 No. 8Modular PLATE - 1 No. INDICATOR LAMP - 1 No. 15A SWITCH - 1 No. 6A 5 PIN SOCKET - 3 Nos. 2Modular SURFACE BOX - 1 Nos. 2M PLATE - 1Nos. RJ11 SOCKET - 1 Nos. RJ45 SOCKET - 1Nos.
G.I. Cable tray with all other accessories 75 x 25mm (W x H) - (16 SWG - 1.6mm) without cover
G.I. Cable tray with all other accessories 100 x 25mm (W x H) - (16 SWG - 1.6mm) without cover
G.I. Cable tray with all other accessories 150 x 25mm (W x H) - (16 SWG - 1.6mm) without cover
G.I. Cable tray with all other accessories 300 x 50mm (W x H) - (16 SWG - 1.6mm) without cover
Earthing Continuity Conductors -25 x 3mm GI
Wiring for submains- medium class PVC- 2 X 4 sq. mm + 1 X 4 sq. mm earth wire in 25mm Conduit
Wiring for submains- medium class PVC- 2 X 6 sq. mm + 1 X 6 sq. mm earth wire in 25mm Conduit
Earthing station with 100mm Dia., 13mm thick, 3000 mm long GI pipe (Class B or better) earth pit as per IS 3043. The earth pit shall be provided with watering pipe (Class B) with wire messed funnel, 25x3 GI strip / 2X8SWG G.I. wire up to chamber ( wire or strip size as per fault level), disconnecting links with 600 x 600 mm (clear) RCC chamber & heavy duty 3mm thick CI chequered plate cover with hinge & stainless steel bolts. Bentonite/Charcoal & Salt shall be provided for earth pits. Excavation, back filling, removal of excess soil is included in the scope
25 mm.- Only PVC Conduits
Indoor LED Fixtures - LED Square Recesed Downlighter 36W (600x600)
SITC of UPS Panel. The UPS Panel shall be of 40 KVA UPS O/P PANEL, Busbar: 100 Amp FP Aluminium Incomer – 100 Amp FP MCCB with DOL, 25kA with MFM, 6 Nos. Phase Indicating Lamps. Outgoings – 63 Amp 4P MCB D Curve - 5 Nos 32 Amp 4P MCB D Curve - 5 Nos 63 Amp 4P MCB D Curve - 2 Nos for Spare 32 Amp 4P MCB D Curve - 2 Nos for Spare
SITC of modular type switch socket 16 amp switch 1 nos. with front & rear plate. The switch shall be industrial Pentra type switch socket with Rotary Switch (rotary knob for ON/OFF control switch pad locking arrangement in OFF position) enclosed in enclosure. The scope shall include fixing of enclosures, supply of all fixing accessories/hardware. Rotary switch or MCB and socket shall be wired up to outgoing terminals etc, complete as required. All Power outlets (Switch Sockets) shall be provided with top Switch-Socket along with three phase 63 Amp 5 pin switch socket with 63 Amp FP MCB.
SITC of modular type switch socket 16 amp switch 2 nos. with front & rear plate. The switch shall be industrial Pentra type switch socket with Rotary Switch (rotary knob for ON/OFF control switch pad locking arrangement in OFF position) enclosed in enclosure. The scope shall include fixing of enclosures, supply of all fixing accessories/hardware. Rotary switch or MCB and socket shall be wired up to outgoing terminals etc, complete as required. All Power outlets (Switch Sockets) shall be provided with top Switch-Socket along with three phase 32 Amp 5 pin switch socket with 32 Amp FP MCB.
SITC of 16 amp switch 3 nos. with front & rear plate. The CRCA module box shall be concealed in such way that front plate shall be flushed with modular partition wall and & brick wall. The front plate shall be SS 304 matt finish.
SITC of 16 amp switch 4 nos. with front & rear plate. The CRCA module box shall be concealed in such way that front plate shall be flushed with modular partition wall and & brick wall. The front plate shall be SS 304 matt finish.
SITC of 16 amp switch 6 nos. with front & rear plate. The CRCA module box shall be concealed in such way that front plate shall be flushed with modular partition wall and & brick wall. The front plate shall be SS 304 matt finish.
SITC of 6/16 amp switch socket 1 no. with front & rear plate. The CRCA module box shall be concealed in such way that front plate shall be flushed with modular partition wall and & brick wall. The front plate shall be SS 304 matt finish.
SITC of 6/16 amp switch socket 2 no. with front & rear plate. The CRCA module box shall be concealed in such way that front plate shall be flushed with modular partition wall and & brick wall. The front plate shall be SS 304 matt finish.
3 Ph input & 3 Ph output 40 kVA fully microprocessor based true online double conversion UPS system with SMF batteries suitable for 1/2 hrs along with necessary battery racks & interconnections & UPS to battery bank cables.
Supply, Installation, testing & commissioning of addressable 2 loop main fire alarm electronic control panel, expendable up to 4 loop & having maximum 250 devices (any combination detectors plus devices) per loop & Audio/ Visual alarm complete as per IS: 2189 specification - modular type front operated with interlocking door arrangement totally enclosed dust and vermin proof for indoor type applications.
Supply, Installation, testing & commissioning of Intelligent multi- criteria Detector along with mounting box & termination glands.
Supply, Installation, testing & commissioning of Isolator Module along with mounting box & termination glands.
Supply, Installation, testing & commissioning of Addressable control Relay module with required accessories along with junction box, glands and terminators ( For AC trip off, Access trip off, PA system, sprinkler flow switch, lift interface, sounder, fire fighter & telephone jack)
Supply, Installation, testing & commissioning of Strobe Lights along with mounting box & termination glands.
Supply, Installation, testing & commissioning of Addressable Manual call point/ station with mounting back box
1st category Cu armoured cables FRLS outer sheathed-2C x 1.5 Sq.mm
Supply, Installation, Testing & Commissioning of InfraRed Analog HD Dome camera, 1/3’’ CMOS image sensor, Fixed Lens: 3.6mm (2.8mm, 6mm & upto 12mm optional lens), Minimum 720 P lines horizontal resolution, IR Range upto 20m,1 channel BNC HDCVI high definition video output, Minimum Illumination: 0.05Lux/F2.0, 0Lux IR ON; Auto(ICR) / Color / B/W filter, Weatherproof Standard : IP67 and etc. to fullfill the requirement.
Design, Supply, testing, installation and commissioning of modular 16 channel 1080P NVR, Recording: 1920X1080P, 15 FPS, 30 days recording, 24 hours/day; Real time monitoring with 25 FPS. Hard disc : 8 SATA III Ports, Each 6TB , up to 48TB, 1 eSATA port, Disk array: Support RAID 0/1/5/6/10, Two no’s of RJ -45 10/100/1000 Mbps self adaptive Ethernet interface, RS 232, RS 485, keyboard interfaces, VGA/HDMI compatible, 2nos front USB 2.0 & 1 no at rear USB 2.0 compatible & 8 TB hard disc and as per storage configuration contractor shall consider the separate hard discs
Supply & inst of 2 TB Hard Disk Drive
Supply & inst of 18.5" LED Monitor
SITC of 8 ports 10/100/1000 with 2 combo ports PoE switch with installation
24 Port Patch Panel
6W/100V. PA Ceiling Speaker
Supply & installation of P.A. Cassette 160 watts Amplifier.
Supply and installation of 250 watts amplifier with USB
SITC of 9 inch Rack
Delegate unit Microphone
15 / 5 A / 6 A Combined Power Plug Socket Point with Fuse and Indicating Lamp, One 15 Amp SP Switch
1st category Cu armoured cables FRLS outer sheathed-2C x 1.5 Sq.mm
S&I of SS304 work bech 600 x 600x750 mm
S&I of SS304 work bech 525 x 600 x 750mm
S&I of SS304 work bech 648 x 600 x 750mm
S&I of SS304 work bech 585 x 600 x 750mm
S&I of SS304 work bech 950 x 950 x 750mm
S&I of GI Powder coated work bench
S&I of SS 304 Garment Cub with 4 nos
S&I of SS 304 wash basin sink and tap
S & I of SS racks of size 2 ft x 4 ft length and 3/4 levels
SITC of Oxygen Digital Fully Automatic Control Panel of 2000lpm. Input power to the manifolds is 110 to 240 VAC, 50- 60 Hz. It should have flow capacity 4,500 SCFH [2,000 L/min]. (Maximum tolearance allowed will be only 10%).
SITC of Medical Grade Copper Tube/Pipes including all type of accessories Like,Tee, Elbow, Valves, etc. complete_Copper Pipes of 15mm OD x 1.0mm thk
SITC of Medical Grade Copper Tube/Pipes including all type of accessories Like,Tee, Elbow, Valves, etc. complete_Copper Pipes of 22mm OD x 1.0mm thk
SITC of Medical Grade Copper Tube/Pipes including all type of accessories Like,Tee, Elbow, Valves, etc. complete_Copper Pipes of 28mm OD x 1.0mm thk
SITC of Medical Grade Copper Tube/Pipes including all type of accessories Like,Tee, Elbow, Valves, etc. complete_Copper Pipes of 42mm OD x 1.2mm thk
SITC of 15 mm Single Port Ball Valve with Pipe line assembly (pre piped) : Pre Piped Degreased Ball Valve with pipe extension. It should be full-port design.It should be blow-out proof stem. It should be lockable valve.
SITC of 22mm Single Port Ball Valve with Pipe line assembly (pre piped) : Pre Piped Degreased Ball Valve with pipe extension. It should be full-port design.It should be blow-out proof stem. It should be lockable valve.
SITC of 28mm Single Port Ball Valve with Pipe line assembly (pre piped) : Pre Piped Degreased Ball Valve with pipe extension. It should be full-port design.It should be blow-out proof stem. It should be lockable valve.
SITC of Gas pressure Regulator of size 25mm
SITC of Vacuum Pump. : It should be oil lubricated rotary vane vacuum pump, having each vacuum pump capacity of 1500lpm with IEC Motor rating of minimum 7.5 HP @ 50 Hz or above. Vacuum pump shall comprise of air cooled, oil lubricated vacuum pumps suitable for both continuous and frequent start / stop operation at inlet vacuum vessels between 525mm Hg and 700 mm Hg. The ultimate vacuum of pump shall be 0.1 mbar with gas ballast valve closed.
SITC of Vacuum Receiver Tank of 500 Litres water capacity.
SITC of Vacuum Regulator Unit : It shall be duly CE marked/UL listed or equivalent.
SITC of High Flow Oxygen Flow Meter 0- 70lpm : It shall be duly CE marked/UL listed or equivalent. The flow meters should be of 0-70 LPM range for oxygen and with inlet pressure 50-60psi. (4.5 bar).
Providing, Fixing, Testing & Commissioning of 3 way mixing valve - 100 mm diameter
SITC OF Medical Gas Pipeline inside OT Comprising of Cooper pipe 15mm Diameter 0.7 and 22mm Diameter 0.9, Pressure transducers , NIST Connectors etc.
SITC of 2 Gases Valve Box with pressure guage only for Oxygen & Vacuum. It should have zone valve box shall consist of the following components: A steel valve box which can house shut-off ball valves with tube extensions, an aluminum frame and a pull-out removable window. Pressure Gauges are included. The window shall be marked to prohibit unauthorized persons from tampering with the valves with the following silk-screen caution: “MEDICAL GAS CONTROL VALVES CLOSE ONLY IN EMERGENCY”
SITC of Digital Area Alarm (2 Services : Oxygen and Vacuum) with pressure sensor : Medical Gas LCD Alarm : The LCD alarm shall be microprocessor based with a 10" (25.4 cm) screen and capable of monitoring medical gases.
SITC of High Flow Oxygen Flow Meter 0- 70lpm : It shall be duly CE marked/UL listed or equivalent. The flow meters should be of 0-70 LPM range for oxygen and with inlet pressure 50-60psi. (4.5 bar).
SITC of Humidifier Bottle : Polypropleyene or Polysulphone 250cc Humidifier bottle should be unbreakable, reusable to disinfectants and complements.
SITC of Vacuum Regulator Unit : It shall be duly CE marked/UL listed or equivalent.
SITC of fully motorized bed with mattress.Overall dimensions : 2150 x 1025 mm Platform Frame : 2070 x 955 mm Mattress Platform : 1890 x 865 mm Mattress Platform Height : 395 x 695 mm (without Mattress) Backrest : 0 – 70 degree Kneerest : 0 – 45 degree Trendelenburg : 0 – 11 degree Reverse Trendelenburg : 0 – 11 degree Safe Working Load : 250 Kgs Patient Load Bearing : 220 Kgs Capacity Power : 100 – 240 V, Max 5A Electrical Shock Protection : Class I Degree of Shock Protection : Type B Liquid Ingress Protection : IPX6 Duty Cycle : 10 % General safety for medical : IEC 60601-2-52 beds General safety for medical : IEC 60601-1-1 Electrical Equipment EMI/EMC : IEC 60601-1-2 Urine Bag holder : Included Corner Safety : 4 Rubber Buffers CPR : Dual Side Manually Operated SMPS : Inbuilt Mattress : 100 mm thick four section
SITC of Double duct Bed Head Horizontal Wall Panel 600 mm. Separete duct for gas outet and seperate duct for electricals. (made up from Aluminum powder coated profiles) with double duct. Separate duct for electrical sockets and separate duct for gas outlet points. Each bed head panel should be pre piped and pre wired. It should have pre wired 4 nos. electrical sockets in separate duct ( 2 nos. 5 A sockets and 2 nos. 15 A sockets). Gas outlet points 2nos. pre piped to be fitted in the bed head panel. Gas outlet points cost not to be included in the bed head panel cost since it is separate line item. It should have provision for RJ45 connector and Nurse call system bedside switch with partition between LV and ELV system.
SITC of Nurse Calling System. The system shall include the following. 19 " Color Monitor – 1 Nos The monitor shall be used for both audio announcement and visual display. The monitor shall display room names along with floor map. Nurse Call Processor -1 Nos The NCP shall collect the data from all the rooms and shall announce call status with high quality voice. COMPOSITE CALL ROOM UNIT (CCRU +) – 6 Nos The CCRU + shall be directly connected to the Nurse Station through CAT 6 Cable COMMON TOILET CALLING UNIT ( CTCU +) – 3 Nos The CTCU + shall be directly connected to the Nurse Station with its own electronics through CAT 6 Cable SHARE DOOR INDICATOR – 3 Nos Shall include various back boxes and electronics connected between beds and toilets and shall also indicate higher priority call status. NS PORT EXTENDER 16 PORT – 1 Nos Designed to connect upto 16 private rooms with Nurse Station.
SITC of Rail for chemically treated stain retardant fabric. The rail shall be suitable for curtains ranging between 18 “ to 24 “ of nylon make.
SITC of chemically treated stain retardant fabric. The chemically treated stain retardant fabric shall be of nylon make with top mesh. The size shall range between 18” to 24”.
SITC of saline stand of SS304. The saline stand shall have telescopic height adjustable mounted on castor. Over all dimension shall be 695 mm diameter base circle with height adjust from 1568 mm to 2121 mm. The 4 prongs bottom frame shall be made of 1.6 mm thick mild steel and the lower basement shall be 30 mm diameter with 1.6 mm thick MS tube. 4 high endurance anti-static plastic moulded 50 mm castors shall be provided with dual locking. The telescopic rod shall be 19 mm diameter, 1.6 mm thick SS 304 grade tube with locking knob. 4 nos. hooks shall be provided for hanging saline bags. The telescopic tube shall have plastic bush at the bottom which provides smooth linear motion during height adjustable. All the MS part shall be pre-treated with 9tank process with zinc phosphate and powder coated with anti-microbial epoxy polyester powder coating.
Supply & laying I.S.I. mark 'B' class GI Pipe -25 mm dia.
Supply & laying I.S.I. mark 'B' class GI Pipe -32 mm dia.
Supply & laying I.S.I. mark 'B' class GI Pipe -38/40 mm dia.
Supply & laying I.S.I. mark 'B' class GI Pipe -50 mm dia.
Supply & laying I.S.I. mark 'B' class GI Pipe -65 mm dia.
Ball valves 25 mm diameter
Ball valves 40 mm diameter
Ball valves 50 mm diameter
Ball valves 65 mm diameter
Supplying &Fixing screwed cast brass cleanout plug with suitable inset keys & opening, male threaded joint with EPDM rubber gasket jointng as pe DIN- 19543, ASTM C 1277-4. a) 80 mm (3") dia
Supplying &Fixing screwed cast brass cleanout plug with suitable inset keys & opening, male threaded joint with EPDM rubber gasket jointng as pe DIN- 19543, ASTM C 1277-4. b) 100 mm (4") dia.
Demolishing brick work in lime or cement mortar including plaster, paint, etc. manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge.
Dismantling doors, windows, fanlight and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : Of area 3 sq. metres and below
Cement mortar 1:3 (1 cement : 3 coarse sand)
Providing and applying 6 mm thick internal sand faced ceiling plaster in cement mortar 1:3 at all heights and locations in single coat for concrete surfaces including scaffolding, hacking of concrete surface, watering,finishing, curing etc. complete.
For plastered wall surface
Replacement of existing damaged false ceiling by new aluminium false ceiling sheets along with grid work.
Supply, Installation, testing & commissioning of addressable 2 loop main fire alarm electronic control panel, expendable up to 4 loop & having maximum 250 devices (any combination detectors plus devices) per loop & Audio/ Visual alarm complete as per IS: 2189 specification - modular type front operated with interlocking door arrangement totally enclosed dust and vermin proof for indoor type applications.
Supply, Installation, testing & commissioning of Intelligent multi- criteria Detector along with mounting box & termination glands.
Supply, Installation, testing & commissioning of Isolator Module along with mounting box & termination glands.
Supply, Installation, testing & commissioning of Addressable control Relay module with required accessories along with junction box, glands and terminators ( For AC trip off, Access trip off, PA system, sprinkler flow switch, lift interface, sounder, fire fighter & telephone jack)
Supply, Installation, testing & commissioning of Strobe Lights along with mounting box & termination glands.
Supply, Installation, testing & commissioning of Addressable Manual call point/ station with mounting back box
1st category Cu armoured cables FRLS outer sheathed-2C x 1.5 Sq.mm
G.I. Cable tray with all other accessories 150 x 25mm (W x H) - (16 SWG - 1.6mm) without cover
IP 42 Wall/column Mounted distribution board with one Nos of DP 16/32A MCB as incomer and 8 Noss 6A/10A SP MCB as outgoing (12 way SPN DB)
NDOOR LED FIXTURES - -LED Square Recessed Downlighter- 24W
1st category Al armoured cables FRLS outer sheathed- 3C x 2.5 Sq.mm
SITC of air pure air & surface ambiance system
Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 6 kg capacity with necessary clamp for erection on Wall.(R3-ME-15-30-c)
Supplying and erecting CO2 Fire Extinguisher 4.5 kg
SITC of 2,300 CFM / 32MM ST.PR./ CSU / KITCHEN PANTRY Ceiling Suspended Cabinet Type DIDW/SISW Fresh Air Fans With Filter & Casing, drive, motor, mounting frame, starter, isolator & Necessary cabling & earthing strip For Following Capacities : As per AMCA210 standard "Laboratory Methods of testing fans for rating" Balancing quality As per AMCA204 / ISO 1940 standard.With VFD With Bypass Stater Panel Compatability wirh BMS and its accessaries and cabling.(BAH-HVAC-FA-113)
SITC of 400 CFM / 25MM ST.PR./ CSU / RMO ROOM TOILET SHAFT FAN Ceiling Suspended Cabinet Type DIDW/SISW Exhaust Air Fans & Casing, drive, motor, mounting frame, starter, isolator & Necessary cabling & earthing strip For Following Capacities : As per AMCA210 standard "Laboratory Methods of testing fans for rating" Balancing quality - As per AMCA204 / ISO 1940 standard With VFD With Bypass Stater Panel Compatability wirh BMS and its accessaries and cabling.(BAH-HVAC-FA-86)
CSMC Charges for 3 years after 1 year DLP (5% of SITC Cost)
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
BOQ_2194357.xls
BOQ • 0.40 MB
SBD.pdf
Tender Documents • 6.46 MB
Download all tender documents and submit your bid