CWE/PAT/T-18/21-22 PROVISION OF GAS PIPELINE SYSTEM INCL 38 BED HED PANEL AND 01 PENDENT PANEL FOR FAM WARD PAED WARD AND SURGICAL WARD II AND ACUTE MED WARD WITH MEDICAL GAS PIPELINE SYSTEM AT MH PATIALA UNDER GE NORTH PATIALA
2021_MES_446503_1
8321/PAT/T-18/21-22
Limited
Miscellaneous Works
Works
90 days
PATIALA
As per cover 1
6 documents required · 6 mandatory
₹1,000
Yes
GE NORTH PATIALA
₹1.6 L
Yes
15 Jun 2021
29 May 2021
14 Jun 2021
29 May 2021
12 Jun 2021
4 Jun 2021
29 May 2021 - 3 Jun 2021
Amount
Schedule 'A'Section-I (Building Works)
Total amount of Sch 'A' Sec I (Building Works)
Schedule 'A'Section-II (INTERNAL ELECTRIFICATION WORKS)
Total amount of Sch 'A' Sec II (Internal Electrification Works)
Schedule 'A'Section-III (Medical Gas) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only. Note : The work will be carried out by Certified Medical Gas Instalator. The Company should have experience for executing the work in hospitals and the items will be installed all as per OEA requirement.
Supply , installation, commissioning and testing of Fully-Automatic Oxygen Panel with maximum input pressure 220 Bar, output pressure 4.2 Bar, FLOW CAPACITY 1000 LPM, minimum three input points (Main, Back up, External supply/emergency case supply units/LMO), operating temperatures +10 to +45 degree C, Digital LCD display, Alarm, sound and as per technical specifications, approved medical standards and consisting of following features :-
(a) Automatic control system consists two first stage regulators and consisting high pressure reducer panel, Alarm and control panel, left / right Ramp pressure sensors, pipeline pressure sensor, high pressure input valve, input filter, 315 Bar input gauge, high pressure reducer body, pressure set up screw, high pressure reducer drain, high pressure gauge, 2nd stage regulator, regulator set up, automatic change -over, automatic output pressure gauge in emergency outlet, back up system input, plant output regulators, plant output pressure gauges, plant output connected piping, control/power wiring and all necessary arrangement complete and should comply Indian Medical Standards and should comply standard : HTM 02-01/DIN/EN/ISO-7396-1 and should be CE certified.
b) Both the first stage regulators in the oxygen control panel will have non-halogenated polymer in the high pressure side to ensure that there will be no ignition due to adiabatic compression.
(c) 40 micron filter should be provided at the inlet of each high pressure regulators of the oxygen control panel.
(d) The first stage regulators will be connected to a common second stage regulator .The first two regulators meant for first stage will be capable of switchover system incorporated from “RUNNING” to “RESERVE” bank due to differential pressure.
(e) The control panel will provide for two individual content contact pressure gauges to indicate the cylinder pressure in the two wings of the manifold and common pressure gauge to indicate the delivery / line pressure.
(f) The control panel will have built in audio-visual signal lamp indications for bank Changeover.
(g) The control panel will be covered with aesthetically suitable cover for safe operation indicating the respective services.
(h) Control panel will have built in protection system to ensure safe operation by low voltage and all protections of surge, overload and earthfault. The Control panel shall include two pressure relief valves, one high pressure and one low pressure
(j) The panel should have the capacity to withstand maximum operating pressure of 220 bar for safety purposes.
(k) The main control unit must be protected by a mild steel with epoxy powder coated with a viewing window to monitor the digital display . Make: MEC Medical Equipment Co Ltd UK, Reanimed, CPX (UK)
Supply , installation, commissioning and testing of Oxygen Manifold: Main confirming to ISO standards with Middle Frames 2 Banks x 5 Cylinder per Each bank Oxygen Manifold (without cylinders) , suitable to withstand a pressure of 145 Kg/cm2, along with high-pressure copper annealed tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 1/2” I.D. x 15swg with high pressure brass fittings made of high tensile brass and connections through non- return valves; high pressure copper tail pipes, made of high pressure copper pipe of size 1/4” I.D. x 15 swg. The design of middle and bottom frames should be provided to fit both round and flat bottom cylinders safely. The manifold shall be tested (hydraulically) at 3500 psig and necessary test certificates accompany along with the supply. Only Non Halogenated Polymer materials are to be used in the Non Return Valves supplied along with the manifold. Make: Oxicareengineers/ Globalmedlife Solution/ Lifeline Medisol/ Aktiv/LMPL / MK/BSI/MR Engg
Suplly , installation, commissioning and testing of Oxygen Manifold: Emergency confirming to ISO standards with Middle Frames 2 Banks x 2 Cylinders per Bank Oxygen Manifold (without cylinders) , suitable to withstand a pressure of 145 Kg/cm2, along with high-pressure copper annealed tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 1/2” I.D. x 15swg with high pressure brass fittings made of high tensile brass and connections through non- return valves; high pressure copper tail pipes, made of high pressure copper pipe of size 1/4” I.D. x 15 swg. The design of middle and bottom frames should be provided to fit both round and flat bottom cylinders safely. The manifold shall be tested (hydraulically) at 3500 psig and necessary test certificates accompany along with the supply. Only Non Halogenated Polymer materials are to be used in the Non Return Valves supplied along with the manifold. Make: Oxicareengineers/ Globalmedlife Solution/ Lifeline Medisol/ Aktiv/LMPL / MK/BSI/MR Engg
Notes for item No.5 and 6 :(a) The cylinders required will be measured and paid separately.(b) The rate inclusive for the provn of cylinder brackets and fixing chains which will be zinc plated for cylinder placing arrangement. (c) The manifold should be tested (hydraulically) at 250kg / sq cm and the rate inclusive for the same.Each header bar shall be with pigtail connections to suit cylinder valves as per IS:3224. (d) The copper tail pipes are fitted to the individual non return valves of the cylinder Oxygen manifold for easy removal of cylinders without disturbance to system operation and the rate inclusive for the same.. e) The sizes of copper pipe mentioned are of minimum size and the quoted rate deemed to be inclusive of provn of higher sizes if any as per OEM requirement.
Supply installation, testing and commissioning of oxygen Back Pressure Compensated flow meter with control range of 0 – 15 lpm (calibration within +/- 10% ) with 250 ml humidifier bottle made of unbreakable polycarbonate material and autoclavable at 121 degree Centigrade temperature.The flow meter shall be strict precision, durability standard and body shall be made of brass chrome plated materials.The flow tube and shroud components shall be made of clear, impact resistant polycarbonate.Flow Tube shall have large and expanded 0 – 5 lpm range for improved readability at low flows with Inlet filter of stainless steel wire mesh to prevent entry of foreign particles.Make: Oxicareengineers/ Globalmedlife Solution/ Lifeline Medisol/ Aktiv/Aneer Engineers/ SSS Tech/LMPL
Supply, installation, testing and commissioning of Medical Air Plant Reciprocating Type 2000 LPM Duplex System (1 working+1 standby) Including hetles air drier,electrical control panel, reciever tank, pressure reducing station for Air-4 &SA-7, compressors DUPLEX Air system (1 working+1 standby) type with Compressed air filteration system one set of 4-stage filter as per technical specifications:- (a) The Medical Compressed Air System should consist of 2 nos. Air Compressors with Electric Motor, Electrical Switch Gear and Automatic Control System, Air Receiver, No-heat Air Dryer, Pressure Regulator-cum –filter, interconnecting piping with necessary valves and fittings thereof.(b) Specifications: Capacity - 73.3 cfm/2076 LPM piston displacement at 8.5 kg/cm2,Drive Electric Motor -2(two) Nos.(1 working+1 standby) Capacity - 10 HP+10HP.Speed -1440 rpm (syn.) Drive - Belt drive ,Electricity supply-440 volt, 50 Hz. 3 phase,Starter -Star/Delta Control & Switchgear/ L & T/BCH/OEM approved with overload protection and Automatic panel for switching of compressor shall be included. (c) Air Receiver-1000 Ltrs ;The reservoir should be fabricated from MS plates as per IS:226 and manufactured as per IS:2825.The reservoir should be supplied with safety valve, pressure gauge and drain valve etc.manufacture’s test certificate to be provided. Reciever should have feature to pass autocut signal to the plant in case it is full., (d) Air Dryer heatless dessicant type capacity 60 CFM, Make Trident, GeM (e) Filters - Ultra filters,
(f) Compressed air filtration system: one set of 4 – stage filter. The filters should be made of die cast aluminums housing with epoxy power paint on the outside and anodized surface treatment inside to prevent corrosion and ensure extra long life. The filters should have maximum contaminant removal efficiency with minimum pressure drop. Total 4-stage of filters should be used (stage 1 & 2 should be installed before the dessicant dryer and balance two stages after it as mentioned below:-
Stage 1 : coalescing filters for general-purpose protection, removing liquid water and oil aerosol to 0.1 mg/cum. (0.1 pm) and particles down to 1 micron. Stage 2 : particular filter for dust protection, removing particles down to 1 micron. Stage 3 : high efficiency coalescing filters, removing liquid water and oil aerosol to 0.01 mg/cu.m. (0.01 pip) and particles down to 0.01 micron. Stage 4 : active carbon filter for removal of oil vapors and hydrocarbon odours with maximum remaining oil content of 0.003 mg/cum. (0.003 pip) should be installed after stage 3 filter. The filters should have following additional features : Audible alarm to give warning when dismantling attempted under pressure Sight glass to allow visual check of liquid collection and drain operation. Make: Anesta / Wata /Ingersol Rand/ Boge/Coaire/Frank
Supply, installation, testing and commissioning of Medical Vacuum Plant Reciprocating Vacuum 2500 LPM Duplex system (1 working+1 standby) ,with reciever tank 1500 Ltr, bacteria filters, vacuum filters complete all as per technical specifications and as per the following :-
(a) Vaccum Pump Single stage, minimum capacity 3141LPM/111 cfm(piston displacement) or 7.5 HP each motor. Each pump should be suited for maximum working pressure of 29 inch mercury (730 mm mercury) Each pump should be fitted with MS channel frame complete having vibration isolators with 3 Nos.silencers at vacuum pump discharge end. The pump should be air cooled. 3 sets of isolation valve, on return valve and filter should be provided with pumps the system should be expandable to receive one additional pump in future. (b) Drive Assembly :The electrical drive for vacuum pump should consist of suitable TEFC induction motor operating at 1440 RPM and connected through a V-belt. The motor shouldbe suited for 415 V +10% 50 HZ.3 Phase AC supply.Capacity : 7.5 HP-2 Nos (1 working+1 standby) make-Crompton Grease / Kirloskar/OEM approved, 3 phase,Starter - Control & Switchgear/ L & T/BCH/Havells/Schinider/OEM approved with overload protection, panel for automatic switching of pumps. (c) Vacuum Receiver : 1 No vacuum receiver of 1500 liters capacity The reservoir should be fabricated from MS plates as per IS:226 and manufactured as per IS:2825.The reservoir should be supplied with safety valve, pressure gauge and drain valve etc.manufacture’s test certificate to be provided. Reciever should have feature to pass autocut signal to the plant in case it is full.
(d) Vacuum Switch :Vacuum switch of 0-760 mm range should be provided, should have both NO/NC contacts and suitable for 230 V 50 Hz AC supply. The vacuum switch should be housed in weather proof casing with 3/8”BSP gas service connection at the bottom of the assembly. (e) Vacuum Filter :2 Nos vacuum filters with drain valve. This filter should be non-ferrous and online. The discharge to autosphare should be through micron filter cartridge, and suitable capacity bacteria filter & secretion trap (f)The medical vacuum plant shall be CE Marked/ISO comprising of air cooled, oil lubricated rotary vane/reciprocating vacuum pumps to provide a flow rate. Make: Anesta / Wata /Ingersol Rand/ Boge/Coaire/Frank
Suply, installation testing and commissiong of Ward suction unit or Ward Vacuum Unit with above 1000 ml suction collection jar-1 Nos as per specifications mentioned below:-
(a) The vacuum regulator should have a vacuum gauge with analog display.The scale should be in mbar or mmhg as required by the end user. (b) 1no of Suction Regulator and 1no of 1000 ml polysulfone /polycarbonate collection jar. (c) Suction regulator should be supplied with a safety jar, including and antibacterial filter and an anti-overflow safety device and should have wide membrane continuous suction controller.(d) Should have vacuum levels: 0-760 mm of Hg and Should have vacuum gauge fitted with a protective bumper device. (e) Should have on/off knob allowing for the quick restoration of a readjusted vacuum level. (f) Must have central adjustment knob with a color coded for 0 to 760 mm of Hg. Should have Polysulfone/polycarbonate 1700cc safety jar, autoclavable at 121º C at 5mins, unbreakable, fitted with an anti-overflow safety device and equipped with a plastic antibacterial filter and should be totally transparent, to ensure perfect sucked liquid visibility. Make- Aneer/SSS Tech/LMPL
Supply,Installation testing and commissiong of Copper Piping 28 mm OD x 1.0 mm thick with complete fittings/fixtures as per technical specification and BS: 13348 and as mentioned below:- (a) Installation of piping should be carried out as per approved medical standards with utmost cleanliness. (b) Only pipes, fittings and valves which have been degreased as per approved medical standards should be used . (c) Pipe fixing clamps for upto 28mm diameter. (d) Pipes should be non ferrous suitable for the diameter of the pipe and wherever required rigid metallic hanging or cemented supports to be used. (e) The main lines to the building to be taken overhead through heavy grade metallic poles or GI tubes with inspection points in metallic boxes wherever required . Adequate supports shall be provided while laying pipelines to ensure that the pipes do not sag. (f) All copper pipes and fittings should be made of phosphorous de-oxidized, non arsenic, and fully degreased. All pipes should be of Copper and copper alloys Seamless, solid drawn round copper tubes for Medical gases or vacuum.
Suitable sleeves shall be provided wherever pipes cross through walls / slabs. All pipe clamps shall be non-reactive to copper.(f) All pipe joints should be made using inert gas fluxless brazing method. (g) All brazed joints in the piping shall be made up using brazing filler metals that bond with the base metals being brazed and that comply with Specification for Brazing Filler Metal, ANSI/AWS A5.8. Copper-to-copper joints shall be made using a copper-phosphorus brazing filler metal (BCuP series) without flux. Dissimilar metals such as copper and brass shall be joined using an appropriate flux with either a copper-phosphorus (BCuP series) or a silver (BAg series) brazing filler metal. Apply flux sparingly to the clean tube only and in a manner to avoid leaving any excess inside of completed joints. All joints should be of copper to copper and should be brazed brazing filler material without flux while being brazed joints shall be continuously purged with oil free dry nitrogen to prevent the formation of copper oxide on the inside surface of the joint. (h) All pipes should be installed without springing or forcing. (j) All pipes should be protected against mechanical injury in a manner satisfactory to authorities having jurisdiction.(k) Painting: All existing and proposed exposed pipes/should be painted with two coats of Synthetic enamel paint & color codification as per IS : 2379 of 1963. and approved medical standards. (l) All pipe clamp shall be non-reactive to copper. After erection the pipe should be flushed and then pressure tested with dry air at a pressure equal to 1.5 times of the working Pressure or 150 psig, whichever is higher for a period of not less than 24 hours in presence of medical authority/ MES authorities.
(m) All concealed pipes to have gas identification bands / labels at appropriate distance. (n) Similarly all pipes which need embedding in the wall should be tested/painted/labeled and properly insulated. (p) Certification: To be certified that pipes are suitable for the particular service and complete cross connection (anti-confusion) test should be carried out. (q) Distribution piping system: MATERIAL (PIPE): Solid drawn, seamless, deoxidized, non arsenical, half hard, tempered and degreased materials conforming to BS: EN 13348. Copper pipe must have reputed third party inspection certificate (Lloyd‟s / Kite / TUV or SGS). Fittings should be made of copper conforming to BS 864 and suitable for a working Pressure of upto 17 bar and especially made forbrazed socket type connections. (r) Pipe line should be supported at the intervals using suitable non-ferrous material suitable for the diameter of the pipe. (s) Fitting shall be end feed type, manufactured from the same grade of copper on the pipes as per BS864/EN1254. (t) The lot no of the manufacturer should be laser embossed on the cupper tubes.
All copper pipes should be inspected and certified for medical use before dispatch and the pipe should be delivered plugged or capped at both ends. Note: (a) The tenderer shall design & submit complete layout drawings with proper colour code, fittings, fixtures complete for approval of GE or rep of accepting Officer before placing order and the quoted includes for the same.(b) The quoted rate inclusive of all mechanical protections with metallic pipes to pipe required, contractor is required to visit the site prior bidding Make: Mex flow/Janya/ Metal Gem / Cubex/Metalco
All as per srl item no 11.00 to 11.03 here-in-before but 42mm OD x 1.2 mm thick
All as per srl item no 11.00 to 11.03 here-in-before but 22mm OD x 1.0mm thick
All as per srl item no 11.00 to 11.03 here-in-before but 15mm OD x 1.0mm thick
All as per srl item no 11.00 to 11.03 here-in-before but 12mm OD x 1.0mm thick
Supply,Installation, testing and commissioning of oxygen Gas outlet points complete with matching probe/adopter with one end suitable for Hose & other end suitable for terminal units complete set for Oxygen, Nitrous Oxide, Air, & Vacuum system as per technical specification confirming to CE certified/ HTM 02-01/EN/ISO/DIN and as mentioned below:- (a) The outlets shall be modular singles, and shall incorporate nameplate color-coding. The single modular outlets shall be of a design that provides for ganging of rough-in plates in the field to form multiples. (b) The gas services shall be sequentially arranged and located as shown on the plans with a minimum centerline spacing of 5 inches (12.5 cm) between outlets. (c) The outlets shall be capable of supporting dispensing equipment without the use of slide brackets. The medical gas outlets shall be designed so that, once installed, routine service of both the primary and secondary check valves can be accomplished without removing the nameplate or gas specific portions.
(d) The primary check valve shall be unitized and of the cartridge type. So that the primary check valve can be removed for service without shutting off the gas supply to the outlet, the secondary check valve shall operate automatically to stop the free flow of the pressure gas. (e) There shall be no secondary check for vacuum or gas evacuation service. Medical gas outlets that require the removal of the nameplate or gas specific components for routine service shall not be acceptable. (f) The outlets shall Conform to CE certified (CE 0482)/ HTM 02-01/EN/ISO/DIN and should meet with the provisions of council Directive of Medical Devices Directive. (g) All outlets are 100% tested for flow and leaks (h) The outlet nameplate shall be permanently color coded with a durable scratch-resistant and protective label. (j) Medical gas outlets shall be cleaned for oxygen service as per Medical Standards, capped and placed in a protective container for shipment. (k) The outlets shall be installed in strict accordance with manufacturer’s instructions, and tested before use in conformance with local and federal codes.
(l) Outlets shall be Double Lock Outlet type manufactured with an approx 165 mm length, Copper inlet pipe stub which is silver brazed to the outlet body. Body shall be of one piece brass construction. For positive pressure gas services, the outlet shall be equipped with a primary and secondary check valve and the secondary check valve shall have break safe mechanism and also comply to pressure test standards and rated at minimum 200 psi in the event the primary check valve is removed for maintenance.The outlet assembly should have separate colour coding for each services and will accept only corresponding gas specific adaptors. All outlets shall be cleaned and de-greased for medical gas service, factory assembled and tested.The medical gas outlets should be of quick connecting and wall mounted modular type. Make: MEC MEDICAL EQUIPMENT CO LTD UK/REANIMED CPX (UK)
All as per srl item no 12.00 to 12.02 here-in-before but Medical Air Oulet with probe (Compressed Air ( 4 Bar ))
All as per srl item no 12.00 to 12.02 here-in-before but Vacuum outlet
Area gas alarm panel six lines, would audio Visual alarms for each gas used on the floor and come fitted with test and mute button Running on electricity 220 V,these units are suggested to be fitted on each floor as well as are as of heavy usage.it would be fitted with a pressure gauge.It indicates low,medium & high pressure sensors. The gas alarm system should have :- (a) Three gas alarm. (b) Individual gas status LED indicator-showing NORMAL, HIGH and LOW conditions for each service. (c) Audio alarm for high and low pressure condition. (d) Display of line Pressure for all the services with factory calibrated pressure sensors. (e) Alarm test / check / mute Facility needed. (f) Small and compact in design. (g) Mounted on a powder coated MS box. (h) Nut and Nipples are to be provided for connection with pneumatic supply line. (j) Low voltage internal operation with input power supply of 220 V AC. (k) Battery Backup. (l) Easy wall mounting facility. (m) The model should be IEC 60601-1-2 compliance. (n) It should be compliant to ISO 7396-1/NFPA 99/HTM standards. (o) The producT should be BIS / CE Certified. MAKE : BSI/LMPL/MR ENGG
Supply, Installation, testing and commissioning of the Master Alarm Panel, which shall be LCD touch screen microprocessor controlled and designed to comply with Complies with HTM 02-01 /EN (ISO-7396-1)/DIN/CE Certified (CE 0482) . The panel shall be 100% digital and shall not require re-calibration. The panel shall be able to interface with building management systems with the use of either an Ethernet Modbus interface or a BacNet interface or RS-485 Transmission. The alarm panel shall be enclosed in a steel box and shall be designed to accept an electrical input range of 120-240 volts AC – 50-60 hertz.
The source voltage shall be stepped down with a self-contained transformer. The panel shall contain audible and visual alarm indicators. The audible alarm may be silenced by pressing the alarm silence button, but the visual alarm indicator can only be cancelled by fault correction. The alarm shall detect and filter out transient signals (less than 0.6 seconds). The alarm shall be capable of displaying alarm history for all possible alarm conditions. Each source signal module shall monitor 6 to 8 source signals.
Each Master Alarm should be modular in design and be fitted with required number of master alarm modules. The master alarms should be capable to monitor from 10 to 30points in a standard box or 10 to 50 points in a large box. Each point represents an alarm condition that the source equipment might have. When an alarm condition exists, a red light flashes and the audible alarm sounds. If several alarm conditions occur simultaneously, the most recent alarm light should flash, while the other alarm lights should remain lit. When an alarm condition is created, an audible alarm should be actuated. A dry contact module should be available to interface with a building management system.
The box material should be of gauge steel of requisite thickness and equipped with mounting brackets that are adjustable . The emissions from alarms should conform to EMC standards.
The Panel shall Complies with HTM 02-01 /EN (ISO-7396-1)/DIN., High visibility LED/LCD readouts , Adjustable audible alarm repeat (from 1 to 99 minutes) , Can be interfaced with BMS and Should be European CE Certified (CE 0482) and should meet with the provisions of Council Directive 93/42/EEC concerning Medical Devices Directive.
Note for item No. 20 to 20.04 :(a) The rate inclusive of all necessary control & power wiring with copper conductor cables with necessary conduits , clamps, cable trays etc and interconnection of master and area valve service unit with inbuilt area alram and all cabling from local alarm panels to master alarm panel complete. Make: Greggersen,Germany or Pneumatik Berlin- Germany / MPS/Tri-Tech Medical -USA / Phoenix-Pipeline-UK/Modular-US/ BSI/LMPL/MR ENGG
Supply, Installation, testing and commissioning of 15mm OD MEDICAL LINE VALVE or ISOLATING VALVE as per CE CERTIFIED /HTM -2022/02-01/DIN/ISO/ BS EN 1057 or ball valves as per BS 1057 , rated at 400 psig, as well as full vacuum ( 29.9" Hg). Valves go from full ON to full OFF by turning the vinyl-gripped valve handle 90 degree Locking-type handles may be ordered separately when required. Copper tubing is factory installed to help prevent valve seat damage during soldering. main and riser valves are not required to be installed in a box unless specially noted or required. MAKE- CONEX/ RB/ AKTIV
All as per srl item no 21.00 here-in-before but 22 mm OD
All as per srl item no 21 here-in-before but 28 mm OD
Supply, installation, testing and commissioning of Horizontal Bed Head Panel with provision of a safe efficient means of delivering services to patients staff in both general and special care applications, it is modular design made of horizontal aluminium extrusions, and ability to house medical gas termainal units ( as per specifications of tender) and electrical socket , smooth curved surfaces, no visible screws and choice of coloured décor stripe, ease of installation via separate rail-bracket or wall mounting plates, easy removal of covers for maintenance and pipeline connection, with integral twin medical rail as part of the modular extrusion design. It has segregation of services i.e. extra low voltage, normal voltage and medical gases , should be maintained throughout . Its aluminium extrusions have a polyester coating finish on all external surfaces. It have provision for nurse call, data or monitoring sockets, should be made at the point fo manufacture .It should be supplied duly prepiped , prewired and fully tested or in carcass form. "Each Horizontal Bed Head Panel shall be having a provision of (as per outlet distribution list) - four multipin 5-15 Amps , switch socket outlet combine - it should be minimum 1500 mm long."with provision for nurse call"
(a) It shall confirm to ISO Standards with the following features (i) The headwall system should be constructed of aluminum extrusions joined together to form a carcass to suit the particular application. Unit should be factory assembled for electrical and mechanical components.
(ii) Segregation of services i.e. Low voltage supplies, High Voltage supply and Medical gases should be maintained throughout. Front fascia plate should be removable individually to access for respective service. Bed space management system with optional equipment rail. With all Equipment Rail mount Accessories. All down drops should be installed at one end preferably & Vertical drop installed at one end should be covered with Aluminum boxing with matching color. Entire pipe line should run in continuous horizontal panels with no break for each unit & length as per area where it has to be installed.
(iii) Each bedhead unit shall be supplied with electrical and electrical outlets prefitted, wired and certified. (wired up to the distribution box provided with leakage protection) facility per unit as under: Oxygen – 2 ,Vacuum – 2 ,Medical Air-2 , Holder for vacuum collection jar –1 , Nurse call switch – 1 , Infusion pump mount pole with adapter for mounting at least two infusion pumps , 5 /15 A combined Electrical outlets – 6. , Two spare spaces , Monitor Bracket Makes :Oxicareengineers/Globalmedlife solution/Aktiv/ Lifeline Medisol/Tedisel/ MR ENGG, LMPL/RADIX
Supply, install,testing and commissioning of Anesthesia Pendant - Pendant, Comprising of: - basic Console -600 mm, Single Shelf 500 mm x 400 mm x 50 mm, with onlyprovision of IV poles Set (tube for Bottle holding) mains socket 04( 15A Single), Medical Gas Terminals 04 & Hose Assembly -Medical Rail - One Set. All as specified and directed at site. Make: Oxylitre /Oxicareengineers/Globalmedlife solution/ Aktiv/ Lifeline Medisol/MR ENGG, LMPL/PRATIBHA
Notes for Item No.1 to 23: The quoted rate inclusive for the following:- a) The Contractor shall provide comprehensive on-site warranty (Including All Spares,Accessories and Labour) for a period of 3 years from the date of final acceptance of the complete system after successful and complete installation and commissioning with regular updation of newer technology as and when evolved. b) The Contractor shall, depute trained manpower to maintain manifold and medical gas pipeline system in case of any breakdowns within 24 Hrs.The technical maintenance personnel of the Contractor shall be responsible for supervision and maintenance shall be available to reach the site(s) within 1 hour's notice. c) If the performance of any individual equipment or system is not satisfactory, the same shall be replaced by the contractor free of cost.
d) If it is found that to meet the performance criteria, any extra equipment is required the same will be provided free of cost by the contractor. e) All faults appearing and their rectification shall be periodically advised to the hospital, the period being not more than a month. f) Any lacuna or lacunae noticed in the functioning of the installation as a result of any design feature shall be rectified by thecontractor free of cost. g) The Contractor shall fully associate the engineers and technicians for MH Patiala during installation, testing, commissioning, operation and maintenance period. The testing of the entire system shall be carried out in the presence of GE / AGE and Officer rep (Min 02 Nos.) from Hospital authorities. h) The Contractor shall train the staff of MH Patiala the operation of complete medical gas and oxygen plant system. j) The Contractor shall submit MOU with authorised Medical Service engineer/ registered Bio medical engineer services experienced in the relevant field for not less than 5 years immediately before placing work order. k) All electrical wiring/cables,cable tray, earthing, Control panels, connected electrical & pipeline distribution system with all connected accessories of complete medical gas system and oxygen plant system is deemed to be included in the quoted rates.
Supply, fixing and testing Voltage stabilizer for automatic operation, three phase, naturally oil cooled, indoor type & designed for input variation between 300 V to 480 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 30 KVA
Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 core complete all as specified and directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe will be measured and paid under respective item of schedule.
Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core complete all as specified and directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe will be measured and paid under respective item of schedule.
Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core complete all as specified and directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe will be measured and paid under respective item of schedule.
Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4 core complete all as specified and directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe will be measured and paid under respective item of schedule.
Sand bedding for coushing of cables complete all as specefied and directed. Note:- Punned thickness of 18 Cms will be measured and paid.
Supply and fix GI pipe light grade 40 mm passing through cables, walls , across the roads with proper clamps, nut & bolts including taking down complete all as specefied and directed.
Supply and fix 4 Pole MCCB 100 Amp, 50 Hz, 415 V AC with rupturing capacity 25 KA ,thermal adjustable ,Icu=100%Icu in sheet steel enclosure made out of CRCA sheet duly powder coated of thickness 2mm with IP- 54 and LED indication lamps complete all as specified and directed by Engineer-in-Charge.
Earthing complete with galvanized steel earth plate, electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI strip 25x4 mm as earthing lead covered with 20mm bore GI pipe light grade by means of bolts, nuts, check nuts and washers of galvanised iron or steel, connected to earthing test point, earth plate electrode surrounded by mixer of common salt and charcoal dust, including 20 mm dia GI watering pipe 'medium grade', funnel with wire mesh, earthing chamber with cement concrete (1:3:6) type C-1, RCC chamber cover 80 mm thick (1:2:4) type B-1, excavating & earth work all as shown in electrical plate No. 3 of SSR (Part-I) and testing on completion complete all as specified and directed.
Supply, installing, testing and commissioning of LT feeder pillar box factory made oudoor type, double door, slopy canopy, fabricated out of 3.15mm thick CRCA sheet with angle iron base frame made of 50 x50 x 6mm ,45 cm height, dust and vermine proof, suitable for voltage 415 V 3 Phase 4 wire weather proof, with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with aluminium busbar (TPN), suitable double compression copper cable glands complete in all respect for Dg set main Panel and including provn of the following:-
i)Aluminium Bus bar 200-A- mounted on porcelain insulator - 01 Set ( Set of 4 Nos) with PVC sleeve insulation
ii) MCCB 4 pole 415 V 3 phase125 Amp, 16 KA (Thermal magnetic release) Ics=100%Icu and adjustable overload setting 80% to100% - 01 Nos (incomming)
iii) MCCB 4 pole 415 V 3 phase 63 Amp, 16 KA(Thermal magnetic release) Ics=100%Icu and adjustable overload setting 80% to100% - 02 Nos (outgoing)
vi) RCBO Double pole 40 Amps Sensitivity 300 mA 240V 50 HZ AC supply - 02 Nos
vii) Digital time switch with current carrying capacity 16 Amps 1 Ph -02 Nos
viii) Digital voltmeter 96x96mm from 0- 500 volts - 01 Nos
ix) Digital Amp meter 0-500 Amp with CT's & slection switch - 01 Nos
x) RYB LED indicator- one set
S&F MCB, single pole 240 volts 6 to 32 Amp capacity fixing in DB’s including proper thimble connections complete all as specified and directed. Make:- Indo Asian,standard, havells.Make:Schenider,Seimens,Legrand
S&F MCB TP,4 Pole,415 volts,63 amp, 16 KA rupturing capacity for fixing in DBs of including proper thimble connections complete all as specefied and directed. Make:Schenider,Seimens,Legrand
Material and labour for precast concrete cable covers class LV, Type 1, flat, size 300mmx l80mm x 40mm laid dry in trenches for cable protection all as specified and directed by Engineer in Charge.
S&F powder coated 50 microns extruded aluminium glazing/ doors & shutters made out of section 63.5x38.10x1.29mm for chowkats or frame & shutters made of size 44.45x44.45x1.29mm for side rails and middle rail, 114.3X44.45X1.29mm for top rails and bottom rails and including 12mm thick High Density Fibre Board pre-laminated on both sides (water proof) below & above middle/lock rail and to be fixed with and including EPDM gasket to render the glazing, air and water tight etc. & aluminium beads 20mm size with and complete all as specified and directed including supply and fixing the following items: (a) Stainless Steel (304 Grade) Finished Butt Hinges 125mm - 3 nos per leaf. (b) Powder Coated Aluminium Tower Bolt 200mm long - 2 nos per leaf (c) Powder Coated Aluminium Handles 150 mm - 2 nos per leaf
M&L for Rubber moulded machine pressed precast concrete interlocking paver block (available in different colour for making patterns) any shape and size confirming to IS 15658-2006 of 60 mm thickness, M-35 Grade with gray cement and pigment laid over and including 25 mm thick sand cushioning complete all as specified and directed by Engineer in Charge.
M/s MAKHAN ENTERPRISES
Jawandha Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .