Executive Engineer STD Ganderbal
Office of Executive Engineer STD Ganderbal
Replacement of 33kV Trivector meter CT PT operated of 33/0.443 kV 400kVA Transformer installed at Sainik School Manasbal in respect of STD Ganderbal
2023_PDD_227622_1
STD/GBL/20 of 2023-24 dated 25-08-2023
Open Tender
Entertainment/Musical Instruments
Turn-key
30 days
Manasbal Ganderbal
Please refer Tender documents.
10 documents required · 10 mandatory
₹200
Yes
Office of Executive Engineer STD Ganderbal
₹4,220
Yes
27 Sept 2023
25 Aug 2023
22 Sept 2023
25 Aug 2023
21 Sept 2023
28 Aug 2023
26 Aug 2023 - 5 Sept 2023
Amount
SITCof 33kV Trivector meter CT PT operated of 33/0.443 kV 400kVA Transformer installed at Sainik School Manasbal in respect of STD Ganderbal (the job includes the dismantling of old damaged unit as well).
SITC of 33kV CT/PT Combined Unit, 3-phase, 50 Hz, ONAN cooled, outdoor type. The combined unit, CTs and PTs shall be as per below specifications. The CT ratio shall be as under: I. 20/5 for 400kVA, 33/0.433 kV Transformer. 2. The rated burden of CT shall be 7VA, The PT shall be 33 kv/110 volts / √3, Three phase PT with rated burden 20VA per phase with proper colour coded identification. PTs shall be of uniform insulating and One minute power frequency dry withstand voltage 70KV
Providing & fixing of Metering cubicle for 3phase 4 wire metering system suitable for 3 phase, HT, tri-vector meter with sealing and locking facility made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The panel shall be provided with two No MS channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening door. Including supply and fixing of 75mm GI pipe between CT/PT combined unit and metering cubicle for CT/PT wiring to tri-vector meter
Providing & fixing of MS Channels for mounting CT PT Combined Units with nuts and bolts (size 100 x 50 x 5 mm)
SITC of 3Ph4 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS232 port . 33kV/√3 /110V/√3, Ph-N (3P, 4W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. (make L&T, Secure or ABB)
Providing & fixing of PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm² (RYB) and for PT wiring minimum wire size shall be 2.5 mm² (RYB)
Providing & fixing of Copper Lugs preferably ring type duly crimped for termination of wires and tapes
Providing and Fixing of ACSR Jumpers with hardware fittings like ACSR to CT/PT unit bush clamp, other hardwares as per site requirement
Providing & fixing of Earthing 40 mm GI Pipe or 20 mm GI rod, 2.5 mtr for CT/PT combination unit. Earthing of metering cubicle through two No 25 x 5 mm flat iron
J.B.M ELECTRICALS
M/S SALIQ TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .