| 1.00Following works to be carried out at 132 KV S/S Manauri, Kaushambi | ||||||
| 1.01 | Complete overhauling of manually operated 132 KV isolators, by opening of its 06 Nos stacks, replacement of defective bearing of same size and repairing of housing if required cleaning of isolator stack by special liquid detergent, filling of high-quality grease. Tightening of all nut & bolts, opening of male/female contact its cleaning and refitting with proper alignment. Application of white petroleum jelly on contact & fingers, oiling and greasing of all movable parts checking of alignment for smooth and reliable operation ensuring all safety precaution, all consumable shall be arranged by contractor, materials and skilled & un skilled manpower required satisfactorily completion of above work. Bay wise detail of isolators given below: (1). 132 KV Cantt. Bay1 LI,2 BI-03 Nos. (2) 132 KV Sirathu Bay - 1 LI.2 BI-03 Nos. (3) 63 MVA Transformer I/ and II Bay (H.V. side) 2 LI. 4 BI-06 Nos. (4) 132 KV T.B.C. Bay-2 BI- 02 Nos. | 14 | Nos | 10,000 ₹1,40,000 | 9,980 ₹1,39,720 Lowest | 9,990 ₹1,39,860 |
| 1.02 | Replacement of defective 02 no, 415 volt. 16 A, 4NO+2NC power contactor for main supply of cooling fans installed on 20 MVA T/F work includes proper connection of contactor with ACDB or AC cubical installed in the switchyard including the cost of all material which will be provided by contractor on their own cost & risk. | 1 | Job | - | - | - |
| 1.03 | Replacement of defective 04 no fan control contactors of rating 230V, 9A, 08 NO, for auto function of cooling fans and 03 no relays of rating 230 V, 9A, 02NO+02 NC for supply monitoring for cooling fans including the cost of all material which will be provided by contractor on their own cost & risk. | 4 | Job | - | - | - |
| 1.04 | Replacement of defective 05 no overload relay of rating (0.5-1A) for cooling fan of transformer on the front side of the marshalling box including the cost of all material which will be provided by contractor on their own cost & risk. | 5 | Job | - | - | - |
| 1.05 | Replacement of defective 05 No 3pole MCB having 230V, 2A on tubular rail fence inside marshalling box including the cost of all material which will be provided by contractor on their own cost & risk. | 5 | Job | - | - | - |
| 1.06 | Wiring of all interconnection with proper ferrules and lugs of suitable size with 4 mm² flexible insulated copper conductors for power connection and with 2.5 mm2 flexible insulated copper conductor for control connection in the marshalling box to RTCC panel as per site required up to completion of works satisfactorily. (Works includes supply and fixing of cable gland (all size), wire. rail base, ferrule, logs, supply and fixing of gasket for marshalling box, repairing of box with front door as required for proper operation of marshalling box, selector switch as per requirement will be provided/done by contractor on their own cost). | 1 | Job | - | - | - |
| 1.07 | Supply and fixing of 08 no fan control switches for on/off control of fans (ON/OFF) of ratings 415 V 10A of standard make including the cost of all material which will be provided by contractor on their own cost & risk. | 8 | Job | - | - | - |
| 1.08 | Supply and fixing of 10 no tap position indicator of push off type with the rating 230 V. 2A, and 01 no panel lanip (LED) of 230 V SW suitable for RTCC panel of said T/F including the cost of all material which will be provided by contractor on their own cost & risk. | 10 | Job | - | - | - |
| 1.09 | Complete repairing and complete overhauling by copper coil of winding of 3HP, 230Volt, 1500 RPM, 50 Hz cooling fans of 40&20MVA T/F installed at 132 kV S/S Bharwari, Kaushambi. This job includes disconnection of supply cable and dismantling from fan mounting frame then shifting the fan to workshop and rewinding the defective motor winding by suitable size & good quality super enamelled cupper wire, straightening of motor shaft and replacement of damaged bearing. Replacement of wom-out parts. Checking of adjustment of all Gaps, Shifting of motor to site, refitting in T/F fan mounting frame, making proper connection and checking the performance of fan up to 2 hrs after connecting proper supply. | 14 | Nos | - | - | - |
Tender Value
₹1.7 L
EMD Value
₹2,000
Closing Date
29 Sept 2025, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer
57 George Town Prayagraj
For overhauling of 132 KV isolators at 132 KV SS Manauri Kaushambi.
2025_UPTCL_1075916_1
10-ETD-IV(P)/2025-2026
Open Tender
Electrical Works
Item Rate
60 days
Kaushambi
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Executive Engineer ETD IV Prayagraj
₹2,000
13 Oct 2025
20 Sept 2025
29 Sept 2025
20 Sept 2025
29 Sept 2025
20 Sept 2025
Amount
Following works to be carried out at 132 KV S/S Manauri, Kaushambi
Complete overhauling of manually operated 132 KV isolators, by opening of its 06 Nos stacks, replacement of defective bearing of same size and repairing of housing if required cleaning of isolator stack by special liquid detergent, filling of high-quality grease. Tightening of all nut & bolts, opening of male/female contact its cleaning and refitting with proper alignment. Application of white petroleum jelly on contact & fingers, oiling and greasing of all movable parts checking of alignment for smooth and reliable operation ensuring all safety precaution, all consumable shall be arranged by contractor, materials and skilled & un skilled manpower required satisfactorily completion of above work. Bay wise detail of isolators given below: (1). 132 KV Cantt. Bay1 LI,2 BI-03 Nos. (2) 132 KV Sirathu Bay - 1 LI.2 BI-03 Nos. (3) 63 MVA Transformer I/ and II Bay (H.V. side) 2 LI. 4 BI-06 Nos. (4) 132 KV T.B.C. Bay-2 BI- 02 Nos.
Replacement of defective 02 no, 415 volt. 16 A, 4NO+2NC power contactor for main supply of cooling fans installed on 20 MVA T/F work includes proper connection of contactor with ACDB or AC cubical installed in the switchyard including the cost of all material which will be provided by contractor on their own cost & risk.
Replacement of defective 04 no fan control contactors of rating 230V, 9A, 08 NO, for auto function of cooling fans and 03 no relays of rating 230 V, 9A, 02NO+02 NC for supply monitoring for cooling fans including the cost of all material which will be provided by contractor on their own cost & risk.
Replacement of defective 05 no overload relay of rating (0.5-1A) for cooling fan of transformer on the front side of the marshalling box including the cost of all material which will be provided by contractor on their own cost & risk.
Replacement of defective 05 No 3pole MCB having 230V, 2A on tubular rail fence inside marshalling box including the cost of all material which will be provided by contractor on their own cost & risk.
Supply and fixing of 08 no fan control switches for on/off control of fans (ON/OFF) of ratings 415 V 10A of standard make including the cost of all material which will be provided by contractor on their own cost & risk.
Supply and fixing of 10 no tap position indicator of push off type with the rating 230 V. 2A, and 01 no panel lanip (LED) of 230 V SW suitable for RTCC panel of said T/F including the cost of all material which will be provided by contractor on their own cost & risk.
Complete repairing and complete overhauling by copper coil of winding of 3HP, 230Volt, 1500 RPM, 50 Hz cooling fans of 40&20MVA T/F installed at 132 kV S/S Bharwari, Kaushambi. This job includes disconnection of supply cable and dismantling from fan mounting frame then shifting the fan to workshop and rewinding the defective motor winding by suitable size & good quality super enamelled cupper wire, straightening of motor shaft and replacement of damaged bearing. Replacement of wom-out parts. Checking of adjustment of all Gaps, Shifting of motor to site, refitting in T/F fan mounting frame, making proper connection and checking the performance of fan up to 2 hrs after connecting proper supply.
alfa engineering (BID ID -5571699)
B.R. ENTERPRISES (BID ID -5570567)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .