| 1 | 1₹66.3 LAccepted-AOC FLAT NO 2450 KRISHNA COLONY JIND 126102 | JIND | HARYANA | 126102 | 1 | Accepted-AOC Due to lower side of rates | |
| 2 | 2₹70.2 L+₹3.9 L (5.90%)Rejected-AOC | 2 | Rejected-AOC Due to higher side of rates |
Tender Value
₹49.7 L
EMD Value
₹99,344
Closing Date
5 Jul 2021, 2:00 pmClosed
EXECUTIVE ENGINEER
EXECUTIVE ENGINEER PUBLIC HEALTH ENGINEERING DIVISION NARWANA
Laying of DI Pipe lines in balance streets providing balance FHTC Const of 2nd BStn and repair of ww structures at village Kuchrana Kalan Under JJM target II
2021_HRY_176205_2
SE no. 3188 dated 08.06.2021
Open Limited
Civil Works
Tender
6 days
NARWANA
Please refer Tender documents.
3 documents required · 3 mandatory
₹2,500
₹99,344
Yes
8 Oct 2022
29 Jun 2021
5 Jul 2021
29 Jun 2021
5 Jul 2021
29 Jun 2021
Amount
Provision for 200 mm i/d floating arms complete with in all respect
Taking out filter media top to bottom layers
Placing of filter media all layers after washed and cleaned qty. After deducting the 10% wastage
Supply & Erection of Horizontal spindle split casing type pumping sets of minimum Four (4) Star rating duties directly coupled to AC squirrel cage induction type motor with 1440 RPM, 3 phase, 50 Hz and accessories as described in Schedule No. II complete in all respect with priming arrangement with complete base frame. A) Raw water pump set 600 Lpm , 12 mtr head 5 BHP
B ) Clear water pump set 600 Lpm , 40 mtr head 10 BHP
C ) Clear water pump set 300 Lpm , 40 mtr head 5 BHP at ww for B/Stn.
C ) Clear water pump set 300 Lpm , 40 mtr head 5 BHP for B/Stn.
Supply and fixing of CI double flanged pipe and specials / bell mouth including cost of jointing material laying jointing refilling including making adequate support of masonary / concrete for delivery and suction pipe from bell mouth in the collecting tank upto the rising main laid by the department as per plan shown from the foundaton wall of pump chamber for all the raw water and clear water pumping sets at water works in position as per specification given in schedule no. II for pumping machinery SI D/F pipes 150 mm i/d
Bell mouth 150 mm i/d
Supply, erection, testing and commissioning of Wall mounted electrical panel board , fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 500 x 1200mm and 400mm deep having following accessories : 1. Incomer switch 200 Amp 2. Aluminium bus bar chamber of 300 Amp. capacity 3. Volt meter , 100 x 100 mm range 0 to 500 V (AE/KAPPA/L&T) 4. Indicating Lamp-One set
Supply, erection, testing and commissioning of Wall mounted electrical panel board , fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200 x 900mm having following items : a) For raw water pump sets for 600 Lpm x 12 M head = 2 No. a) Main switch 63 Amp 2 No. ((L&T, Siemens, ABB) b) Volt meter 100 x 100mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) c) Amp meter 100x100mm range 0 to 100 Amp 2 Nos(AE/KAPPA/L&T) d) CT 100/3 Nos (AE/KAPPA/L&T) e) VSS 1 No & ASS 2 No. each of approved make f) SPP 2 No. of approved make g) Motor starter, star delta, 2 No. for 3000 LPM x 12 M Head Motor (L&T Siemens, AAB) h) Capacitor of suitable capacity = 2 No i) Indicating Lamp-One set j) Change over switch 63 Amp = 1 No
Supply, erection, testing and commissioning of Wall mounted electrical panel board , fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200 x 900mm and having following items : a) For Clear water pump sets for 600 Lpm x 40 M head = 2 No. a) Main switch 63 Amp 2 No. ((L&T, Siemens, ABB) b) Volt meter 100 x 100mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) c) Amp meter 100x100mm range 0 to 100 Amp 2 Nos(AE/KAPPA/L&T) d) CT 100/3 Nos (AE/KAPPA/L&T) e) VSS 1 No & ASS 2 No. each of approved make f) SPP 2 No. of approved make g) Motor starter, star delta, 2 No. for 3000 LPM x40 M Head Motor (L&T Siemens, AAB) h) Capacetor of suitable capacity = 2 No i) Indicating Lamp-One set j) Change over switch 63 Amp = 1 No
Supply, erection, testing and commissioning of Wall mounted electrical panel board , fabricated from 16 SWG CRCA sheet duly stouted with suitable angle iron frame work and completely powder coated of approximate size 1200 x 900mm and having following items : a) For Clear water pump sets for 300 Lpm x 30 & 40 M head = 2 No. ( At w/w for b/Stn & at B/Stn. ) a) Main switch 63 Amp 2 No. ((L&T, Siemens, ABB) b) Volt meter 100 x 100mm range 0 to 500 volt 1 No.(AE/KAPPA/L&T) c) Amp meter 100x100mm range 0 to 100 Amp 2 Nos(AE/KAPPA/L&T) d) CT 100/3 Nos (AE/KAPPA/L&T) e) VSS 1 No & ASS 2 No. each of approved make f) SPP 2 No. of approved make g) Motor starter, star delta, 2 No. for 3000 LPM x40 M Head Motor (L&T Siemens, AAB) h) Capacetor of suitable capacity = 2 No i) Indicating Lamp-One set j) Change over switch 63 Amp = 1 No
Supply erection, testing of ISI marked copper wire for 04 Nos motors with under ground system in PVC and flexible pipes copper wire size 6 sq. Mm complete in all respect with accessories like thimble etc. Complete in respects.
Supply erection, testing of ISI marked copper wire for 03 Nos panel boards from main switch to panel and wiring of panel with size 10 sq. mm (coppeer wire) ISI marked complete in all respect with accessories like thimble etc. complete in all respect.
Supply erection testing of reputed make LED light 100 watt with fitting and accessories complete in all respect
Credit of old bricks
Bidder Name
Amount
M/S AAR PEE CONSTRUCTION COMPANY JIND(GSTN-NA)
ANGREJ SINGH CONTRACTOR(GSTN-NA)
ANGREJ SINGH CONTRACTOR
ANGREJ SINGH CONTRACTOR
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .