Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.0 CrAdmitted-Finance | ₹3.0 Cr | L1 | Admitted-Finance |
| 2 | L2₹3.6 Cr+₹55.6 L (18.3%)Admitted-Finance | ₹3.6 Cr+₹55.6 L (18.3%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Calcutta Power Construction Co. L2 | JAYPEE PROJECTS LTD. L1 |
|---|---|---|---|---|---|
| 1.00ELECTRICAL - Part - A IMPORTANT NOTES : 1) Quantity UR means Unit Rate to be quoted. The quantity shall be as per site requirement & as directed by Engineer in Charge. 2) The quantities mentioned in this document are estimated on the basis of drawings prepared & submitted . The contractor has to physically measure, prepare BOQ & get written approval before procurement of material from Estate(E&M) Section.. 3) The contractor shall prepare measurement sheet for the work done & get it certified from Engineer in Charge. The billing will be done as per certified measurement sheet & P.O. 4) No rates (Supply & Installation) change for the quantity variation up to 25% 5) Measurement of LT Busduct shall be done by contractor at site as per actual location & then the item should be procured. | |||||
| 1.01 | 11kV VCB PANEL:
Supply, erection, testing and commissioning of Two panel vaccum switchgear unit (VCB) with following features:
a) The panel unit should have 11kV, 3pole, 50Hz, 400Amps, 250MVA, 13.1kA symmentrical breaking capacity, single phase motor operated & manual spring charging system with power pack and intelligent quasar metering with RS485 communication facilities as per IS:2516
b) Power pack 110 Volts DC unit for control circuit supply for each panel.
c) The PT Should be resin cast bus connected in separate bus PT enclosure, resin cast, dry type having voltage ration 11kV/110V,3phase,3wire,50Hz horizontal draw out type as per IS 3156. Burden of 100VA and accuracy class as 1.0
d)CT ratio : 100/5+5, Protection class 5P10 and metering accuracy class 1.0
e) Breaker should have E/F, O/C, S/C Protection with microprocessor based SCADA compatible E/F, S/C, O/C IDMTL Relay, along with Master trip for each panel,
f) ON, OFF, Spring charge, Trip circuit healthy, Indication must be in the panel.
g) WTI, OTI,Bunchhole alarm and trip with annunciation facility for each panel.
h) The above VCB should be eredted on masonary trench in angle iron frame including supply and fixing of angle iron frame.
i) Provision of in-built feeder earthing switch with required locking arrangement for each module.
j) The contractor has to supply the GA diagram, Complete Circuit wiring diagram, make list, Colour of Panel etc for getting approval from the section. The Panel will be inspected at manufacturing site by the Institute, travelling cost will be borned by the Institute.
Preferred Make:- ABB,Schnider,Siemens | 1 | No. | 29,00,000 ₹29,00,000 | 10,44,692 ₹10,44,692 Lowest |
| 2.00TRANSFORMER : | |||||
| 2.01 | Installation Testing commissioning of 11kV/415V, 500KVA transformer in substation no – 14 which includes filtration of transformer oil of 800L.
The details of job include: -
i) Testing of BDV
ii) Megger value, voltage ratio at all tap position
iii) Core Balance
iv) Vector group
v) O/C & S/C test and determination of internal impedance
vi) DGA Test report.
Following precommissioning tests are included in scope of contractor.
Testing of BDV
Megger value, voltage ratio at all tap position
Core Balance
Vector group
O/C & S/C test and determination of internal impedance
DGA Test report.
Following precommissioning tests are included in scope of the Contractor.
Testing of BDV
Megger value, voltage ratio at all tap position
Core Balance
Vector group
O/C & S/C test and determination of internal impedance
DGA Test report. | 1 | No. | 50,000 ₹50,000 Lowest | 3,29,373 ₹3,29,373 |
| 3.00LOW VOLTAGE SWITCH BOARDS : Supply, Unloading, Installation Testing and Commissioning of following TTA(Totally Type Tested Assembly) floor mounted panels as per IEC 61439 and SLD enclosed. The rate shall include unloading of Panels from transport vehicle, shifting to the stores or near by site location & then to the location of panels, including crane hiring charges, lifting shifting tools tackles, manpower, mounting on supports etc. as directed by site engineer. Work also involves positioning panel on prepared trench and support channels panel alignment, assembling transport section of panels, fixing of panels to based channels with fasteners or on floor / wall with anchor fasteners as per requirements, bus bar & earth bus interconnections, tightening of joints, bolts, hardware etc. and wiring of loosely supplied components and accessories as manufacturers instructions, operational checks but excluding supply of structural steel. (Supply, fabrication & painting of Structural steel has been included separately elsewhere in the tender). (rate shall include use of hydra, loading, unloading equipment/personel) The contractor has to supply the GA diagram, Complete Circuit wiring diagram, make list, Colour of Panel etc for getting approval from the section. The Panel will be inspected at manufacturing site by the Institute, travelling cost will be borned by the Institute. Preferred Panel Fabricators :- Authorised TTA Panel Fabricator of Legrand, Siemens, Schneider, ABB. | |||||
| 3.01 | MAIN LT PANEL : As per Annexure-A (Sl. No. 3.1) attached with Tender Document | 1 | No. | 19,00,000 ₹19,00,000 Lowest | 23,00,163 ₹23,00,163 |
| 3.02 | 240 KVAR AUTOMATIC POWER FACTOR CORRECTION : As per Annexure-A (Sl. No. 3.2) attached with Tender Document | 1 | No. | 19,50,000 ₹19,50,000 Lowest | 20,69,758 ₹20,69,758 |
| 3.03 | FIRE FIGHTING PANEL : As per Annexure-A (Sl. No. 3.3) attached with Tender Document | 1 | No. | 4,25,000 ₹4,25,000 Lowest | 4,97,799 ₹4,97,799 |
| 3.04 | WATER MANAGEMENT PANEL : As per Annexure-A (Sl. No. 3.4) attached with Tender Document | 1 | No. | 4,40,000 ₹4,40,000 Lowest | 5,40,766 ₹5,40,766 |
| 4.00MCB/MCCB & DISTRIBUTION BOARDS: Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) | |||||
Tender Value
₹2.3 Cr
EMD Value
₹4.7 L
Closing Date
17 Feb 2025, 11:00 amClosed
Superintending Engineer (EM)
Office of the Superintending Engineer (EM), Estate (EM) Works Section, Old Building IIT KGP
Electrical works including EOT Crane, HVAC Works and Fire Protection System associated with Construction of Deep and Shallow Water Maneuvering and Seakeeping Basin Facility for OE and NA department at IIT Kharagpur.
2025_IITKG_842636_1
IIT/IW/EM/NIT/41/2024-25
Open Tender
Electrical Works
Item Rate
180 days
IIT Kharagpur
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹4.7 L
Estate (EM) Works Section, Old Building IIT KGP
24 Feb 2025
3 Jan 2025
18 Feb 2025
3 Jan 2025
17 Feb 2025
3 Jan 2025
27 Jan 2025
Amount
ELECTRICAL - Part - A IMPORTANT NOTES : 1) Quantity UR means Unit Rate to be quoted. The quantity shall be as per site requirement & as directed by Engineer in Charge. 2) The quantities mentioned in this document are estimated on the basis of drawings prepared & submitted . The contractor has to physically measure, prepare BOQ & get written approval before procurement of material from Estate(E&M) Section.. 3) The contractor shall prepare measurement sheet for the work done & get it certified from Engineer in Charge. The billing will be done as per certified measurement sheet & P.O. 4) No rates (Supply & Installation) change for the quantity variation up to 25% 5) Measurement of LT Busduct shall be done by contractor at site as per actual location & then the item should be procured.
11kV VCB PANEL: Supply, erection, testing and commissioning of Two panel vaccum switchgear unit (VCB) with following features: a) The panel unit should have 11kV, 3pole, 50Hz, 400Amps, 250MVA, 13.1kA symmentrical breaking capacity, single phase motor operated & manual spring charging system with power pack and intelligent quasar metering with RS485 communication facilities as per IS:2516 b) Power pack 110 Volts DC unit for control circuit supply for each panel. c) The PT Should be resin cast bus connected in separate bus PT enclosure, resin cast, dry type having voltage ration 11kV/110V,3phase,3wire,50Hz horizontal draw out type as per IS 3156. Burden of 100VA and accuracy class as 1.0 d)CT ratio : 100/5+5, Protection class 5P10 and metering accuracy class 1.0 e) Breaker should have E/F, O/C, S/C Protection with microprocessor based SCADA compatible E/F, S/C, O/C IDMTL Relay, along with Master trip for each panel, f) ON, OFF, Spring charge, Trip circuit healthy, Indication must be in the panel. g) WTI, OTI,Bunchhole alarm and trip with annunciation facility for each panel. h) The above VCB should be eredted on masonary trench in angle iron frame including supply and fixing of angle iron frame. i) Provision of in-built feeder earthing switch with required locking arrangement for each module. j) The contractor has to supply the GA diagram, Complete Circuit wiring diagram, make list, Colour of Panel etc for getting approval from the section. The Panel will be inspected at manufacturing site by the Institute, travelling cost will be borned by the Institute. Preferred Make:- ABB,Schnider,Siemens
TRANSFORMER :
Installation Testing commissioning of 11kV/415V, 500KVA transformer in substation no – 14 which includes filtration of transformer oil of 800L. The details of job include: - i) Testing of BDV ii) Megger value, voltage ratio at all tap position iii) Core Balance iv) Vector group v) O/C & S/C test and determination of internal impedance vi) DGA Test report. Following precommissioning tests are included in scope of contractor. Testing of BDV Megger value, voltage ratio at all tap position Core Balance Vector group O/C & S/C test and determination of internal impedance DGA Test report. Following precommissioning tests are included in scope of the Contractor. Testing of BDV Megger value, voltage ratio at all tap position Core Balance Vector group O/C & S/C test and determination of internal impedance DGA Test report.
LOW VOLTAGE SWITCH BOARDS : Supply, Unloading, Installation Testing and Commissioning of following TTA(Totally Type Tested Assembly) floor mounted panels as per IEC 61439 and SLD enclosed. The rate shall include unloading of Panels from transport vehicle, shifting to the stores or near by site location & then to the location of panels, including crane hiring charges, lifting shifting tools tackles, manpower, mounting on supports etc. as directed by site engineer. Work also involves positioning panel on prepared trench and support channels panel alignment, assembling transport section of panels, fixing of panels to based channels with fasteners or on floor / wall with anchor fasteners as per requirements, bus bar & earth bus interconnections, tightening of joints, bolts, hardware etc. and wiring of loosely supplied components and accessories as manufacturers instructions, operational checks but excluding supply of structural steel. (Supply, fabrication & painting of Structural steel has been included separately elsewhere in the tender). (rate shall include use of hydra, loading, unloading equipment/personel) The contractor has to supply the GA diagram, Complete Circuit wiring diagram, make list, Colour of Panel etc for getting approval from the section. The Panel will be inspected at manufacturing site by the Institute, travelling cost will be borned by the Institute. Preferred Panel Fabricators :- Authorised TTA Panel Fabricator of Legrand, Siemens, Schneider, ABB.
MAIN LT PANEL : As per Annexure-A (Sl. No. 3.1) attached with Tender Document
240 KVAR AUTOMATIC POWER FACTOR CORRECTION : As per Annexure-A (Sl. No. 3.2) attached with Tender Document
FIRE FIGHTING PANEL : As per Annexure-A (Sl. No. 3.3) attached with Tender Document
WATER MANAGEMENT PANEL : As per Annexure-A (Sl. No. 3.4) attached with Tender Document
MCB/MCCB & DISTRIBUTION BOARDS: Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way (4 + 24), Double door
12 way (4 +36), Double door
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, Inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
4 way (4 + 12), Double door
6 way (4 + 18), Double door
12 way (4 + 36), Double door
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
12 way , Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Triple pole
Four pole
Supplying and fixing 40A to 63A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Triple pole
Four pole
Supplying and fixing 80A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Four pole
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCBO), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. Surge Protection Device:
Supplying, installation & marking of surge arrestor/ surge protection device at the main distribution board after the incoming breaker of type 1+2 tested for Imax 50 kA for three phase and neutral
Supplying, installation & marking of surge arrestor/ surge protection device at the sub main distribution board after the incoming breaker of type 2 tested for Imax 40 kA for three phase and neutral
SWITCH BOXES & SWITCH SOCKET Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 amps switch
15/16 A switch
3 pin 5/6 A socket outlet
6 pin 15/16 A socket outlet
Telephone socket outlet
RJ45 DATA SOCKET
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
CEILLING FAN AND EXHAUST FAN
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Supply, Installation, Testing and Commissioning of 450 mm Sweep, 220 - 240 volt, a.c., 50 HZ, Single phase, metal blades with powerful capacitor type durable motor, rubber mountings with metal rigid frame Heavy Duty type Exhaust Fan complete with Louver protection for bird & all accessories of the following specification :- Power Input =/ < 150 Watts, Speed = /< 1000 RPM, Air Delivery = /> 3900 CMH and mounting with grouted frame/ clamp arrangements with necessary accessories & connection with mending good to the damages.
Supply & Fixing of 140 - 240 volt a.c., 50 HZ, single phase Input Voltage, Industrial type Wall/ Column Mounted Heavy Duty Industrial Almonard Fancomplete unit & all accessories of the following Specification :- Heavy & robust Cast Iron base, Aluminum alloy single piece blade, Powder coated paint in metallic finish with Power Consumption < /= 100 Watt, Speed >/=1400 RPM, Air Delivery >/= 150 CMM , 450 mm Sweep, Power Factor > = 0.99, THD < 5% and connection with 3X1.5 sq mm FRLS PVC insulated copper conductor single core cable and earthing etc as required. (Makes-CGL / Khaitan/Orient).
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. 510 mm sweep
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75mmX75mm)
3 Module (100mmX75mm)
4 Module (125mmX75mm)
6 Module (200mmX75mm)
8 Module (125mmX125mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module
3 Module
4 Module
6 Module
8 Module
CABLE SYSTEM. Installation of cables along with associated work like sleeving for cable entry through wall / slab / road crossing shall not be paid extra. The same shall be considered as cable laying part of Power, control, earthing cable laying system activity. GI/Hume pipes rates shall be considered extra. Supply and laying of HT cables in cable ducts/uPVC conduits as required and including testing and commissioning of the following sizes of 11KV grade multicore aluminium/copper conductor XLPE/PVC insulated and PVC sheathed armoured cable conforming to IS : 7098 (Part-II)
HT cable. Supply of PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade enearthed. 3C X 95Sq. mm. Al, 11 kV, Armoured XLPE (UE)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 120 sq. mm
LT POWER AND CONTROL CABLES : Supply of 1.1KV Grade XLPE/PVC insulated copper/aluminium conductor steel of armoured/unarmoured power cables as per the specs. Supply and laying of LT cables in cable ducts/uPVC conduits as required and including testing and commissioning of the following sizes of 1.1KV grade multicore aluminium/copper conductor XLPE/PVC insulated and PVC sheathed armoured cable conforming to IS : 7098 (Part-I) / IS : 1554 (Part-I).
1.5 mm² x 3C CU Armoured XLPE Cable
1.5 mm² x 4C CU Armoured XLPE Cable
2.5 mm² x 4C CU Armoured XLPE Cable
4 mm² x 4C CU Armoured XLPE Cable
6 mm² x 4C CU Armoured XLPE Cable
10 mm² x 4C CU Armoured XLPE Cable
25 mm² x 3.5C AL Armoured XLPE Cable
35 mm² x 3.5C AL Armoured XLPE Cable
50 mm² x 3.5C AL Armoured XLPE Cable
150 mm² x 3.5C AL Armoured XLPE Cable
300 mm² x 3.5C AL Armoured XLPE Cable
300 mm² x 3.5C AL Armoured XLPE Cable
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
HT Cable Termination. Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
LT Cable Termination. Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3 X 1.5 sq. mm
3½ X 25 sq. mm (28mm)
3½ X 35 sq. mm (32mm)
3½ X 50 sq. mm (35mm)
3½ X 150 sq. mm (50mm)
3½ X 300 sq. mm (70mm)
3½ X 300 sq. mm (70mm)
4 X 10 sq. mm (25mm)
4 X 2.5 sq. mm
4 X 4 sq. mm
4 X 6 sq. mm
Water Proof Termination: Supply, installation of FLP & WP terminations with Double compression type Brass-Nickel cable gland , lugs & PVC Shrouds. The gland shall be provided with earth tag , ensures earth continuity between gland and equipment, etc. complete as required.
4 X 1.5 sq. mm
INTERNAL WIRING: Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
LIGHT FITTING: Supply, Unloading, Installation, Testing & Commissioning of standard light fittings and lighting accessories including lamp. The scope shall includes unpacking assembly of luminaries, providing of all hardware such as chain, nuts, anchor fasteners, bolts, screws, cleats, clamps, PVC insulated wires / cables from Junction box to lighting fixtures, ceiling roses ball and socket 'arrangement with J.B., suspension conduit pipe 0.5 m long 19 mm black MS conduit down rod for light fitting. The cost of fabrication and installation of MS supports will be the part of this item only. The scope of work also includes any modifications required to be carried out on the mounting bracket to suit mounting of light fixtures & any modification inside control gear box / fixture for proper commissioning of fixture. All LED Fittings are with Driver, LED luminaries housing/body shall be pressure die cast aluminium or extruded Aluminium or CRCA as specified along with finished powder coating, complete with all accessories.
Fixture shall be supplied with the following along with mounting accessories: - CRCA Powder coated with white housing - Recess mounted - Bottom Opening - High efficacy long life LEDs - Aesthetic CRCA powder coated bottom frame - Special translucent high transmisivity, non yellowing HET diffuser - Non-Integral multi stage CCCV electronic driver with 3kV surge protection. Driver shall be pre wired upto the terminal block - Confirms IS 10322 / Part 5 / sec 1 : 1987 - Specification:- Lumen Output = 3600-3800 lm, CCT = 6500K, CRI >/= 80, P.f >/= 0.95, Luminous efficacy >/= 120 lumen/watt , THD =/< 10%, - Suitable for 600MM X 600MM (2ft x 2ft ) Cutout size in Calcium silicate / non walkable false ceiling. - Similar to Philips make Item Model - RC380B LED36S-6500 G6 L60W60 PSU OD S1 ,
Fixture shall be supplied with the following along with mounting accessories: - CRCA Powder coated with white housing - Recess mounted - Bottom Opening - High efficacy long life LEDs - Aesthetic CRCA powder coated bottom frame - Special translucent high transmisivity, non yellowing HET diffuser - Non-Integral multi stage CCCV electronic driver with 3kV surge protection. Driver shall be pre wired upto the terminal block - Confirms IS 10322 / Part 5 / sec 1 : 1987 - Specification:- Lumen Output = 4000-4200 lm, CCT = 6500K, CRI >/= 80, P.f >/= 0.95, Luminous efficacy >/= 120 lumen/watt , THD =/< 10%, - Suitable for 600MM X 600MM(2ftX2ft) Cutout size in Calcium silicate / non walkable false ceiling. - Similar to Philips make Item Model - RC380B LED42S-6500 G6 L60W60 PSU OD S1 ,
Fixture shall be supplied with the following along with mounting accessories: - High power, high efficiency 140 mm to 150 mm dia. indoor recess/surface mounting LED Downlighter with Pressure Diecast Aluminum Housing & Polycarbnate diffuser and electronic driver of Short Circuit & Surge Protection facilities. - Surface/recess mounting type, Bottom Opening including all necessary hardwares/accessories - Pressure die cast aluminium housing with special wave shaped radial fins, black powder coated for superior thermal performance - Specially designed, easy to install mounting clips - Specification :- CCT = 6500K, Lumen >/= 1500, CRI >/= 80, P.f >/= 0.95, Efficacy(Lumen/watt) >/ = 110, THD < 10 %, - Suitable for 15 W LED downlighter - LED lumen output of the luminaire of a minimum of 1500 lumens. - Similar to Philips make product code - DN296B LED15S-6500 PSU WH / SM296C LED15S-6500 PSU WH
Fixture shall be supplied with the following along with mounting accessories: - Surface mounting type including all necessary hardwares/accessories - IP66 Outdoor LED luminaire made with Polycarbonate Cover & die cast aluminium housing suitable for outdoor/streetlight mounting with energy efficient electronic driver. - Fitting should be with dust proof, IP66 with frosted ends & gasket with transparent prismatic interior & smooth exterior - All other necessary accessories Specification :- CCT >/= 5700 - 6500K, Lumen >/= 4000 - 4500, CRI >/= 70, P.f >= 0.95, Efficacy(Lumen/watt) >/=120 lumen/watt, THD < 10 % and Surge protection as per IS 5885 - LED lumen output of the luminaire of a minimum of 4000 lumens. - Similar to Philips make Item Model - BRP331 LED 42 CW R5N PC PSU S1 V1
Fixture shall be supplied with the following along with mounting accessories: - Surface mounting type including all necessary hardwares/accessories - 4 ft.(Fixture Size ) commercial applications Suspended/ Surface mounted LED tube light Linear batten with extruded aluminium housing and high transivity polycarbonate diffuser including intregrated electronic driver with all accessories & Suspended clamps. - Fitting should be with polycarbonate body, IP40 with frosted ends & gasket with transparent prismatic interior & smooth exterior - All other necessary accessories - Specification:- CCT = 6500K, Lumen >/= 4000, CRI >/= 80,P.f >/= 0.90, Efficacy(Lm/watt)>/= 110, THD </= 10%. - Similar to Philips make Item Model - BN 170C LED40S-6500 MW D0 L120 S1 L1. - LED lumen output of the luminaire of a minimum of 4000 lumens.
Fixture shall be supplied with the following along with mounting accessories: - Surface mounting Highbay type including all necessary hardwares/accessories - Ceiling (Surface/Suspended) mounted Vertical Round type Highbay/ Mediumbay Industrial PDC housing Body luminaire with IK08 Polycarbonate Cover including electronic driver with High efficacy long life LEDs . - Special translucent high transmisivity, non yellowing PMMA diffuser - Non-Integral multi stage CCCV electronic driver with 3kV surge protection. Driver shall be pre-wired upto the terminal block - Confirms IS 10322 / Part 5 / sec 1 : 1987 - Specification :- CCT >/= 5700K, Lumen >/= 10000, CRI >/= 70, P.f >/= 0.95, Efficacy(Lumen/watt) >/=150, THD < 10 %, -Similar to Philips make Item Model - BY615P LED100S 5700 WB PSU GR ,
EARTHING SYSTEMS EARTHING STATIONS: Supply, Installation of earth stations with necessary all materials, labour, excavation & all civil works, etc. as per IS/IEC etc. Complete with all required hardware as mention below.
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
EARTHING STRIPs/WIREs: Supply, laying of hot dipped galvanized (GI)/copper bare earth conductor bar / flexible wire /strip of following sizes along the cable trenches or cable trays or fixing to walls or structures or buried individually in paved/unpaved areas but excluding civil work finishing after layering of earthing strips etc. The installation shall include welded joints with 4'' over lapping of the strips. Welded joints shall be used for G.I. strips. Welded joints after welding shall be painted with anticorrosive black bitumen paint , applying anti corrosive primer paint and two coat each of bituminous paint for buried earth strip. Excavation & backfilling of soil for burying the strip wherever applicable is paid extra as per the rate of excavation and backfilling rate. Jumper 150 mm x 50 mm shall be provided at every 10 meter interval for main earthing strip under instruction of engg. in charge and jumper rate paid extra.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating(Jointing shall be done by overlapping and with welded joints with 4'' over lapping of the strips)
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
LIGHTNING PROTECTION SYSTEM (CONVENTIONAL LIGHTNING ARRESTOR): Air Terminal ( Horizantal ) :
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc.complete as required.
Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required.
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
HOT DIPPED GALVANIZED IRON CABLE TRAYS Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc.as required.
100mm wide cable tray perforated type (1.6 mm thick & 50 mm high collar)
150mm wide cable tray perforated type (1.6 mm thick & 50 mm high collar)
300 mm wide cable tray perforated type (1.6 mm thick & 50 mm high collar)
450 mm wide cable tray perforated type (2 mm thick & 50 mm high collar)
600 mm wide cable tray ladder type (2 mm thick & 62.5 mm high collar)
750 mm wide cable tray ladder type (2 mm thick & 62.5 mm high collar)
UPS SYSTEM
Supply,Unloading, Installation, testing & Commissioning of the following rating of UPS System including unloading, transportation from store to site ,errection insulation, testing of UPS System including Battery and Battery rack errection & Installation under the supervision of supplier of UPS. The scope also includes supply and installation of the flexible wire from SDF enclosure to UPS and UPS to Main UPS DB. Flexible wire shall be as per the recommendation of UPS supplier. Supply,Unloading at site, handling, erection, alignment and other associated work of 20 kVA UPS under the supervision of supplier's commissioning engineer. UPS shall have three phase input as well as output. Supply,Unloading at site, handling, erection, alignment and other associated work of 12V, (Suitable AH capacity and quantity) SMF battery bank to provide 30 Mins backup time. Minimum 96000 VAh. Battery to be provided.
ISOLATOR FOR UPS. Supply, installation of 16 kA, 63A TP +N MCCB, with rotary handle in enclosure made up of 1.6mm thick CRCA sheet, pretreated in seven tank process, powder coated with paint thickness not less than 100 micron ( Shade RAL 7032 ). The MCCB shall be interlocked to prevent the enclosure Door being opened unless the MCCB in OFF position and Also Enclosure shall be provided with facilities for Padlocking in the OFF position Cable end box shall be provided for incoming and outgoing cables.
Supply & installation of cable of suitable size from UPS isolator to UPS & from UPS to isolator. (Distance Between Isolator to UPS & UPS to isolator will be max. 5 Mtr.)
4 Runs x 1 core x 6 mm² CU XLPE flexible leads for 20 KVA UPS
MISCELLANEOUS ITEMS :
Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
Supplying and fixing cable route marker with 10 cm X 10 cm X 5mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
Safety items Safety Equipment's: Supply, Installation of below mention safety equipment including all labour and materials etc., complete as per directions of Engineer-In-Charge.
Sand buckets with floor stand and sand (set of 4 buckets of 9 Ltr. capacity) Stand size : 1.5 M x 0.9 M x 0.6 M stand shall be painted with epoxy paint as per IS requirement.
Caution boards ( 433V each)
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Rubber mats of 11 KV grade 2 Mtrs x 1 Mtrs x 6 mm Thick
Rubber Hand Gloves pair ( 11 KV Grade )
Shock treatment chart with teak wood frame and glass cover as approved by Electrical Inspectorate. In English & Local language.
First aid box with standard items
Dry powder type fire extinguisher of 5 Kg. Capacity
Supply, Installation of 4.5kg capacity CO2 type fire extinguishers complete with mounting brackets, spray nozzles, connecting pipes, "OPEN/CLOSE" valves with all other necessary accessories complete as required.
Electrical single line diagram (As Built drawing) with teak wood frame and glass cover.
Structural Steel Fabrication
Supply, transport, unloading, shifting & Fabrication of steel sections and erection of MS base frames, MS angle channels, flat etc. for supporting various items of equipment such as various panels/switchgear, dummy panels, adaptor boxes addition support for proper cable termination, MS Fabricated cable trays, push button stations, junction boxes, light fittings, DB etc. The scope include welding, bolting, chipping , grouting etc., including applying one antirust coat of approved primer and two finished coats of approved paint with primer & paint, breaking and finishing of walls, floors etc. Contractor has to apply one coat of antirust paint (Red-oxide ) before installation. The scope is inclusive of minor civil work as required, supply of GI hardware materials, consumables, tools & tackles and necessary labour with supervision but not limited to, and complete as per approved drawings, specification and directions of Engineer-In charge. The scope also includes transportation of material from owner’s issue point to actual place of work by contractor's own lifting and transporting arrangement.
Making masonry cable trench with floor cutting making 5' inch wall (both side). Size 800 mm width X 800 mm depth x 3000 mm length for erection of 2 panel 11kV VCB on trench and HT cable laying.
Supply and Laying of 100mm dia class B G.I. pipe in underground trench, along walls for cable protection. Make: TATA. JINDAL, BANSAL
Gripple Hangers System
M10 Eyebolt with Nut & Washer (2 No Each)
M10 Nut & Washer (2No. Each)
GHF NO.4 LOOP WIRE 5.0 MTR
Fire Protection System - Part - B Special Note: 1) The contractor has to supply the Complete Circuit wiring diagram for Fire Protection System, make list etc for getting approval from the Section. 2)The work includes Application submission and liaisoning with WBFES for obtaining FSR and further NOC from WBFES is the responsibility of the contractor. Application Fees required will be borned by the Institute. Necessary drawings will be provided by the project Consultant. Hydrant System (Refer attached technical data sheets) Supplying, fixing, testing and commissioning of The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above
Supplying,testing, installing & commissioning of BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified
Supply, fixing, testing and commissioning of Single headed SS-304 fire hydrant valve as per IS: 5290 (ISI Marked Type-A) with 80 mm N.B. flanged inlet, brass spindle, 63 mm dia instantaneous type SS. coupling blank cap & chain. Including tapping from wet riser complete as required.
Supply, fixing, testing and commissioning of swinging type First Aid hose reel in red colour with 25mm dia x 30 mts long and below mentioned size heavy duty rubber water hose terminating with ABS nozzle of 5 mm outlet with shut off valve as per IS: 8090 - 1976 complete with drum and brackets for fixing on walls, bolts & nuts conforming to IS: 884 (ISI Makred) complete as required.
Supply, fixing, testing and commissioning of RRL Hose pipe, 63 mm dia and 15 mts long, conforming to IS: 636 Type-A (ISI marked) suitable for bursting pressure not less than 35.7 Kg/Sqcm. type A with SS-304 heavy duty instantaneous type coupling (Pair male & female parts) conforming to IS: 903 (ISI makred)..
Supply, fixing, testing and commissioning of 63 mm dia instantaneous pattern branch short SS-304 branch pipe as per IS: 903 (ISI marked) 20 mm dia nozzle, suitable for inter connection to hose pipes coupling complete as required.
Supply, fixing, testing and commissioning of fire cabinet of size not less than 0.75 x 0.6 x 0.25 mtr made out of M.S. sheet not less than 1.5 mm thick having central opening and 4 mm thick glazed acryclic sheet doors (Two nos.) suitably marked on the outside 'with the letters "FIRE HOSE" including necessary locking arrangement and painting in red colour suitable to accommodate, 2 nos 15 mtr long Hose pipe, branch pipe, nozzle and painted in red along with GI support angles for internal hydrants.
Supply, fixing, testing and commissioning of brass body Ball valve with lever of pressure rating 300 PSIg, including providing necessary union/flange and making proper connection.
Supply, fixing of Fire man Axe
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Automatic Sprinkler System (Refer attached technical data sheets) Supplying, fixing, testing and commissioning of The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above
65 NB (Rate only)
50 NB (Rate only)
40 NB (Rate only)
Installation, testing, & commissioning of Quartzoid bulb Standard response, Standard coverage sprinklers to be Operated at 68 Deg C, K80 FM Approved /UL Listed upright type
Supply, fixing, testing and commissioning of FM approved/ UL listed Alarm control valve with automatic Alarm Gong to be connected with control valve, drain, test valve as per manufacturer's specifications complete as required. Including matching flanges, nut bolts, gaskets, etc.
Supply, fixing, testing and commissioning of FM/UL listed Flow switch on sprinkler riser for Aerosol area and shall be connected to fire alarm panel through cable. Cable shall be measured seperately.
Supply, installation, testing and commissioning of IS 14846 OS & Y , Rising Spindle Gate valve, PN 10, With flanges nut bolts, etc.
Supply, fixing, testing and commissioning of brass body Ball valve with lever of pressure rating 300 PSIg, including providing necessary union/flange and making proper connection.
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Fire water Pumping System (Refer attached technical data sheets)
Supply, Installation Testing commissioning of End suction 96 m3/hr 70 m head, Main electric Pump along with accessories.
Supply, Installation Testing commissioning of End suction 96 m3/hr 70 m head, Diesel Engine Standby Pump with fuel tank and other accessories
Supply, Installation Testing commissioning of Vertical inline, Electric operated 10.8 m3/hr 70m head, Jockey pump with accessories
Supply, Installation Testing commissioning of MCC panel for above listed pumps as per attached electrical single line diagram.
Supplying, fixing, testing and commissioning of The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above
Supply, installation, testing and commissioning of IS 14846 OS & Y , Rising Spindle Gate valve, PN 10, With flanges nut bolts, etc.
Supply, installation, testing and commissioning of NON - RETURN VALVE with dual plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified.
Supply, installation, testing and commissioning of Y type Strainer
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Fire Extinguishers (Refer attached technical data sheets)
FIRE EXTINGUISHER 9KG ABC TYPE (Rate only)
FIRE EXTINGUISHER 6KG ABC TYPE
FIRE EXTINGUISHER 4.5KG CO2 TYPE
FIRE EXTINGUISHER 9LTR. FOAM TYPE
Fire Alarm System
Supplying, installation, testing & commissioning of addressable manual call point complete as required. Please refer attached technical data sheet.
Supplying, installation, testing & commisssioning of intelligent addressable programmable sounder complete as required. Please refer attached technical data sheet.
Supply, Installation, testing commissing of addressable Monitor Module,Operating Temperature-20 ºC to +60 ºC with back box & mounting accessories. Please refer attached technical data sheet.
Supply, Installation, testing commissing of Addressable Smoke Detector with built in LED, mounting base complete with all connection etc. Please refer attached technical data sheet.
Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required. Please refer attached technical data sheet.
Supplying, installation, testing & commissioning of addressable beam detector with short circuit isolator (inbuilt or seperate) complete with emitter and receiver including connections with remote test features etc complete as required. Please refer attached technical data sheet.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Spares
FIRE EXTINGUISHER 6KG ABC TYPE
FIRE EXTINGUISHER 4.5KG CO2 TYPE
Supply of RRL Hose pipe, 63 mm dia and 15 mts long, conforming to IS: 636 Type-A (ISI marked) suitable for bursting pressure not less than 35.7 Kg/Sqcm. type A with SS-304 heavy duty instantaneous type coupling (Pair male & female parts) conforming to IS: 903 (ISI makred)..
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
EOT Crane including Gantry Girder works - Part C Special Note: The contractor has to supply the GA diagram, design & drawing with TDS recommended from OEM, complete circuit wiring diagram, make list, Colour etc for getting approval from the section.
Supply, transport, loading / unloading, erection, testing and commissioning of EOT crane - 3T capacity including Rails (Refer attached technical data sheets and drawings) as per following data :- i. Top of the crane rail shall be 9620mm above FFL. ii. Minimum clear gap between the topmost part of the crane and the bottom most part of the truss shall be 100mm. iii. Shed side clearance shall be 190mm. iv. Max. Hook height shall be 9600mm above FFL. v. Centre to centre of rails shall be 23.7Mtr.
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. The Job Includes supply & fixing of approx 240 mtr. ISMB 450 Gantry Girder & ISMC 250 Channel with necessary ISA 75x75x12 angle , Tor 16 Holdfast fastner etc. as per attached drawing of G.A. of Crane Bracket & Gantry Girder.
HVAC Works - Part -D
Providing and installing roof mounted wind driven natural turbo ventilators including making suitable cut outs in roofing sheets, sealing the openings to provide weathertight and watertight roof. Etc. complete. 1200 CFM capacity, approx. 600 mm diameter
Providing , installing, testing and commissioning of Blue Star Hi Wall units with R32 refrigerant complete with power cable from the unit to the power socket.
2.0 TR x 3 STAR - FS324YBTU
1.5 TR x 3 STAR - FS318DLTU
Providing and installing wall mounted powder coated stand for outdoor unit
Providing, installing, testing and commissioning of 5 KVA V-Guard voltage stabilizer
Providing and laying / fixing copper piping for the above Hi Wall units
Providing and fixing microcellular pipe insulation Class O
6.35 ID x 10 mm thick
12.5 ID x 10 mm thick
25 mm ID x 9 mm thick
Providing and laying flexible copper cable (3C x 2.5 sq. mm.) including clamping / fixing to RCC and wall supports. Make: Polycab
Providing and fixing 25 mm UPVC drain pipe to the required line and slope including clamping / fixing to RC and wall supports. Make: Astral
Calcutta Power Construction Co. (BID ID -3172444)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 17.04 MB
BOQ_885728.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .