Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical | Admitted-Fee/PreQual/Technical |
Tender Value
₹26.3 L
EMD Value
₹53,000
Closing Date
18 Sept 2026, 5:00 pmClosed
SM_TENDER CELL
GNIDA OFFICE
Providing Street Light on 45 Meter wide road infront of 220 KV Sub-Station Jalpura, Greater Noida.
2026_GNIDA_1183367_13
SM/(E-TENDER CELL)/2026/808 DATED-03.09.2026
Open Tender
Electrical Works
Percentage
180 days
GREATER NOIDA
REFER TENDER DOCUMENT
5 documents required · 5 mandatory
₹860
₹53,000
21 Sept 2026
8 Sept 2026
21 Sept 2026
8 Sept 2026
18 Sept 2026
8 Sept 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | BOQ | - | - | - | - |
| 1.02 | Supply & fixing of 9 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 155 mm and base plate 12mm thik) having 3mm thikness with Double arm bracket (1 Mtr length each) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect.
UPPWD 2018 / Sl. No. 646 | 35 | Nos | 21,430 | ₹7,50,050 |
| 2 | Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness with single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, excavation & back filling and Required T&P completee in all respect.
UPPWD 2018 / Sl. No. 641 | 16 | Nos | 16,500 | ₹2,64,000 |
| 3Supplying, installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 VoItAC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4- 5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.20.95, IP- 66,IK-10, CRI >80 , under voltage and over voltage protection,EMI- EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , | |||||
| 3.01 | SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 Im/Watt output ..LM79 &LM80 Testreport from NABL lab for all testing required for LED fixtures as perBIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
DSR (E&M )-2025/ Pg. No. 8.14 | - | - | - | - |
| 3.02 | 120 Watt | 16 | Nos. | 3,512 | ₹56,192 |
| 3.03 | 200 Watt | 70 | Nos. | 5,305 | ₹3,71,350 |
| 4Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. UPPWD 2018 / Sl. No. 501 | |||||
| 4.01 | 16 sq. mm 4 core (i) | 1,785 | Mtr. | 343 | ₹6,12,255 |
| 4.02 | 50 sq. mm 3-1/2 core (L) | 400 | Mtr. | 492 | ₹1,96,800 |
stage.html
html • 0.01 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 5.74 MB
PreQ_Prov_Stre_Ligh_45m_Road_220KV_Station_Jalpura.pdf
Tender Documents • 1.77 MB
BOQ_2225624.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .