Electrical work in c/w Development of infrastructure/maintenance facilities for trains at Suratgarh Station, Work for shifting ARF at other location in Suratgarh Yard to facilitate coaching terminal at Suratgarh Junction and Upgradation/ Augmentation/Creation of Disaster management Rolling Stock maintenance facility at Suratgarh over BKN Div.
06-EL-BKN-E-Tender-26-27
06-EL-BKN-E-Tender-26-27
Open
18 Months
Alwar, Rajasthan
₹0
₹10.1 L
1 Jun 2026
1 Jun 2026
11 Jun 2026
85/90 GSM showing over all electrical installation at site as per requirement and as per specification. 5268565.0
0 Description:- A) Supply, installation, testing & commissioning of complete uni pack CSS-1 of with
O/G), GI enclosure and LT distribution board with tie-feeder as per specification. B) Supply, installation, testing & commissioning of complete uni pack CSS-2 of with 01 no. 11 kV 500KVA dry type transformer, HT received from CSS-1, GI enclosure and LT distribution board with tie-feeder and
Description:- Supply, installation, testing and commissioning of 11 kV, 630A, 21kA / 3 sec, outdoor
Switch (LBS) & 1 No. Vacuum Circuit Breaker (VCB) as per Specification. (Inspection Clause : By RITES at factory Premises )
beam ISHB 150, size 150mm x 150mm of length 10.0 Mtrs. with required foundation and painting etc. as per specification.
5 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY 5 Description:- Supply, fixing, connecting and charging of off load type Gang operated 3 pole switch suitable for 400 Amp 11 KV 3 phase central post rotating double break isolator complete with MS hardware copper moving and fixed contact, assembly of 9 nos. pin insulator, GI pipe of suitable length of operation including 3 nos. vertical mounted 11 kV horn gap fuse set/dropout 11 kV barrel drop out fuses mounted on 6 no. pin insulator as per standard spec. on existing H pole.
Description:- Design, Supply, install, testing & commissioning of LT panel with 2X800Amp ACB as
with suitable capacity CT, Digital Ammeter, Voltmeter, Energy meter & selector Switches as per specification. (Inspection Clause : By Railway Representative at factory Premises)
Description:- Design, manufacturing, supply, testing, erection and commissioning of LT panel, medium voltage made by 2 mm CRCA sheet with- (a) Incoming 1 x 400 amps.4 pole MCCB with adj
(Ics = 100% Icu) with proper foundation work as per technical specification. (Inspection Clause : By Railway Representative at factory Premises)
Description:- Design, supply, fixing & commissioning of LT panel made by 2 mm CRCA sheet with 1
63A,16kA and 2 nos. 4 pole MCCB 40A,16kA All MCCB should be adjustable over load 80% to 100% & Adjustable short circuit, Ics = 100% Ics with meter & indication LED, copper bus bar etc. with foundation as per spec. (Inspection Clause : By Railway Representative at factory Premises)
VPI dry type transformer with proper enclosure as per requirements.(Inspection Clause : By Railway Representative at factory Premises)
down transformer 230V/40-72 Volts outdoor type as per specification.
Description:- Supply & erection of 5 m high with double arm model no. BOP-5030 of Bajaj or similar, pole shaft material S355J0 or equivalent as per IS, hot dip galvanized steel octagonal pole
(for mounting inside the base compartment of pole), foundation bolt size 4x16mm dia. 600 mm in length including excavation and making foundation as per spec. and drawing. It shall be galvanized internally and externally by single dipping method. The pole and foundation shall be made as per specification and attached drawing. (Inspection Clause : By RITES at factory Premises )
Description:- Supply and fixing of 250 Watt LED Flood light with required fixing arrangement outdoor type, Aluminum dia cast housing instant start Input operating Voltage range and frequency
temperature with CRI more than 85, Power Factor 0.95, Working life for LED (Minimum 50,000 burning hours at L70 lumen maintenance, THD should be less than 20 , make PHILIPS / EDISON / OREVA / PYROTECH / SURYA /CG / OSRAM / BAJAJ / HAVELLS / HALONIX or similar same as per tech spec.
Description:- PIT LIGHTING: Design, fabrication, supply, erection, testing & commissioning of LED based luminaire having input voltage 40V-72V AC, frequency 50/60 Hz, Input Power 16 watt with IP-
a way to illuminate the under frame of the coach and path lighting of pit line. The cubicle shall be fabricated with MS sheet / Poly carbonate body with high built of epoxy coating, heat resistive up to
specifications. (Inspection Clause : By RITES at factory Premises )
Description:- Cat walk lights: Design, fabrication, supply, erection, testing &commissioning of LED based Cat walk lighting luminaires complete, with input wattage of 22W suitable to work on 40V-72V
should be Ingress protection IP- 67 & Impact protection IK10. The cubicle shall be fabricated with MS sheet / Poly carbonate body with high built of epoxy coating, heat resistive up to 70 degree centigrade complete with weather proof and rust proof. Fixture shall be IRGOLD-B1 of M/s Goldwyn Limited or equivalent. (Inspection Clause : By RITES at factory Premises )
BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY Description:- Supply, installation, testing and commissioning (with foundation/supporting structure) of 200 W LED circular highbay with toughened glass fitting with glass cover suspended 15 type [IP-66] with additional safety chain, luminaries has efficacy upto 130 lm/W with10kV SPD as similar to cat no. CIP-325-200-57-60D-HL5-LM-NSG of Crompton or equivalent with suitable junction box for looping. Make shall be as per specification and as per site requirements. Make PHILIPS / EDISON / OREVA / PYROTECH / SURYA /CG / OSRAM / BAJAJ / HAVELLS / HALONIX or similar same as per tech spec. (Inspection Clause : By Railway Representative at factory Premises)
bore 25mm or as suitable for street light, clamps, nuts, bolts, cable, etc. as per instruction of site engineer.
site requirement and instructions of Railway supervisor.
PVC Unarmored copper cable ISI marked (IS:694) of 1.1 kV grade in existing surface or recessed conduit/casing capping including making connections etc. as required.
insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe with transportation as per spec.
insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe with transportation as per spec
insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe with transportation as per spec.
insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe with transportation as per spec.
insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe with transportation as per spec.
insulated PVC outer sheathed aluminium conductor armoured cable in trench/pipe with transportation as per spec.
Description:- Laying, testing & commissioning of 11KV / 33 KV XLPE cable in air / ground / in trench / spun / HDPE pipe, with transportation from main depot to required site, and as per specification
for collection of cables from the Elect Maintenance / Works Depot including loading, unloading, transportation and return of un-used cables back at Depot. Cost of these provisions is deemed to be included in this item.
Description:- Transportation, Laying, testing and commissioning of LT XLPE cable 4c/1c x400/630
Railways. The contractor will be responsible for collection of cables from the Elect Maintenance / Works Depot including loading, unloading, transportation and return of un-used cables back at Depot. Cost of these provisions is deemed to be included in the quoted rate for this item.
Sqmm cable all as specified and as directed.
PN 6, PE 80 as per requirement. (Inspection Clause : By Railway Representative at factory Premises)
29 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY Description:- Laying of HDPE pipe conforming to IS 4984:2016, 50 mm dia, wall thickness 3 mm, under the road. The work involves laying of HDPE pipe along with transportation.
requirement. (Inspection Clause : By Railway Representative at factory Premises)
work involves laying of HDPE pipe with transportation.
requirement. (Inspection Clause : By RITES at factory Premises )
road. The work involves laying of HDPE pipe with transportation.
per requirement. (Inspection Clause : By Railway Representative at factory Premises)
work involves laying of HDPE pipe along with transportation.
Kachha/ Pakka land and all type of soil as per site requirement and without protective layer of brick) Surface of trench shall be made good in all respect and satisfaction of site engineer.
Kachha/ Pakka land and all type of soil as per site requirement and without protective layer of brick) Surface of trench shall be made good in all respect and satisfaction of site engineer
Description:- Cutting of cement concrete floors (PCC / RCC), any type / depth as required for laying of UG cables in trenches and disposing off the excavated material as directed including refilling the
barricading and danger lighting around the excavated areas safety precaution is a mandatory requirement and cost of this provision, wherever required, is deemed to be included in the quoted rate of this item
1.5mm thick size 150X100mm welded with 12mm dia MS rod 85 cm long. The lower end of rod should be turned in hooks shape and attached with the cable at the time of laying.
Description:- Drilling of horizontal bore below Track/Road by pushing method (trenchless
Railway representative taking all necessary safety precautions related track and movement of trains. Horizontal boring will be done at minimum 1.5 Mtr. Below from ground level at railway track portion.
size & 2mm thick, with cover and all fixing arrangements as per specification and as per site requirement.
and MS flat 35x5mm as per technical specification. (Inspection Clause : By RITES at factory Premises )
part-I for passing incoming and outgoing cable from ground through it size 38 mm dia. Pipe should be of reputed make and as per tech. spec.
part-I for passing incoming and outgoing cable from ground through it size 50 mm dia. Pipe should be of reputed make and as per tech. spec.
BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
part-I for passing incoming and outgoing cable from ground through it size 100 mm dia. Pipe should be of reputed make and as per tech. spec.
Description:- Supply of material and wiring of LP/TP/FP/Ex.Fan point with 1.5 sqmm PVC single core
conduit with 1.5sqmm PVC wire insulated copper for earth wire 1-way/2-way switch 5/6A as required and good quality ceiling rose including connection (with modular switch, celling rose, PVC conduit & chase work) as per spec.
with modular board and wiring with 2.5sqmm PVC CU cable as per spec.
with modular board and wiring with 4.0 sqmm PVC CU cable as per spec.
with sheet metal box of good quality concealed fixing of MS/PVC as per site spec
with sheet metal box of good quality concealed fixing of MS /PVC as per site spec
with sheet metal box of good quality concealed fixing of MS /PVC as per site spec
with sheet metal box of good quality concealed fixing of MS /PVC as per site spec
wire in PVC conduit concealed and 2.5sqmm PVC insulated, single core, multi-stranded copper wire for earth wire as per spec.This item includes PVC conduit (25 MM) and chase as per requirement.
wire in PVC conduit concealed and 4.0sqmm PVC insulated, single core, multi-stranded copper wire for earth wire as per spec. This item includes PVC conduit (25 MM) and chase as per requirement.
wire in PVC conduit concealed and 6.0sqmm PVC insulated, single core, multi-stranded copper wire for earth wire as per spec.This item includes PVC conduit (25 MM) and chase as per requirement.
Description:- Supply, installation, testing and commissioning of SPN DB 12 Way with suitable IP
10-32 Amp. SP MCB, 10 kA, 'C' curve, 10KA as required with bus bar, neutral bar and necessary wire sets as per specification.
PVC insulated, single core wire in PVC 19/20 mm ISI PVC conduit pipe mounted on structure/ shed with ceiling rose 5 Amp. mounted on wooden block/PVC junction box as per specification.
Description:- Supplying and drawing 6.0 sq. mm PVC insulated multistrand copper conductor cable
earthing wire conforming to IS: 694-1990 in existing conduit/casing capping. Wire should be of reputed make.
and its accessories, size 25 mm, thickness 1.6 mm as per IS:9537 Pt-III.
accessories, as per IS:9537 High mechanical stress (HMS) type including fixing accessories. Anchor or similar of reputed make.
61 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY 61 Description:- Making and filling of chase for 25 mm dia PVC/MS conduit. Surface of chase shall be made good in all respect and satisfaction of engineer incharge.
Description:- Supplying and drawing 4.0 sq. mm PVC insulated multistrand copper conductor cable
earthing wire conforming to IS: 694-1990 in existing conduit/casing capping. Wire should be of reputed make.
Description:- Supply and fixing of HOT DIP GALVANISED RIGID STEEL CONDUIT PIPES (HIGH
and with galvanized clamps & GI junction boxes as per requirement. The box should have IP-67 protection.(Inspection Clause : By Railway Representative at factory Premises)
64 Description:- Fixing of LED four feet fitting complete with tube.
IP 54 protection to avoid ingress of dust and insects. LED panel light shall be of reputed make.
module) used for concealed modular wiring. The regulator is made of high-grade, UV-stabilized polycarbonate material, specifically designed to support all brands BLDC fans.
67 Description:- Supply and fixing of blank plates (1-Module) used in concealed modular wiring.
Installation as per site requirement.
Contractor is responsible for falling of fan within a period of 12 month.
and as per tech. spec.
includes installation of fan along with required accessories as per site requirements.
less than 10 KA. MCB and DB should be as per tech spec. and of same make.
MCCB-1 no., 2P 63A, 100 mA RCCB-3 no. and 2P 25A 'C' series 10 kA MCB-18 nos. MCCB, MCB, RCCB and DB should be as per tech spec. and of same make.
Description:- Supply and fixing of Double Door MCB TPN DB SP (8+12 module), neutral and earth
SP MCB 32/25/16/10/6 amp. 'C' series. Breaking capacity not less than 10 kA. MCB, RCCB and DB should be as per tech spec. and of same make.
Description:- Supply and fixing of junction box size 390x305x170mm comprising of SMP/FRP
model no. GSJB 3525 or similar with 4 no. aluminum busbar cap 200 Amp. Suitable for 415 volt supply requirement. The box shall be fixed robustly with clamps at pole / wall as per requirement. All the material should be of good quality and as per tech. spec.
Description:- Supply and fixing of junction box size 500x450x100mm comprising of sheet steel
shade, gland plates, neoprene EDPM/rubber gasket, locking arrangement, zinc passivated earth bolt, canopy etc. 4 no. aluminum busbar cap 200 Amp., suitable for 415 volt supply requirement. The box shall be robust clamps at pole / wall as per requirement.
77 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY 77 Description:- Supply, fixing, testing and commissioning of fabricated feeder pillar distribution box made of MS sheet 1.6 mm thick size 600mmX300mmX600mm with suitable MS stand copper bus bar of 200 Amp. Capacity and 2X63 Amp MCB four pole as per technical specification.
box two ways outdoor type as per RDSO Drg. No. SKE-3929 as per specifications.
Description:- Design, manufacturing, supplying and fixing of three phase 440 V pre-cooling points
specification and drawing. MCCB and coupler should be of reputed make and as per tech. spec. This item shall be approved by Railway before installation (Inspection Clause : By RITES at factory Premises )
input of 415 V 3 Phase, 50 Hz, AC and output of 110V-150V DC at 200 Amps. As per RDSOs latest specifications. (Inspection Clause : By RITES at factory Premises )
+ N + E) with 63A MCB for ON/OFF for welding with enclosure as per site requirements and specification. This item shall be approved by Railway before installation.
Description:- Design, manufacturing, supply, testing, erection and commissioning of 6 way MCCB incomer & MCCB outgoing DB panel , fabricated from 1.6mm thick CRCA sheet, powder coated with
similar), having provision for incomer 160 Amp, 4 pole 36kA MCCB - 1 no. and Outgoing - 63 amp 4 pole 16kA MCCB - 4 nos. Panel shall be manufactured from CPRI tested firm or should be of reputed switchgear manufacturer's make with foundation work and as per tech. spec.
& fix magnetic trip unit, breaking cap 36 kA (min.) as incoming for DB above.
magnetic trip unit, breaking cap. 16 kA (min.) (Legrand cat. no. 625327 or similar of reputed make) as outgoing for DB. MCCB should be of reputed make and as per tech. spec.
magnetic trip unit, breaking cap. 16 kA (min.) (Legrand cat. no. 625327 or similar of reputed make) as outgoing for DB. MCCB should be of reputed make and as per tech. spec.
Description:- Supply, erection, testing and commissioning of 16 Mtrs high mast shaft totally hot dip galvanized and suitable for wind velocity as per IS 875 part-3, design and casting of suitable
as 10T/sqmtr. at 2 meter depth including supply of foundation bolts manufactured from special steel along with nuts, washers and anchor plates and templates. Are required make: Bajaj/Philips or similar. The mast shall have one longitudinal weld and single dipping (hot dip galvanized) per section (as per specification attached). (Inspection Clause : By RITES at factory Premises )
Description:- Supply, fixing and commissioning of Switching Panel with electromechanical time switch with two daily dial / electronic time switch & two suitably rated contactors for operating 6 / 8 X 150 / 250 / 400 W LED flood lamps, suitable control gear for operation of lowering and lifting
should be of reputed make and the switch also incorporates electronic over current trip and latch mechanism. The panel shall be of appropriate size with sufficient clearance for working during maintenance and it should be properly installed near high mast with proper foundation. Height of panel shall be kept minimum 500mm above the ground.
Description:- Supply and fixing of 400W Flood light for high mast Input operating Voltage range
Working life for LED (Minimum 50,000 burning hours, Colour temperature=6000K(+/-500K). make PHILIPS / EDISON / OREVA / PYROTECH / SURYA /CG / OSRAM / BAJAJ / HAVELLS / HALONIX or similar same as per tech spec. (Inspection Clause : By Railway Representative at factory Premises)
comprising of aluminum housing with polycarbonate enclosure, (1 fitting per mast is necessary). BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
Description:- Dismantling, relocating, re-fixing, erection, testing & commissioning of 12.5/16 meter
representative. It includes design / casting of shallow foundation for high mast with M-20 concrete considering safe soil bearing capacity at site as 10T/sq.mtrs. at 2 mtrs. depth including supply of foundation bolts manufactured from spl. steel along with nuts, washers, anchor plates, templates.
Description:- Supply and fixing or replacement of the hot dip galvanized head frame as capping
docking the luminaries carriage, cast aluminum pulley with stainless steel axle large enough to accommodate the stainless steel wire ropes and electric cable, canopy to cover the pulley's and with a provision to mount lighting finial.
with operating mechanism, to be mounted in the base compartment of the high mast, coupled to the winch shall be supplied for raising and lowering of the luminaries carriage as optional item.
Description:- Supply and fixing/replacement of double drum winch, suitable to operate by motor or
end termination shall be completely self-sustaining type, without the need for brake shoe, springs or clutches and shall have a ratio of 53:1 / 50:1 and minimum safe working load shall be not less than
Description:- Supply and fixing/replacement of stainless-steel wire ropes with 316/304 grade or
winch drum shall be fitted with talurit end thimbles shall be secured on ropes by compression splices and bulldog grips as required.
should be same as exiting junction box.
97 Description:- Repairing of lowring and lifting mechanism of high mast.
Description:- Supply, fixing and commissioning of Switching Panel with electromechanical time switch with two daily dial & two suitably rated contactors for operating 6/8/12 X400 W LED flood
necessary cable etc. for commissioning of the Mast as per detailed specification and panal should be commission on proper foundation. All the accessories should be of reputed make and as per technical specification.
Description:- Providing SH rail post 1.5 / 2.5 mtrs. Long for safety of highmast. Work includes cutting of 50@47<47K47@90 lbs capacity rails in pieces of desired length (1.5/2.5 mtrs.), digging of
from concerned SSE). The rail pole shall be erected over a cement concrete bed (1:3:6) of 15 cm thickness and back filling of pit with excavated earth soil. The depth of the pit shall be 0.5 mtrs. or as directed by Site Engineer. These rail poles should be grouted properly
Description:- Supply, installing, testing and commissioning earth electrode complete in all respect with perforated GI pipe medium "B" class (Blue) confirming to IS 1239 part-I length of 4 mtr., bore
chamber covered by CI/RCC frame etc. Digging pit and refilling it with charcoal and salt in successive layers and connection with 25x3 mm GI strip as per IS:3043 and drawing and testing of earth resistance as reqd
Description:- Supply, laying and fixing of 25 x 5 mm GI earth strip at 0.5 meter below ground level
as required (jointing shall be done by overlapping and with 2 sets of GI nut bolt & spring washer spaced at 50 mm). Note:- Suitable GI saddles with screws shall be provided to secure earth strips run on walls /floors etc.
102 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY Description:- Supply of unit maintenance free earth material as per RDSO Specs. No RDSO/PE/SPEC/PS/0/0109 (REV.0) 2008 or Latest
RDSO/PE/SPEC/PS/0/0109 (REV.0) 2008 or Latest.
30mA with Earth leakage, overload and short circuit protection as per relevant IS or IEC 61009 as per specification.
accommodate DP/TP "C" series, MCBs of reputed make.
water connection angle valve as per spec.
Description:- Supply fabrication and fixing of MS cage made of suitable size1" 1 MS angle and MS
hinges including one coat of red oxide and two coats of enamel paint along with fixing arrangement on existing wall/rail /pipe/foundation by nutbolt /clamp /washer etc. as specification
1M x 1M) for water cooler as per site requirement and instructions of railway site supervisor.
Description:- Supply of material, fabrication, installation and commissioning of Rolling in
powder coating - grey shade, gland plates, neoprene EDPM/rubber gasket, padlock arrangement, zinc passivated earth bolt, canopy etc. All material of should be of good quality.
Description:- Supply and Fixing LED flood lights 30 W, outdoor type, Aluminum die cast housing,
PF more than .95 , life of complete fixture has to be minimum 50,000 burning hours at L70 lumen maintenance. THD should be less than 20 as per make Oreva, Pyrotech, Philips, Surya, CG, Osram, Gear, Bajaj and Havells or similar.
site requirement and instructions of railway representative.
Description:- Supply and fixing of 20A SP C Type Mini Modular MCB 'C' series 3kA or more product
graphite/brass contacts, FR Grade nylon glass filled housing, Tripping characteristic C Curve, Voltage
Description:- Supply and fixing CPVC Pipe SDR 11 Class1 20 mm size having thermal stability for hot and cold water supply, including all CPVC plain & brass threaded fittings, including fixing the
solvent cement and testing of joints complete as per direction of Rly supervisor with all accessories required for ac water drainage. Concealed work, including cutting chases and making good the walls etc.
steel tubes 50mm to 70mm Category of steel tubes is Medium Hot dip Galvanized zinc coating on the tubes in accordance with IS4736 latest" with all its accessories.
117 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY 117 Description:- Supplying, fixing ,testing & commissioning Automatic operation street light timing switch box having lighting control (on-off) through astronomical calculation and pre-wired with suitable size of contactors, copper conductor etc. at specified locations as per specification attached and similar to model no 04764 of LEGRAND make or Siemens / ABB with suitable enclosure
adjustable magnetic trip unit as per specification.
119 Description:- Supply and fixing of Metal enclosure for MCCBs of reputed make
30mA with Earth leakage, overload and short circuit protection as per relevant IS or IEC 61009 as per spec
61439-3, Suitable for flush mounting and surface mounting with door for IP 54, similar to Legrand or any reputed make.
Description:- Removal of existing Rail/Swage poles with overhead wire and all accessories from
suitable cement concrete and transportation of rail pole and all accessories with fitting etc. complete from site to place located at that station by concern SSE/Elect.
cement concrete and transportation of rail/swage/octagonal pole and all accessories with fitting etc. complete from the site to place located at the station by concern SSE/Elect. 1039191.0
Thyristor Switched Power Factor Correction System with7 % Harmonic Block Reactor as per specification. (Inspection Clause : By RITES at factory Premises ) 7150900.0
0 Description:- Design, fabrication, Supply, installation, testing and commissioning of outdoor type package substation(Compact Substation) with HT 11KV RMU comprising of 2 Nos of LBS of rating
outgoing 1 No of 1000 A ACB (operating voltage750 V) Motorized, 50 KA, EDO type Microprocessor release, Shunt release, Under voltage release and E/F relay complete, with LT side SCADA compatibility and subject to approval from competent authority and as per detailed technical specifications of tender documents. The final commissioning of substation includes submission of all technical documents, literature, test certificates etc., as required including necessary arrangements for EIG inspection all as specified and directed. (Inspection Clause : By RITES at factory Premises )
Description:- Material and labour for Construction of concrete masonry plinth below ground level with M10 concrete for compact substation with provision for HT and LT cable incoming/outgoing
and got approved from Railways prior to commencement of work at site. (ii) Necessary form work, shuttering and finishing of surfaces are included in the scope of work and the quoted rates are deemed to be inclusive of this provision.
Description:- Material and labour for Construction of concrete M20 masonry plinth above ground level with plastering for compact substation with provision for HT and LT cable incoming / outgoing
Railways prior to commencement of work at site. (ii) Necessary form work, shuttering and finishing of surfaces are included in the scope of work and the quoted rates are deemed to be inclusive of this provision.
Description:- Fabrication, supply, fixing, testing and commissioning of HT Metering Panel 3 CT & 3 PT, for 3 phase 4wire metering with transparent cover TTB with 30 x 8 mm Copper Bus bars (HT
phase 4 wire DLMS compatible) CT 11 KV, ratio10/1 A (or as directed), 0.2 s class accuracy, 2.5 VA burden including necessary foundation all as specified and as per DISCOM approved specifications and drawings.
129 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
output as per RDSO specification. (Inspection Clause : By RITES at factory Premises )
Description:- Supply, fixing, testing and commissioning of LHB type socket assembly 500 amps,
ON & OFF push buttons, ON & OFF indicators supported with appropriate DMC/SMC barriers to be fixed in cement concrete foundation. of material & excavation of the cable trench as per standard specification.conf. to RDSO spec no.RDSO/PE/Spec/AC/0177 (rev-(0)2013- or latest
with copper conductor working voltage above 750 V & up to 1.8kV/3.0 kV grade. As per RDSO spec ELRS/SPEC/ELC/0019 REV 3 of Feb. 2017 or latest, Make - RDSO approved only.
equivalent of M/S Harting suitable for HOG LHB power car as per RDSO/PE/MS/AC0051-2011 Rev-2 or latest accepted make - CHALTBAU or similar.
Output Voltage: 110V DC, 5A Output voltage: Adjustment Range: ±20%, Protections: Overload / Over Voltage / Short Circuit, Auto-Recovery After Protection
Description:- Supply of 16 core X 1 Sqmm Teflon insulated copper cable (PTFE) with PVC sheathed
per RDSO/PE/MS/AC/0051-2011 rev. 2 or latest Make - Geecore par no. HOR002422 JSSS1034 (PTFE/SCR/FRLS) or equivalent.
carrying coupler etc.
Description:- Supply, installing, testing and commissioning of copper plate earthing with
refilling it with charcoal and salt and connection by copper flat. Masonry enclosure of 40 x 40 x 30 cm.(inner), 12.5 cm. should be provided at the top of the pit as per drawing attached at annexure-IV and IS:3043.
connecting earth with equipment.
for 3 core 11kV XLPE cable size of 120 to 185 mm sq. - indoor type. Item should be of reputed make and as per tech. spec.
for 3 core 11kV XLPE cable size of 120 to 185 mm sq. - outdoor type. Item should be of reputed make and as per tech. spec.
140 Description:- Supply & fixing of straight joint of LT cable size 6-16 sqmm of reputed make.
141 Description:- Supply & fixing of straight joint of LT cable size 25-50 sqmm of reputed make.
142 Description:- Supply & fixing of straight joint of LT cable size 70-150 sqmm of reputed make.
G.I. tube, having single prong at top, with 85 mm dia6 mm thick G.I. base plate including holes etc. complete as required.
other metallic object) by riveting / nut bolting/sweating and soldering etc as required.
lightning conductor complete as required.(For horizontal run) BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
lightning conductor complete as required.(For vertical run)
in black/red chequared pattern.
per site requirement and site engineer instructions
pole with cement concrete ratio 1:2:4 M-15 as per technical specification and satisfaction to site engineer. (Supply of Octagonal Poles are not included in this NS)
labour charges and other expenditure as instructed by site engineer. 2140832.0
0 Description:- Design, supply, fixing, installation and commissioning of 25kW alternator testing bed
alternators, including design supply and installation and commissioning of plumber block, pulley and shaft arrangement. (One set contains two nos. of arrangement i.e. one each, under one alternator of a AC coach) as per RDSO latest specification and complete in all respect . S.No. Item Item Qty Qty Unit Unit Rate Basic Value Escl.(%) Amount Bidding Code Unit Schedule () B-Electrical work in c/w Work for shifting ARF at other location in SOG yard to facilitate coaching terminal at Suratgarh Junction and Upgradation/ 8843336.00 Augmentation/creation of Disaster management Rolling Stock maintenance facility at SOG over BKN Div.
Description:- Supply of material and wiring of LP/TP/FP/Ex.Fan point with 1.5sqmm PVC single core
conduit with 1.5sqmm PVC wire insulated copper for earth wire 1-way / 2-way switch 5/6A as required and good quality ceiling rose including connection. This item includes modular switch, celling rose, PVC conduit and required chase as per site requirement.
existing modular board and connection as per site requirement
existing modular board and connection as per site requirement.
with sheet metal box of good quality concealed fixing of MS/PVC as per site requirement.
with sheet metal box of good quality concealed fixing of MS /PVC as per site requirement.
with sheet metal box of good quality concealed fixing of MS/PVC as per site requirement.
with sheet metal box of good quality concealed fixing of MS /PVC as per site requirement.
Socket with sheet metal box of good quality concealed fixing of MS /PVC as per site requirement.
Description:- Wiring of sub-main with 2x2.5 sqmm PVC insulated, single core,multi-stranded
copper wire for earth wire as per spec.This item includes PVC conduit (25 mm) and chase as per requirement. BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
wire in PVC conduit concealed and 4.0 sqmm PVC insulated, single core, multi-stranded copper wire for earth wire as per spec. This item includes PVC conduit (25 MM) and chase as per requirement.
wire in PVC conduit concealed and 6.0 sqmm PVC insulated, single core, multi-stranded copper wire for earth wire as per spec.This item includes PVC conduit (25 MM) and chase as per requirement.
Description:- Supply, laying, connection and commission of sub-main 2x10 Sqmm with PVC
earthing wire in 19/20 mm ISI PVC conduit in recessed/ on surface as per site requirement etc. of various size cable as below. As per specification.
PVC insulated, single core wire in PVC 19/20 mm ISI PVC conduit pipe mounted on structure/ shed with ceiling rose 5 Amp. Mounted on wooden block/PVC junction box.(As per specification)
Description:- Supplying and drawing 6.0 sq. mm PVC insulated multistrand copper conductor cable
earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make and as per tech. spec
Description:- Supplying and drawing 4.0 sq. mm PVC insulated multistrand copper conductor cable
earthing wire conforming to IS: 694-1990 in existing conduit/casing caping. Wire should be of reputed make and as per tech. spec.
16 Description:- Fixing of T-5/ LED Tubular Lamp four feet complete with all accessories.
Contractor is responsible for falling of fan within a period of 12 month.
module) used for concealed modular wiring. The regulator is made of high-grade, UV-stabilized polycarbonate material, specifically designed to support all brands BLDC fans.
ventilation fan of 300 mm. sweep with louver shutters. Fan should be of reputed make and as per tech. spec.
refilling with charcoal & salt. (As per specification)
mm thick with CI/RCC earth pit cover 300 x 300 x 25 mm with lifting hooked in center.
Description:- Supply, laying and fixing of 25 x 5 mm GI earth strip at 0.5 meter below ground level
as required (jointing shall be done by overlapping and with 2 sets of GI nut bolt & spring washer spaced at50 mm). Note:- Suitable GI saddles with screws shall be provided to secure earth strips run on walls /floors etc.
with cover and all fixing arrangements as per specification and as per site requirement
GI perforated cable tray with cover and all required mounting accessories as per technical specification.(Inspection Clause : By Railway Representative at factory Premises)
25 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY Description:- Supply of material and laying of perforated GI cable tray of size 300mm X 50 mm with cover and all fixing arrangements as per specification and as per site requirement. (Inspection Clause : By Railway Representative at factory Premises)
Description:- Supply and fixing of junction box size 390x305x170mm comprising of SMP/FRP
model no. GSJB 3525 or similar with 4 no. aluminium busbar cap 200 Amp., suitable for 415 volt supply requirement. The box shall be fixed robustly with clamps at pole/ wall as per requirement. All the material should be of good quality and as per tech. spec
Description:- Supply and fixing of junction box size 500x450x100mm comprising of sheet steel
shade, gland plates, neoprene EDPM/rubber gasket, padlock arrangement, zinc passivated earth bolt, canopy etc. 4 no. aluminium busbar cap 200 Amp., suitable for 415 volt supply requirement. The box shall be robust clamps at pole/ wall as per requirement.
D e s c r i p t i o n : - Laying, testing, commissioning & transportation of LT cable in Air/Pole/Pipe/Trench/wall/cable tray etc. with complete lugs/glands and transportation of cable etc. Laying cable in air with fixture (02 nos. per mtrs).Cables shall not be bent sharp to a small radius
shall be 12 times the overall diameter of the cable. Cable should be properly terminated with standard size of lug. The cable along the wall should be provided with suitable size of M.S. clamps, Reg Bolts / J bolts shall be provided to supporting the cable. The distance between two supports not more than 0.50 meters. Breaking of wall to make holes for the contractor shall do cable entry in the building shall be restored to original levels to the satisfactions of the railway.
PN 6, PE 80 as per requirement. (Inspection Clause : By Railway Representative at factory Premises)
under the road. The work involves laying of HDPE pipe along with transportation
requirement. (Inspection Clause : By Railway Representative at factory Premises)
work involves laying of HDPE pipe with transportation.
requirement. (Inspection Clause : By Railway Representative at factory Premises)
work involves laying of HDPE pipe with transportation
kachha/pakka land and all type of soil as per site requirement and without protective layer of brick) Surface of trench shall be made good in all respect and satisfaction of site engineer.
Description:- Cutting of cement concrete floors(PCC / RCC), any type / depth as required for laying of UG cables in trenches and disposing off the excavated material as directed including refilling the
barricading and danger lighting around the excavated area as safety precaution is a mandatory requirement and cost of this provision, wherever required, is deemed to be included in the quoted rate of this item.
part-I for passing incoming and outgoing cable from ground through it size 50 mm dia. Pipe should be of reputed make and as per tech. spec.
1.5mm thick size 150X100mm welded with 12mm dia MS rod 85 cm long. The lower end of rod should be turned in hooks shape and attached with the cable at the time of laying.
BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY Description:- Drilling of horizontal bore below Track/Road by pushing method (trenchless
Railway representative taking all necessary safety precautions related track and movement of trains. Horizontal boring will be done at minimum 1.5 Mtr. Below from ground level at railway track portion.
Description:- Supply & erection of 5 m high with double arm model no. BOP-5030 of Bajaj or similar, hot dip galvanized steel octagonal pole with galvanized base plate of 200x200x12 mm,
pole), foundation bolt size 4x16mm dia. 600 mm in length including excavation and making foundation as per spec. and drawing. It shall be galvanized internally and externally by single dipping methods. The pole and foundation shall be made as per specification and drawing attached.
suitable bore as per fitting, clamps, nuts, bolts, cable etc. as per instruction of site engineer
site requirement and Engineer in charge of railway.
PVC Unarmoured copper cable ISI marked (IS:694) of 1.1 kV grade and approved make in existing surface or recessed conduit/casing capping including making connections etc. as required.
Description:- Removal of existing Rail/Swage poles with overhead wire and all accessories from
suitable cement concrete and transportation of rail pole and all accessories with fitting etc. complete from site to place located at that station by concern SSE/Elect.
cement concrete and transportation of rail/swage/octagonal pole and all accessories with fitting etc. complete from the site to place located at the station by concern SSE/Elect.
pole with cement concrete ratio 1:2:4 as per technical specification and satisfaction to site engineer. (Supply of Octagonal Poles are not included in this NS)
labour charges and other expenditure as instructed by site engineer.
MS flat 35x5 mm. The cable tray shall be 260mm wide as per technical specification
Description:- Design, supply, fixing & commissioning of LT panel made by 2 mm CRCA sheet with 1
63A,16kA and 2 nos. 4 pole MCCB 40A,16kA All MCCB should be adjustable over load 80% to 100% & Adjustable short circuit, Ics = 100% Ics with meter & indication LED, copper bus bar etc. with foundation as per spec.
Description:- Supply and fixing of Double Door MCB TPN DB SP (8+12 module), neutral and earth
SP MCB 32/25/16/10/6 amp. 'C' series. Breaking capacity not less than 10 kA. MCB, RCCB and DB should be as per tech spec. and of same make.
Description:- Supply and fixing of Double Door MCB DB SP 12 way (10+2 module), neutral and
32/25/16/10/6 amp. 'C' series. Breaking capacity not less than 10 kA. MCB, RCCB and DB should be as per tech spec. and of same make.
53 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY 53 Description:- Supply, installation, testing and commissioning of SPN DB 12 Way with suitable IP protection having 1 No. RCBO 40 Amp Cap., sensitivity 30 mA in the incoming and in outgoing 06 Nos. 10-32 Amp. SP MCB, 10 kA, 'C' curve, 10KA as required with bus bar, neutral bar and necessary wire sets. As per specification. MCB, RCBO and DB should be as per tech spec. and of same make.
54 Description:- Supply and fixing of MCB DP 32 amp with box. Breaking capacity not less than 10 KA.
55 Description:- SITC of MCCB 4P, 100A, 16kA adjustable thermal adjustable magnetic trip unit.
56 Description:- SITC of MCCB 4P, 63A, 16kA adjustable thermal adjustable magnetic trip unit.
57 Description:- Supply and fixing of Metal enclosure of reputed make for above MCCB.
box two ways outdoor type as per RDSO Drg. No. SKE-3929 as per specifications.
complete with 3P 80A MCCB, 63 A 5 pin coupler (male + female) and accessories as per specification and drawing. MCCB and coupler should be of reputed make and as per tech. spec.
N + E) with 63A MCB for ON/OFF for welding with enclosure as per site requirements and specification.
input of 415 V 3 Phase, 50 Hz, AC and output of 110V-150V DC at 200 Amps. As per RDSOs latest specifications. (Inspection Clause : By RITES at factory Premises )
Description:- Supply, erection, testing and commissioning of 16 Mtrs high mast shaft totally hot dip galvanized and suitable for wind velocity as per IS 875 part-3, design and casting of suitable
as 10T/sqmtr at 2 meter depth including supply of foundation bolts manufactured from special steel along with nuts, washers and anchor plates and templates. Are required make: Bajaj/Philips or similar. The mast shall have one longitudinal weld and single dipping (hot dip galvanized) per section (as per specification attached). (Inspection Clause : By RITES at factory Premises )
Description:- Supply, fixing and commissioning of Switching Panel with electromechanical time switch with two daily dial & two suitably rated contactors for operating 6/8/12 X400 W LED flood
necessary cable etc. for commissioning of the Mast as per detailed specification and panel should be commission on proper foundation. All the accessories should be of reputed make and as per technical specification.
comprising of aluminum housing with polycarbonate enclosure.
Description:- Dismantling, relocating, re-fixing, Erection, testing & commissioning of 12.5/16 meter high mast system as per site requirement to the satisfaction of rly. Representative. Design / casting
capacity at site as 10 T/sq mtrs at 2 mtrs depths. Foundation both, nuts, washers, anchor plates, templates should be made of spl. Steel. Any alteration/modification shall be done as per site/tech spec. requirement to the satisfaction of rly.
Description:- Supply and fixing or replacement of the hot dip galvanized head frame as capping
docking the luminaries carriage, cast aluminum pulley with stainless steel axle large enough to accommodate the stainless steel wire ropes and electric cable, canopy to cover the pulley's and with a provision to mount lighting finial.
with operating mechanism, to be mounted in the base compartment of the high mast, coupled to the winch shall be supplied for raising and lowering of the luminaries carriage as optional item.
BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY Description:- Supply and fixing/replacement of double drum winch, suitable to operate by motor or
end termination shall be completely self-sustaining type, without the need for brake shoe, springs or clutches and shall have a ratio of 53:1 / 50:1 and minimum safe working load shall be not less than
Description:- Supply and fixing/replacement of stainless-steel wire ropes with 316/304 grade or
winch drum shall be fitted with talurit end thimbles shall be secured on ropes by compression splices and bulldog grips as required.
71 Description:- Repairing of lowering and lifting mechanism of high mast.
for 10 kVA AT for color light signaling supply in 25 kV AC traction system as per RSDO specification no. TL/SPC/PSI/CLS/0020(2012/20) with A&C Slip no. 1 to 4 or latest & connection as per requirement
Description:- Providing SH rail post 1.5 / 2.5 mtrs. Long for safety of high mast. Work includes cutting of 50@47<47K47@90 lbs. capacity rails in pieces of desired length (1.5/2.5 mtrs.), digging of
from concerned SSE). The rail pole shall be erected over a cement concrete bed (1:3:6) of 15 cm thickness and back filling of pit with excavated earth soil. The depth of the pit shall be 0.5 mtrs. Or as directed by Site Engineer. These rail poles should be grouted properly.
water connection angle valve as per spec.
Description:- Supply & fixing of M.S.Jali I" x I" welded on MS angle frame 30 x30 x 3 mm which is
whole structure including the framed jali painted with one coat of red oxide and two coats of enamel paint. Providing roofing on rail/iron structure by MS/GI sheets with support of 50 x 50 x 6 mm angle, nut-bolt and washer as per specification
cooler as per site requirement and site supervisor of railway
leakage, overload and short circuit protection compliance to standard IEC/EN 61009 as per spec.
accommodate DP/TP "C" series, MCBs of reputed make.
charging points and all accessories as per site requirements and site engineer instructions. Square
sign / direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than 160 deg. Square
direction boards in half elliptical shape. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2 mm thickness. The text / graphics matter visibility shall not be less than
82 BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY Description:- Supply of material, fabrication, installation and commissioning of Rolling in Examination lighting MS box of suitable dimension comprising of sheet steel 1.6mm thick, 60 micron powder coating - grey shade, gland plates, neoprene EDPM/rubber gasket, padlock arrangement, zinc passivated earth bolt, canopy etc. All the material should be of good quality.
Description:- Supply and Fixing LED flood lights 30 W, outdoor type, Aluminum die cast housing,
PF more than .95 , life of complete fixture has to be minimum 50,000 burning hours at L70 lumen maintenance. THD should be less than 20 as per make Oreva, Pyrotech, Philips, Surya, CG, Osram, Gear, Bajaj and Havels or similar.
for bore 150mm, discharge140 to 160 LPM, Head 160 to 180 Mtr, BEE approved. Make: KSB/Duke/CRI/Sabar/CG/Kirloskar.
Description:- Supplying, fixing, testing & commissioning of digital soft starters model no.CSXi of
1.6mm thick sheet, neoprene EDPM/ Rubber gasket, with start stop push button, 4no. Aluminum bus- bar, ammeter & 4 pole MCCB 50 A with adjustable thermal setting and min.25 kA breaking capacity. Starter and MCCB should be of reputed make and as per tech. spec
made of MS sheet 1.6 mm thick size 600mmX300mmX600mm with suitable MS stand copper bus bar of 200 Amp. Capacity and 2X63 Amp MCB four poles as per technical specification.
85/90 GSM showing over all electrical installation of Railway station As per specification.
VPI dry type transformer as per specification
Description:- Supply, installation, testing and commissioning (with foundation/supporting
type [IP-66] with additional safety chain, luminaries has efficacy upto 130 lm/W with10kV SPD of Crompton or equivalent with suitable junction box for main supply in each low & looping complete in all respect as per site requirements
Description:- PIT LIGHTING: Design, fabrication, supply, erection, testing & commissioning of LED based luminary having input voltage 40V-72V AC, frequency 50/60 Hz, Input Power 16 watt with IP- 67enclosure & Impact protection IK-10 with High brightness, high intensity with an efficiency of 130
a way to illuminate the under frame of the coach and path lighting of pit line. The cubicle shall be fabricated with MS sheet/ Poly carbonate body with high built of epoxy coating, heat resistive up to
Description:- Cat walk lights: Design, fabrication, supply, erection, testing &commissioning of LED based Cat walk lighting luminaries complete, with input wattage of 22W suitable to work on 40V-72V
should be Ingress protection IP- 67 &Impact protection IK10. The cubicle shall be fabricated with MS sheet/Poly carbonate body with high built of epoxy coating, heat resistive up to 70 degree centigrade complete with weather proof and rust proof. Fixture shall be IRGOLD-B1 of M/s Goldwyn Limited or equivalent. Make shall be as per T.S.
PROTECTION) GI with junction box and its complete accessories, size 25 mm dia, thickness 1.6 mm as per IS 9537 part II. The box should have IP-67 protection.
Description:- SITC of outdoor type IP-67, 4 way terminal junction box hinged type, ABS materials, highly weather able and extremely durable and provided with 4 nos of terminals mounted on SMS/Hylam sheet including provision of locking arrangements knockout cable entries etc. with all
BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
similar to orpat,bajaj,crompton,philips or similar of reputed make.
197/2008 or latest as per technical spec.
98 Description:- Installation of unit maintenance free earth as per technical spec.
100 Description:- Supply, erection, testing & commissioning of firefighting equipment as per spec.
Description:- Supply & Fixing ISI marked (IS:15683) Portable Fire Extinguisher, CO2 type flat base
respects including initial fill with CO2 gas confirming to IS:307 of 1966 filled to a filling ratio of not more than 0.667 and wall suspension bracket capacity of 4.5 kg capacity
Description:- Supplying and Fixing of fire bucket stand made out of MS angle with one coat of primer and two coat of enamel paint of approved shade including platform and associated civil
liter capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters "Fire" in black and gold at approved location as per direction of Engineer in charge.
and railway representative.
Description:- Supply and fixing of 20A SP C Type Mini Modular MCB 'C' series 3kA or more product
graphite/brass contacts, FR Grade nylon glass filled housing, Tripping characteristic C Curve, Voltage
Description:- Supply and fixing CPVC Pipe SDR 11 Class1 20 mm size having thermal stability for hot and cold water supply, including all CPVC plain & brass threaded fittings, including fixing the
solvent cement and testing of joints complete as per direction of engineer in charge of railway with all accessories required for ac water drainage. Concealed work, including cutting chases and making good the walls etc.
Description:- Supplying, fixing ,testing & commissioning Automatic operation street light timing
suitable size of contactors, copper conductor etc. at specified locations as per specification attached and Similar to model no 04764 of LEGRAND make or similar of Siemens/ABB.
Description:- Design, manufacturing, supply, testing, erection and commissioning of 4 way MCCB incomer & MCCB outgoing DB panel , fabricated from 1.6mm thick CRCA sheet, powder coated with
similar), having provision for incomer 250 Amp, 4 pole 36kA MCCB - 1 no. and Outgoing - 125 amp 4 pole 16kA MCCB - 2 nos., 63 amp 4 pole 16kA MCCB - 2 nos Panel shall be manufactured from CPRI tested firm or should be of reputed switchgear manufacturer's make and as per tech. spec.
Description:- Supply, fixing and commissioning of 250 amps. 4 pole MCCB with adjustable thermal
should be of reputed make and as per tech. spec. BIKANER DIVISION-ELECTRICAL/NORTH WESTERN RLY
& fix magnetic trip unit, breaking cap 16 kA (min.) as incoming for DB at item above. MCCB should be of reputed make and as per tech. spec.
fix magnetic trip unit, breaking cap 16 kA (min.) as incoming for DB at item above. MCCB should be of reputed make and as per tech. spec.
Description:- Supply, fixing, testing and commissioning of single stage Mono-block open well
size (MM) suction X delivery 50X40, Discharge (LPM):180 or above at 26 meter head suitable for single phase 50Hz AC supply of reputed make.
submersible pump 230 volt. Starter should be of reputed make.
Texmo/Duke/sabar.
three-phase pump (Monopole/Submersible) including connections and providing cable from main board to control panel and connection for WLG in open bore well as per detailed specifications
valve and supporting clamps (2 set) As per specification.
Description:- Supplying, connecting, fixing and lowering of GI pipe 2" Dia medium "B" class (Blue)
fixing of suitable size accessories like flange , safety clamp , cable clamp etc. and excluding flat copper cable. Pipe should be of reputed make and as per tech. spec.
grade conf. to IS: 694/1990 with latest amendments, size 6 sqmm. Cable should be of reputed make and as per tech. spec.
Description:- Supply of 10/12W Emergency Lights For emergency light failure Super Bright White LED with Microcontroller based Intelligent Battery Charging/Discharging mechanism for optimum life
output for an initial period of 2 hours and with reduced power for the subsequent 10 hours. It has sufficient battery capacity to ensure working emergency light continuously for 12 hours in order to provide the required illumination, when the normal supply fails.
requirement and site engineer instructions
120 Description:- Supplying & erecting of shock Restoration Chart in glass frame. (As per specification)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
UpdatedGCCACSupto11.pdf
ATTACHMENT
JPOforprotectionofSTCables.pdf JPO for Protection of Cables
ATTACHMENT
RBSIGNAGESPOLICYPART-1.pdf RB Signage Policy Part 1
ATTACHMENT
RBSIGNAGESPOLICYPART-2.pdf RB Signage Policy Part 2
ATTACHMENT
06of2026-27.pdf
ATTACHMENT
JPOforprotectionofSTCables.pdf
ATTACHMENT
RBSIGNAGESPOLICYPART-1.pdf
ATTACHMENT
RBSIGNAGESPOLICYPART-2.pdf
ATTACHMENT
Download all tender documents and submit your bid