Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance H NO 787 22 JHANG COLONY ROHTAK 124001 | ROHTAK | HARYANA | 124001 | Admitted-Finance |
Tender Value
₹28.8 L
EMD Value
₹57,600
Closing Date
29 Nov 2024, 5:30 pmClosed
NAVIN KUMAR
ED - Gurgaon
Extension of electrical substation installed at Haryana State Guest Houst Chanakyapuri New Delhi.
2024_HRY_412046_1
2024DD4CE651 1977 4C43 B0ED 97257327467F664BAR
Open Tender
Electrical Works
Works
90 days
DELHI
2 documents required · 2 mandatory
₹5,000
₹57,600
Yes
9 Jan 2025
20 Nov 2024
2 Dec 2024
20 Nov 2024
29 Nov 2024
20 Nov 2024
20 Nov 2024 - 21 Nov 2024
Amount
MCCB ,DISTRIBUTION BOARDS, MCB's, RCCB's, CHANGE OVER etc. Supply and erection of Modular case circuit breaker single pole/4 pole on existing wall/pedestal/Panel including bounding to earth and making necessary connections required to complete the job in all respect up to the entire satisfaction of the Engineer-in-charge of the work. Triple pole MCCB 125 to 160 Amp, 25 KA
Triple pole MCCB 200 to 250 Amp, 25 KA
4 pole MCCB 600 to 800 Amp, 50 KA
SAFETY ITEMS Supply and erection of Medium Voltage caution notice plate of size 200*150 mm in three languages.
Supply and erection of High Tension Voltage caution notice plate of size 250*200 mm in three languages.
Supply and erection of shock restoration chart in glass frame.
EARTHING AND LIGHTENING ARRESTOR Earthing with G.I. earth plate 600 mmx 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) complete as required.
Earthing with tinned copper earth plate 600mmx600mmx3mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and salt) etc. complete as required.
Extra for charcoal or coke and salt for G.I. plate or copper plate earth electrode.
Supplying and laying 25mm x 3 mm G.I. strip in 40 mm dia,GI pipe as/from earth electrode including soldering etc. as required.
Providing and fixing 25 mm x 3mm G.I. strip on surface or in recess for connections etc. as required with all labour and material.
Providing and fixing 25 mm x5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required.
Providing and fixing 25 mm x 5mm copper strip on surface or in recess for connections etc. as required with all labour and material.
Supply and erection of 25mm dia 1.5 Metre long lightning GI. Tube rod tapered into a point at the top with 16cm x 16cm x 3mm thick G.I base plate and necessary nuts and bolts with washers.
LT CABLE Supply and erection of suitable compression type brass cable glands for underground Cable :-10 sqmm to 16 sqmm Cable 2 to 4 Core
25 sqmm to 50 sqmm Cable 2 to 4 Core
300 sqmm to 400 sqmm Cable 3 to 3½ Core
Supply and erection of aluminium lugs heavy duty including crimping etc. upto the entire satisfaction of the Engineer-in-charge of the work. 16 Sqmm
HT CABLE Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 150 to 185 sqmm
Providing & Erection/Laying of PVC / XLPE insulated undergroung Aluminium conductor undergroung cable onsurface / existing cable tray complete in all respect with necessary connection upto the entire satisfaction of engineer in charge of the work. 16 Sq mm 4 Core (Arm.)
35 Sq mm 3.5 Core (Arm.)
400 Sq mm 3.5 core (Arm.)
Supply, Erection, testing and commissioning of Transformer-400 KVA 11/0.433 K. V.3 Phase-50 cycles copper wound outdoor type as per latest IS specification efficency level 3 confirming to IS 1180 and IS 2026 with losses at 50% load 1150W, 100% load 3330 W duly laid on existing foundation at site of work, along with petty works required up to the entire satisfaction of the Engineer-in-charge of work as per detailed specification given as under: No. load voltage ratio 11/0.433 K V. No. of Phase = 3 Frequency cycles = 50HZ Type- double wound core type copper wound Cooling = ONAN Duty = Outdoor Vector group/ISS-DYN 11 Tapping on HV Compensation +5.0% To-10% in steps of 2.50%. Temperature rise (oil/Res = 0C) 40/45 C Attitude= upto 1000metres above M.S.L. Fitting/Accessories Provided. Bucholez relay with alarm and trip contact. OFF LOAD TAP CHANGER Externally hand operated. Oil conservator with Filling hole & cap. Plain oil level guage with minimum Level marking. Thermometer pocket other specifications as per DNIT in PDF.
Supply, installation, testing and commissioning of HT panel 1 way RMU type (1 VCB + 2 loadbreak switches to be used for 2 independent incoming HT power supply) outdoor type Make ABB/Siemens/ Schneider complete upto the entire satisfaction of the Engineer - in - Charge as per specification as under :- with standard protection devices other specifications as per DNIT in PDF.
Dismantling of the old VCB, including its shifting charges through crane etc.
Dismantling of old transformer including its shifting charges through hydra etc.
Buy back of old material i.e. VCB & 315 KVA dry type transformer
Buy back of old main LT panel having 1 no. 800 amp. 4 pole ACB with microprocesser based release, 9 nos. 63 amp. 4 pole MCCB with rotary handle, 2 nos. 125 amp. 4 pole MCCB with rotary handle, 2 nos. 200 amp. 4 pole MCCB with rotary handle, 6 nos. 15 amp. 4 pole MCCB with rotary handle
Buy back of 125 KVR APFC panel with capacitors of various rating, APFC relays, MCCB's, MCB's and other allied items
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .