Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹61.5 LAdmitted-Finance | -22.89% | ₹61.5 L | L1 | Admitted-Finance |
| 2 | L2₹62.2 LAdmitted-Finance | -21.99% | ₹62.2 L | L2 | Admitted-Finance |
| 3 | L3₹63.8 LAdmitted-Finance | -19.99% | ₹63.8 L | L3 | Admitted-Finance |
Tender Value
₹79.8 L
EMD Value
₹1.6 L
Closing Date
29 Jan 2026, 2:00 pmClosed
Executive Engineer,PHED,Distt Rural Div.I,Bikaner
Executive Engineer,PHED,Distt Rural Div.I,Bikaner
Construction and Commissioning of Tubewell with 2 Year DLP and 5 Year OandM and Replacement of Old Polluted Pipe Line At Village Jasrasar
2026_PHCJA_528329_1
NIB 85 2025-26
Open Tender
Civil Works - Water Works
180 days
Bikaner
Please refer Tender documents.
3 documents required · 3 mandatory
₹2,000
Executive Engineer,PHED,Distt Rural Div.I,Bikaner
₹1.6 L
Yes
5 Feb 2026
16 Jan 2026
29 Jan 2026
16 Jan 2026
29 Jan 2026
16 Jan 2026
Constructon and Comm of Tubewell
Construction of tube well from ground level & up to 100 mtr depth to accommodate housing and assembly pipe of following sizes in all type of alluvium strata unconsolidated formation such as pebbles, boulders etc. by percussion/rotary drilling method as per IS:2800 Part 1: 1991 and IS:2800 Part II: 1979 (both amended upto date) and technical specifications, with gravel as per IS:4097-1967 and it's packing as per IS: 2800 (Part I & II) 1979 as amended up to date (the work includes the cost of gravel & it's primary packing and packing during development, lowering of housing & strainer assembly pipes with supply and wrapping of coir-rope, wherever necessary for arresting fine sand particles and development work, but excluding the cost of housing and strainer pipe assembly). The work would be completed after obtaining sand free water.Nominal bore 250 mm dia.
Add 15% extra on depth more than 100 mtr for drilling beyond 100 mtr and upto 200 mtr depth from ground level.
Add 40% extra on depth more than 200 mtr
Construction of tube well after completion of drilling by rotary method & upto 150 mtr. depth in all type of rocks by DTH system as per IS:2800 Part 1: 1991 and IS:2800 Part II: 1979 (both amended upto date) and technical specifications. The work shall be deemed completed only after obtaining sand free water. The bore well should have a throughout nominal size bore beyond casing pipe. Nominal bore 200 mm dia.
Add 15% extra on above item (Item No 2.4.1 to 2.4.2) for drilling depth beyond 100 mtr and up to 200 mtr from ground level, rate shall be applicable for only extra depth beyond 100 mtr and up to 200 mtr.
Supply of ERW M.S. black casing pipe ISI marked (IS: 4270/2001) or amended up to date of following sizes 250 mm dia NB (Thicknee of pipe 7.1 mm & mass of tube 46.57 Kg/m)
200 mm dia NB (Thickness of pipe 5.4mm & mass of tube 28.46 Kg/m)
Labour charges for making slots on blank pipes made of ERW MS black pipe of following sizes, the slotting should be as per IS:8110-1985 or as amended up to date. 250 mm dia nominal bore of 7.1mm thickness
Supply & Fixing tube well cover of MS sheet 8mm thick at top & 5mm thick 100mm wide shroud around the edge so as to form a cap on the top end of casing pipe with GI Nipple 45cm long & two GI flanges at both ends in 80mm sizes passing through a hole in the centre of MS sheet. A 25 mm socket with end plug shall also be welded over top plate. A GI nipple having outside thread of size 1/2" (for installation pressure gauge) shall be provided & welded with 80mm GI nipple near top plate nipple shall be provided with end plug. 250 mm dia
Providing & Lowering in tubewell ISI marked GI Pipe “B" (medium) class as per IS:1239 part I 2004 or amended up to date, threaded and double flanged (welded) on both ends and two number 25x3mm MS flat welded on both ends between pipe & flange, rubber washer & nut bolts etc. complete in all respect.65 mm dia
Supply & Installation of 3 phase ISI marked submersible motor pump set of five star rating by BEE and as per IS: 8034-2018 (pump) and IS 9283-2013 (motor) or as amended up to date of approved make of following duty condition with required accessories including making connection suitable for tube well/DCB. The job includes lowering of motor pump, installation of complete fitting & accessories, jointing of electrical cables up to switch board, testing of submersible pump set and interconnection up to water mains, complete in all respect. 15 KW (20 HP) and above, head above 120 mtr.
Supply & Fixing of ISI marked three core PVC flat submersible cable as per IS 694:1990 or amended up to date and conductor as per class 5 of IS 8130:1980 including making connection etc. 3 core 10.0 Sq.mm
Supply & Fixing XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured of IS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand, second Class bricks covering, refilling earth, compaction of earth, making necessary connection, testing etc. as required of size. 35.0 Sq.mm, 3.5 core
S & F M.S. clamp, set of 50x6mm flat from iron with nuts and bolts etc. for holding the riser pipe assembly of submersible pump set.
Supply and Fixing of electric control feeder panel comprising of suitable rating MCCB , fully automatic star-delta starter, over load relay, ampere meter with CTs, volt meter, phase preventor, suitable starting capacitors, phase indicators, lighting arrangement etc complete suitable for three phase pump set. The panel should have space for energy meter ( supplied by DISCOM). All these equipments shall be housed by panel box made out from 18 guage M.S. Sheet with powder coating. Panel should be of minimum size 900 x 600 x 450 mm with Stand ( made of angle iron of size 35x35x5mm) duly bolted/screwed with enclosure box having 4 legs, each leg’s length 18" and double door including in built locking system. The legs should be embedded in M-15 cement concrete plat form.The size of CC plateform should be equal or bigger than the base size of panel having height of at least 200 mm from ground level. The panel should have opening of suitable size in front of space for energy meter with glass for meter reading. The operation of panel should be suitable for 440 Volt AC Supply.Above Above 15 HP and up to 20 HP
Providing & Fixing of double flanged, CI body, ISI marked NRV of approved make of following sizes 65 mm dia
Providing, installing, testing and commissioning of double flanged bulk flow meter with removable mechanism, of class B conforming to ISO 4064/1 or amended upto date of approved make including cost of all material and labour as per specifications with GI Box (sheet 16 SWG) suitable with locking arrangement of following dia.
65mm dia
Maintenance of tubewells which includes round the clock monitoring of tubewells of all sizes, complete repairs / rewinding of submersible pump sets including cost of material components required to repair pumpsets, starters, meters etc. of electric panel of tube wells, Lowering and unlowering of pumpsets complete in all respect, maintenance of log-books & Histroy sheet as directed by Engineer-in-charge for tubewell per month. (16.0 HP to 25.0 HP)
Part B - Providing Laying Jointing of Pipe Line
Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in trenches of required width and gradient for laying and jointing of pipe line including excavation for sockets, and dressing of sides, ramming of bottoms, depth up to 1.5 Mtr. including taking out the excavated soil, and then returning the soil as required in layers not exceeding 20cm in depth including consolidating each deposited layer by ramming, watering etc. and disposal of surplus excavated soil as directed within a lead of 50 Mtr. including required all safety provisions etc.: All kinds of soil
Providing, lowering, laying in trenches, aligning, fixing in position and jointing Ductile Iron (DI) ISI marked K-7 grade S&S pipes as per IS:8329-2000 (amended up to date), with internal cement mortar lining suitable for potable water with rubber ring (EPDM) joints as per IS: 5382-1985 including all taxes (Central and local), transportation and freight charges, inspection charges, loading/ unloading charges, including cost of labour and material, specials (Tee, bend etc.) satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge. (excluding earth work) Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately.
Providing, lowering, laying and jointing in trenches, standard lengths HDPE ISI marked Pipes as per IS-4984: 1995 (amended up to date) with necessary jointing material like mechanical connectors, i.e. thread/ insert joint/ quick release coupler joint/ compression fitting joint or flanged joint and specials jointing pipe by electro fusion welding method, including all taxes , transportation and freight charges, inspection charges, loading/ unloading charges, stacking of pipes, including cost of labour and material, specials (Tee, bend etc.), satisfactory hydraulic testing, disinfection, commissioning etc. complete as per technical specifications and direction of Engineer-in-charge of following class and diameter. (excluding earth work) . Note : Providing and fixing of all requisite specials as per drawing, design and layout are inclusive in RM measurement of the item and shall not be paid separately. Supply may be in coil or straight length in 6 M/12 M.
90 mm dia
Providing, lowering, aligning, fixing in position in pipe line, CI D/F Sluice valves of approved make of following Pressure rating & dia complete, confirming to IS:14846 (amended up to date) and of following specifications: Body, Bonnet, Wedge, Gland, Thrust Plate, Cap & Hand wheel of Grey cast iron of IS:210/ FG200 Stem - SS 304 ,Body Seat ring, Wedge facing ring & Bushes - LTB2/ SS , Face to face dimensions as per IS 14846/2000 (amended up to date), All exposed machined ferrous surfaces shall be painted with one coat of aluminium red oxide primer conforming to IS:5660 and two coats of black Japan paint conforming toType B of IS 341or paint conforming to IS9862 or IS2932( Non-Toxic- suitable for drinking water) applied inside and outside, Flanges Drilled as per IS 1538.Nut-Bolt confirming to IS:1363 and IS: 1367/ CS/ galvanised steel.Insersion rubber of black EPDM 6mm thick . Suitable support structure as per directions of EIC. Sluice valves including all jointing & jointing material, labour, testing and commissioning along with pipe line as per Technical Specifications and as per direction of Engineer-in-charge. Note: Rates are exclusive of tail piece/ dismantling joints and earth work. Manually Operated CI Sluice valve of Class PN-1.0
Providing and fixing of flanged/ plain ended MS Specials made from MS sheet strips of relevant IS specification of approved thickness by welding, lowering, laying, aligning, fixing in position at all level/ depths in trenches complete including all taxes, material, labour, inside lining, outside coating, testing and commissioning along with pipe line as per technical specifications and direction of Engineer-in-charge. MS pipe specials upto 600 mm dia (with minimum 5.0 mm thickness sheet)
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.20 MB
BOQ_942609.xls
BOQ • 0.28 MB
TD85Final.pdf
Tender Documents • 2.90 MB
Download all tender documents and submit your bid