Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 1 SHAKTI NAGAR JAMMU JAMMU KASHMIR 180001 | JAMMU | JAMMU AND KASHMIR | 180001 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Rejected-Technical | Rejected-Technical DUE TO SHORTFALL OF REQUISTE DOCUMENTS |
Tender Value
Refer Docs
EMD Value
₹64,000
Closing Date
27 May 2025, 4:00 pmClosed
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
Supply, installation, testing and commissioning of Fire Alarm System and Portable Fire extinguishers along with other allied works at Additional Accommodation at Guest House, Canal Road Jammu.
2025_PWDJK_276970_2
MHDJ/e-NIT 42 of 2025-26
Open Tender
Machineries/ Mechanical Engg Items
Turn-key
90 days
convention hall jammu
AS PER E NIT
2 documents required · 2 mandatory
₹1,000
XEN MECHANICAL AND HOSPITAL DIVISION JAMMU
₹64,000
8 Jul 2025
21 May 2025
28 May 2025
21 May 2025
27 May 2025
22 May 2025
21 May 2025 - 27 May 2025
Amount
Supply, installation, testing and commissioning of single Loop Analogue Addressable Fire Alarm Control Panel, with single loop driver card, loop current 500 mA maximum per loop, dual flash based microprocessor, supports to connect 240 addressable devices one each loop via fully digital communication protocol equipped with a white backlit display (240x64 pixel resolution) graphical LCD Display with at least 6 lines of information,, 200 fire zones (soft zones), fully programmable via alphanumeric keypad or configuration software, dedicated USB and RS-22 serial port for direct or PC connection. 5500 events storage, loop current 500 mA, panel shall be equipped with in built multi-meter for live monitoring of loop current, earth voltage, loop voltage etc., installer's logo application, can be networked to compatible addressable panels and repeater panels by adding a network card, features battery charger status and temperature, supports programmable cause / effect of outputs, panel housing meets IP30 ingress protection classification
Supply, installation, testing and commissioning of Wi eless intelligent Photo Electric (Optical) Smoke Detector with advanced dual path optical chamber design, optimised performance utilising internal algorithm, programmable three sensitivity levels/settings (High, Normal, and Low), 7 operating frequency channels for bi-directional wireless communication with compatible translator/expande: module, operating wireless frequency 865MHz, maximum radiated power 14 dBm (25mW), communication range of max 200 meter in open space, two tri colour (Red/Ainber/Green) LED's provided for functional and battery level status indication, support magnet test or aerosol based tester, dual trap/filter to prevent entry if insects and dust particles, provided with dual lithium batteries (primary and secondary power source) Approved by LPCB for EN 54-7 and EN 54-25 standard.
Supply, installation, testing and commissioning of V'ireless Multi-Criteria (Optical-Thermal) Detector with advanced dual path optical ch. mber design and heat/thermal sensor for improved performance and elimination of ruisance alarms, thermal sensor alarm temperature of 58°C (Class A1R ROR), programmable three sensitivity levels/settings (High, Normal, and Low) for smoke sen: or and two sensitivity level for thermal sensor, 7 operating frequency channel for bi-directional wireless communication with compatible translator/expande module, operating wireless frequency 865MHz, maximum radiated power 14 dBm (25mW), communication range of max. 200 meter in open space, two tri-colour (Red/Ainber/Green) LED's provided for functional and battery level status indication, support magnet test or aerosol based tester, dual trap/filter to prevent entry if insects and dust particles, provided with dual lithium batteries (primary and secondary power source) Approved by LPCB EN 54-5, EN 54-7, EN 54-29, and EN 54-25 standard
Supply, installation, testing and commissioning of Wireless Heat (Thermal) Detector with heat/thermal sensor for optimised performance utilising internal algorithm, thermal sensor alarm temperature of 580C (Class Allt ROR) or 780C (Class BS High Temperature), programmable multiple sensitivity level, 7 operating frequency channels for bi-directional wireless communication with compatil le translator/expander module, operating wireless frequency 865MHz, maximum rad ated power 14 dBm (25mW), communication range of max. 200 meter In open space, two tricolor (Red/Amber/Green) LED's provided for functional and battery level status indication, support magnet test or aerosol based tester, dual trap, filter to prevent entry if insects and dust particles, provided with dual lithium batteries (primary and secondary power source). Approved by LPCB EN 54-5, and EN 54-25 standard
Supply, installation, testing and commissioning of Wireless Sounder interface Module allows to connect conventional Sounder or Sounder f eacon to addressable loop via translator/expander module, 7 operating frequency channels for bidirectional wireless communication with compatible translator/ expandir module, operating wireless frequency 865MHz, maximum radiated power 5 dim (mW), communication range of max. 150 meter in open space, provided with dual sthium batteries (primary and secondary power source)
Supply, installation, testing and commissioning of Wireless intelligent resettable type Manual Call Point, 7 operating frequency channels for bidirectional wireless communication with compatible translator/expande module, operating wireless frequency 865MHz. maximum radiated power dam (mW), communication range of max. 150 meter in open space. Approved by LPCB IN 54 11 and IN 54.2 standard
Supply, installation, testing and commissioning of Translator module, shall allow addressable loop communication to 32 wireless field levices, system devices can be configured through translator module or software, hop powered, two orthogonal antennas for safe and reliable wireless communica ion, shall have high wireless. transmission range with wireless field devices of max. 150 meter in open space, maximum radiated power 5dBm (3mW), enabled with operating frequency channels for bi-directional wireless communication, operating frequency range 865MHz, IP 65 rated. Approved by LPCB for EN 54-18 and EN 54-25 standard.
Supply, installation, testing and commissioning of 'Wireless Expander module to enhance/boost wireless communication range of the Translator module, enables communication between 32 wireless field devices and translator module, system devices can be configured through translator module or software, powered through auxiliary power supply, two orthogonal antennas for safe and reliable wireless communication, shall have high wireless transmission range with wireless field devices of max. 150 meter in open space, maximum radiated po wer 5dBm (3mW), enabled with 7 operating frequency channels for bidirectional wir less communication, operating frequency range 865MHz, IP 65 rated. Approved by LI CB for EN 54-18 and EN 54-25 standard
Supply, installation, testing and commissioning of 24V DC 3A Switching mode power supply
Mounting Accessories like back box for detectors, gas detector, devices & cable glands, etc
Supply, installation, testing and commissioning of 20 x 1.5 Sq.mm PVC insulated copper conductor armoured cable
Supply, installation, testing and commissioning of wall mounted automatic Fire extinguisher using two heat sensing quartzoid bulb with valves for detection & extinguishing of fires, Wall Mounted Automatic Fire Extinguisher Powder Based (as per IS 4308) Automatic, Mild Steel, Hose Length 500 millimeter, Quartzoid bulbs No temperature rating 68 degree Celsius, Pressure Testing PED Certificate/ CE Marking to PED 2014/68/EU, Annexure 3 (Module H) from EU Notified Body. Capacity 6 KG ABC Automatic Wall Mounted Fire extinguisher.04
Supply, installation, testing and commissioning of store I Pressure Water Mist Based Bs En Standard Based Portable Fire Extinguishers, Confor nity to Standard EN 3-7 + A1: 2007 & EN 3-8,2006 with latest amendment, Weight of Filled Portable Fire Extinguisher (kg) 10.438, Suitable for Class -A fire ratings as per EN 3-7 13A, Fire Rating for Class -F 75F, Operating Temperature (-30°C ≤ N >= 60°C), Warranty for the Complete Product 5 year, Operating Temperature (+5°C to + 60°C), Service Pressure 15 bar, Burst Pressure 112 bar, Minimum Discharge Time (seconds) required as per EN Standard 12 second, Shelf Life (Life Cycle) of the Fire Extinguisher 10 Years, Marine Equipment Directive (MED) Approved CE Certification from EU Notified Borry, CE Identification Number of the Notified Body (Must Declare), CE 1128, Availability of Test Report from Central Govt./NABL/ILAC accredited lab to prove conformity 15 specification Test Report No 1329b, Issue:04, Test Report Date 20.07.2018 Name of the Lab BRE Global Ltd. Stored Pressure Water Mist Based Fire Extinguishers 6 litre Capacity.
Supply, installation, testing and commissioning of Higi Pressure Water Mist & CAFS, Capacity 50 Ltrs. trolley, (As per EN 1866 1:2007-08) working Pressure 31 Bar, Air Bottle Capacity 6 Litre 300 Bar Pressure, Approved By PESO (Petroleum and explosive safety organization), Fire extinction suitability with standard AFFF 6% confirming to 15 4989 or UL 162 standards Class - A Fires, Class-B Fires, Class-B Polar Solvent Fires, Live Electrical fires - 1000 V as per EN 3-7:2004+A1:200/ Tested for 35 kV, Certification from NABL accredited Lab and any Central Govt. Lab. (tusted in Indian condition) as per EN 1866-1:2007-08. Test report shall be enclosed along with the offer, The product should be PED certified to PED 2014/68/EU, ANNEX III (MODULE H). The supplier should have a license from PESO for refilling & storage of higli pressure gas cylinders. Water Mist & CAF High Pressure 50 Ltrs. Trolley.
M/S NISHAT FIRE AND SAFETY SYSTEMS (BID ID -2374549)
Bee Kay Protection Systems (BID ID -2375654)
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .