Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.5 LAccepted-AOC | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹28.0 L+₹4.5 L (18.9%)Rejected-Finance B 56 LANE NO 4A SECTOR 7 VASHNAVI ENCLAVE CHANNI HIMAT JAMMU 180015 | JAMMU | JAMMU AND KASHMIR | 180015 | L2 | Rejected-Finance BEING L2 | |
| 3 | L3₹33.8 L+₹10.3 L (43.6%)Rejected-Finance 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | L3 | Rejected-Finance BEING L3 | |
| 4 | L4₹34.8 L+₹11.3 L (48.0%)Rejected-Finance | L4 | Rejected-Finance BEING L4 | |
| 5 | L5₹38.0 L+₹14.4 L (61.3%)Rejected-Finance R O WARD NO 08 H NO 108 DHAR ROAD UDHAMPUR TEHSIL DISTT UDHAMPUR 182101 | UDHAMPUR | UDHAMPUR | JAMMU KASHMIR | 182101 | L5 | Rejected-Finance BEING L5 |
| Sl No | Description | Qty | Unit | slathia construction works L5 | shivom builders L4 | MOHAN LAL AND SONS L3 | ANIKET TRADERS L2 | PROACH ASSOCIATES BUILDERS & ENGINEERS L7 | PAWAN KUMAR GOVT. CONTRACTORS L1 | ASIA BUILDER L6 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | M&L Checking of Earth Resistance of Chemical/conventional Earthing and maintaining the Register as per Note Points mentioned below:
NOTE :-
(a) Contractor will Check Earth Resistance of test points and will be maintained in Register, same will be put up to the Engineer-in-Charge through JE E/M.
(b) New Earth Resistance Tester for testing will be provided by the Contractor.
(c) Contractor will be responsible for cleaning of bushes, grass, sand etc inside and all around upto 0.50 Metre Area of existing Earth Pit with tightening of Strip.
(d) Cost of register for noting earthing results, location wise shall deemed to be included with the unit rate. Proforma of detail column will be printed as per the direction of Engineer-in-charge.
(e) The contractor is responsible for maintaining the value of chemical / conventional earthing as per station norms as directred by Engr-in-Charge.
(f) Recovery for Penalty will be made as follows :-
(i) Earthing left without Checked lesser by 25 No. - Rs. 60.00/Earthing
(ii) Earthing left without Checked in a Month - Rs. 150.00/Earthing
(iii) Earthing left without Cleaning in a Month - Rs. 50.00/Earthing
(iv) Earthing left without Watering in a Month - Rs. 30.00/Earthing | 6,000 | EACH EARTH PIT | 50 ₹3,00,000 | 20 ₹1,20,000 | 100 ₹6,00,000 | 20 ₹1,20,000 | 200 ₹12,00,000 | 5 ₹30,000 Lowest | 80 ₹4,80,000 |
| 2.00 | M&L for supply and pouring of RoHS tested Earth Enhancement Compound after mixing with water with a resistivity < 0.12 ohm-m. It shall be free from bentonite and other hazardous substances. It shall be a permanent, non-corrosive material and will not leach any chemicals into the ground. It shall retain moisture even in high soil resistivity areas. complete all as specified and as directed.
Note: Measurement of Chemical will be done in Powder form. | 5,000 | KG | 30 ₹1,50,000 | 40 ₹2,00,000 | 19 ₹95,000 | 45 ₹2,25,000 | 12 ₹60,000 | 10 ₹50,000 Lowest | 80 ₹4,00,000 |
| 3.00 | supply and fixing in repair of Earth Pit 125 mm dia with FRP Earth Pit Cover of top size 200x200mm bottom size 300x300mm with height of 150mm with lockable Lid, Earth Pit cover shall be made of Poly plastic for closing of earth pits complete all as specified and as directed. | 250 | EACH | 250 ₹62,500 | 350 ₹87,500 | 300 ₹75,000 | 300 ₹75,000 | 400 ₹1,00,000 | 250 ₹62,500 | 150 ₹37,500 Lowest |
| 4.00 | Labour only for repairing of existing earthing pit at Airforce Area by replacement of existing earth plate of any size including necessary excavation at a depth not less than 3.5 below ground level and improve it by adding a Alternative layer of salt and charcoal for reducing soil resistivity and enhancing moisture content in Soil all as specified and directed by Engr-in Charge.
Note:- (a) Copper/GI Plate shall be measured and paid separately.
(b) Salt should be paid separetely in respective item in schedule.
(c) Charcoal should be paid separetely in respective item in schedule. | 40 | Each set | 500 ₹20,000 Lowest | 750 ₹30,000 | 800 ₹32,000 | 800 ₹32,000 | 700 ₹28,000 | 500 ₹20,000 Lowest | 1,200 ₹48,000 |
| 5.00 | Supply only Copper plate of size 60 cm x 60 cm x 3.15 mm complete all as specified and directed by Engr-in-Charge. | 20 | Each | 11,000 ₹2,20,000 | 3,500 ₹70,000 | 8,000 ₹1,60,000 | 5,000 ₹1,00,000 | 8,000 ₹1,60,000 | 7,500 ₹1,50,000 | 2,000 ₹40,000 Lowest |
| 6.00 | Supply only GI plate of size 60 cm x 60 cm x 6.00 mm complete all as specified and directed by Engr-in-Charge. | 15 | Each | 1,200 ₹18,000 | 1,800 ₹27,000 | 2,100 ₹31,500 | 1,100 ₹16,500 Lowest | 1,400 ₹21,000 | 2,200 ₹33,000 | 2,000 ₹30,000 |
| 7.00 | Supply Common salt commercial for the earth pit all as specified and directed by Engr-in-Charge. | 17.5 | Qtl | 500 ₹8,750 | 230 ₹4,025 Lowest | 800 ₹14,000 | 1,200 ₹21,000 | 600 ₹10,500 | 1,200 ₹21,000 | 2,500 ₹43,750 |
| 8.00 | Supply Charcoal dust for the earth pit all as specified and directed by Engr-in-Charge. | 17.5 | Qtl | 900 ₹15,750 | 1,800 ₹31,500 | 800 ₹14,000 Lowest | 1,500 ₹26,250 | 1,200 ₹21,000 | 1,200 ₹21,000 | 2,000 ₹35,000 |
| 9.00 | M&L Earthing complete as per electrical plate No 5 of MES SSR Part I with galvanised steel plate earth electrode 60 cm x 60 cm x 6.0 mm, burried directly vertically in ground in a pit of depth not less than 2.5 metres below ground level with the top edge of earth plate at a depth not less than 1.5 m below normal ground level connected to and including galvanised iron or steel earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing strip protected by galvanised iron or steel pipe 50 mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20mm bore GI medium grade. The earthing shall be inclusive of excavation and earth work in any type of soil, charcoal, salt, funnel complete all as specified & directed by Engr-in-Charge.Note 1- following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal, dust, common salt and ground enhacement material as required to bring the earthing resistance as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (h) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering.
Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. | 35 | EACH SET | 2,500 ₹87,500 | 2,400 ₹84,000 Lowest | 4,000 ₹1,40,000 | 3,000 ₹1,05,000 | 4,500 ₹1,57,500 | 3,300 ₹1,15,500 | 12,000 ₹4,20,000 |
| 10.00 | All as per item No 9 but GI strip of size 25x4 mm | 25 | EACH SET | 3,000 ₹75,000 | 300 ₹7,500 | 3,500 ₹87,500 | 2,700 ₹67,500 | 4,900 ₹1,22,500 | 100 ₹2,500 Lowest | 12,000 ₹3,00,000 |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
8 Sept 2025, 6:00 pmClosed
GE AF UDHAMPUR
GE AF STATION UDHAMPUR
REPAIR/ MAINTENANCE/ REPLACEMENT OF CONVENTIONAL/ CHEMICAL/ EARTHIING, LIGHTENING ARRESTER AND CERTAIN WORKS AT AIR FORCE STATION UDHAMPUR
2025_MES_725454_1
GEAFU-43/2025-26
Open Tender
Civil Works
Item Rate
180 days
GE AF STATION UDHAMPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF UDHAMPUR
₹90,000
3 Oct 2025
11 Aug 2025
10 Sept 2025
11 Aug 2025
8 Sept 2025
25 Aug 2025
11 Aug 2025 - 18 Aug 2025
Amount
M&L Checking of Earth Resistance of Chemical/conventional Earthing and maintaining the Register as per Note Points mentioned below: NOTE :- (a) Contractor will Check Earth Resistance of test points and will be maintained in Register, same will be put up to the Engineer-in-Charge through JE E/M. (b) New Earth Resistance Tester for testing will be provided by the Contractor. (c) Contractor will be responsible for cleaning of bushes, grass, sand etc inside and all around upto 0.50 Metre Area of existing Earth Pit with tightening of Strip. (d) Cost of register for noting earthing results, location wise shall deemed to be included with the unit rate. Proforma of detail column will be printed as per the direction of Engineer-in-charge. (e) The contractor is responsible for maintaining the value of chemical / conventional earthing as per station norms as directred by Engr-in-Charge. (f) Recovery for Penalty will be made as follows :- (i) Earthing left without Checked lesser by 25 No. - Rs. 60.00/Earthing (ii) Earthing left without Checked in a Month - Rs. 150.00/Earthing (iii) Earthing left without Cleaning in a Month - Rs. 50.00/Earthing (iv) Earthing left without Watering in a Month - Rs. 30.00/Earthing
M&L for supply and pouring of RoHS tested Earth Enhancement Compound after mixing with water with a resistivity < 0.12 ohm-m. It shall be free from bentonite and other hazardous substances. It shall be a permanent, non-corrosive material and will not leach any chemicals into the ground. It shall retain moisture even in high soil resistivity areas. complete all as specified and as directed. Note: Measurement of Chemical will be done in Powder form.
supply and fixing in repair of Earth Pit 125 mm dia with FRP Earth Pit Cover of top size 200x200mm bottom size 300x300mm with height of 150mm with lockable Lid, Earth Pit cover shall be made of Poly plastic for closing of earth pits complete all as specified and as directed.
Labour only for repairing of existing earthing pit at Airforce Area by replacement of existing earth plate of any size including necessary excavation at a depth not less than 3.5 below ground level and improve it by adding a Alternative layer of salt and charcoal for reducing soil resistivity and enhancing moisture content in Soil all as specified and directed by Engr-in Charge. Note:- (a) Copper/GI Plate shall be measured and paid separately. (b) Salt should be paid separetely in respective item in schedule. (c) Charcoal should be paid separetely in respective item in schedule.
Supply only Copper plate of size 60 cm x 60 cm x 3.15 mm complete all as specified and directed by Engr-in-Charge.
Supply only GI plate of size 60 cm x 60 cm x 6.00 mm complete all as specified and directed by Engr-in-Charge.
Supply Common salt commercial for the earth pit all as specified and directed by Engr-in-Charge.
Supply Charcoal dust for the earth pit all as specified and directed by Engr-in-Charge.
M&L Earthing complete as per electrical plate No 5 of MES SSR Part I with galvanised steel plate earth electrode 60 cm x 60 cm x 6.0 mm, burried directly vertically in ground in a pit of depth not less than 2.5 metres below ground level with the top edge of earth plate at a depth not less than 1.5 m below normal ground level connected to and including galvanised iron or steel earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel. Earthing strip protected by galvanised iron or steel pipe 50 mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20mm bore GI medium grade. The earthing shall be inclusive of excavation and earth work in any type of soil, charcoal, salt, funnel complete all as specified & directed by Engr-in-Charge.Note 1- following items deemed to be included in quoted rate (a) Earth electrode. (b) Main earthing lead from earth electrode to test point and further to equipment to be earthed upto 7.5 metre. (c) Material and labour for connecting earth electrode and earthing lead as specified. (d) Adequate quantity of charcoal, dust, common salt and ground enhacement material as required to bring the earthing resistance as per direction. (e) All labour involved including testing of earth net work. (f) Excavation and earth work or drilling hole for electrode. (g) Funnel with watering pipe, wire mesh and copper lugs etc. as specified. (h) G.I. protection pipe of size ordered specified for protection of earthing lead from mechanical injury or tempering. Note 2 - On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
All as per item No 9 but GI strip of size 25x4 mm
Taking down old unserviceable of earthing system and in replacement of Earthing complete with copper earth plate electrode of size 60cm x 60cm x 3.15mm buried directly in ground vertically at a depth not less than 2.5 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick and packed alternate layer of common salt and charcoal including Copper strip of size 20x3 mm by means of nuts, bolts and check nuts, washers of copper up to main board/test point or as required including necessary excavation and earth work in any type of soil so as to achieve earth resistance below 3 Ohms including excavation of polypit chamber with polyplastic pit cover (cost of polypit chamber with polyplastic pit cover shall be deemed to be included in the rate separated quoted) complete all as specified and as directed by Engineer-in-Charge including dismantling of existing unserviceable earthing. Notes : (a) Copper strip beyond test point shall be measured and paid for separately. (b) Earthing resistance result shall be less than 5 Ω .If the result comes more than 5 Ω the contractor shall carry out the earthing at separate location/site given by the Engr-in-Charge after taking out of earth electrode without any extra cost to the deptt. (c) Test point terminal block shall be measured and paid for separately. (d) The contractor's quoted rates shall be deemed to include for dismantling/taking down of old unserviceable earthing of any type and making good the disturbed surfaces and nothing extra shall be admissible on this account. (e) Any other fittings/fixtures if technically required for achieving desired results (if not included above) shall be provided by the contractor without any extra cost to the Govt. (f) If mother soil is not available then mother soil wil be provided by contractor from outside source without any extra cost to the Govt.
S&F IN repair for maintenance free safe earthing system complete with 01 Number UL 467 approved/ CPRI tested copper bonded ( copper cladded earth rod with 250 microns of copper cladding) earth rod 17.2mm dia. 3000 mm long electrode buried in ground to bore holes 120 mm dia. vertically to a depth not less than 3.50 Mtr deep below ground level with top edge of earth electrode at a depth not less than 500 mm below normal ground level inter connection with copper earth lead strip 20 x 3.15 mm and further connected to test point terminal block all as directed. Each earth pit shall include minimum 50 Kg (two bags of 25 Kg each) NABL Lab Certified back fill compound for filling bore holes with mother soil mixed in 1:3 ratio (one part of back fill compound and three parts of mother soil), so as to achieve earth resistance below 1 Ohm including excavation of polypit chamber with polyplastic pit cover (cost of polypit chamber with polyplastic pit cover shall be deemed to be included in the rate separated quoted) complete all as specified and as directed by Engineer-in-Charge. Notes :(a) Copper strip beyond test point shall be measured and paid separately. (b) Earthing resistance result shall be less than 1 Ω .If the result comes more than 1 Ω, then earthing will be redone at no extra cost to govt (c) Pouring of chemical in earth pit shall be measured and paid separately.
M & L in repair for cement concrete 1:2:4 (20 mm graded stone aggretage) provided around PCC Earthing Pit Chamber of platrform 450 x 450 x 100 mm with fair finished concrete surfaces including necessary formwork and earth work as required/ordered at site, complete all as specified and as directed.
M&L Taking out loose/displaced Serviceable Aluminium Strip/ Copper Strip/ GI Strip of any size and any description with Accessories and refixing the same with necessary Fixing Arrangement like Screws, Saddles,clamps, Nuts and Bolts, complete all as specified and as directed.
M&L for replacement of Galvanised Iron Strip 32x6mm with Saddles and fixing Screws for Roof/Earth Conductors and Down Conductors, complete all as specified and as directed.
M&L for replacement of Aluminium Strip 25x3.15mm with Saddles and fixing Screws for Roof/ Earth Conductors and Down Conductors above Ground, complete all as specified and as directed.
M&L for replacement of Copper Strip 20x3.15mm with Saddles and fixing Screws for Roof/ Earth Conductors and Down Conductors above Ground, complete all as specified and as directed.
M & L for replacement of Copper strip 32 x 6 mm with saddles and fixing screws etc for Roof/Earth Conductors and Down Conductors above ground to interconnect the earth pit to equipment room, all as specified and directed.complete with saddles and fixing screws for fitting the strip.
M&L for replacement of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire, complete all as specified and as directed.
M&L for replacement of Galvanised Iron Tubing/Pipe 15 mm bore (dia), light grade watering pipe for pouring of water in earth pit complete all as specified and as directed.
M&L for replacement of Galvanised Iron Tubing/Pipe 25 mm bore (dia), light grade for wire Protection, earthing strip protection, ixed in Walls/Floors with suitable type of Clamps, earthing pipe etc., complete all as specified and as directed.
M&L for replacement of Galvanised Iron Tubing/Pipe 40mm bore (dia), light grade for Strip Protection, fixed in Walls/Floors with suitable type of Clamps, earthing pipe etc., complete all as specified and as directed.
M&L for replacement of Test Point Terminal Block made of Gun Metal or Phosphorus Bronze size 75x75x25mm, drilled and screwed including 3 No. 8mm dia, 25mm long hexagonal Head Screw, complete all as per specified and as directed.
M&L for replacement of Air Termination Single Pointed Aluminium Rod 12 mm dia and 300mm long with Galvanised Steel Tubing 40mm bore (dia), 1.50 Metre long, light grade with all Fittings with Arrester Clamp 12 mm made out of Brass including provision of Cement Concrete 1:2:4 (20mm graded stone aggregate) Block 300x300x300mm, complete all as specified and as directed.
M&L for replacement of Air Termination Single Pointed Copper Rod 12 mm dia and 300mm long with Galvanised Steel Tubing 40mm bore (dia), 1.50 Metre long, light grade with all Fittings with Arrester Clamp 12 mm made out of Brass including provision of Cement Concrete 1:2:4 (20mm graded stone aggregate) Block 300x300x300mm, complete all as specified and as directed.
Supply and fixing in repair of Earthing identifier marker of 25mm flat iron 5 mm thick length of flat iron 75 cm long which is 60 cm FI above the Ground level and 15 cm length FI below the Ground level and fixed with PCC 1:2:4 (12.5 mm graded aggregate) in post holes and the TOP of the flat iron parabolic/semicirculer/traingular/rectangular shape MS plate 1.6 mm thick of size 30 cm width and 20 cm height to welded/fixing to the flat iron including two coat of synthetic enamel paint over a coat of primer on steel surface cutting for Equipment Earthing/Lighting Earthing/L2 Earthing etc complete all including Earth Plate No/Description of Earthing/Type of Earthing on Plate with white paint including earth plate no and earthing resistance with earthing check date and earthing check due date complete all specified and directed by Engineer in charge.
S&F In repair of multi pointed copper rod,19/20mm dia and 500mm long with base plate of size 100 x 100 x 5mm fixed on top of roof of the building including drilling holes on copper strip and GI Pipe as required for making system for attaching complete all as specified and as directed by Engineer-in-Charge on buildings having height upto 6 mtr. Note:-The rates quoted shall be deemed to include for scaffolding, saftey measures and insurance of workmen etc. and nothing extra shall be admissible on this account.
S&F in repair of heavy duty porcelain/poly carbonate insulators of size 32 x 32 mm to be fixed on wall/roof/pipe for laying of copper strip as roof/down conductor on building of height between upto 25 metres including nuts & bolts of brass of appropriate size all as specified and as directed by Engr-in-Charge including taking down old unserviceable.
Taking down old unserviceable flexible pipe and M&L for flexible pipe of size 40 mm complete all as per specified and directed.
S&F in repair CI funnel for watering in earth pit with GI pipe including welding or threading etc complete all as specified and as diirected.
Supply and fixing in repair of THOR safe lightening Protection Rod, with side flash capture head (SLPH), ICMET certified confirming to NFC 17-102, CPRI certified for 40KA which is a free standing mast of appx 4.5 mtr height made of stainless steel, free standing OD 77mm, thickness 3.2 mm, base plate hole M16 12 Nos, to with stand wind speed of 180 KM/Hr and mast coupler, accessory box with in-built bus bar insulator and base plate for fixing on foundation using stainless steel nuts and bolts. The contractor shall provide down conductor of 70 sqmm copper cable properly thimbled with copper lugs on both sides from mast to earthing test point including dismantling the existing unserviceable. Note: Down conductor shall be measured and paid for seprately under relevant item of BOQ.
M&L in repair for ALICE Digital ( Lightening impulse counter Electromechanical) for counting surge impulse all as specified and as directed by Engr-in-Charge.
M&L in repair for Down conductor using 25 sqmm single core copper cable both ends thimbled properly with copper Lugs complete all as specified and directed.including taking down old.
M&L in reapir for Down conductor using 16 sqmm single core copper cable both ends thimbled properly with copper Lugs complete all as specified and directed.including taking down old.
Material and labour for brazing of earthing copper strips at various locations of size 20mm to 50mm width of thickness 3mm to 6mm by using oxygen and acelylene gas cylinder with copper rod material including removing of existing nut, bolt and insulator and refixng after brazing complete all as specified and directed Note: 1. Any damage of building portion during working time will be repaired and made good deemed included in quated rate of item. 2. Contractor shall be responsible to replace old warnout nut bolt and insulators with new material. cost of matrial also deemed included in quoated.
Material and labour for welding / brazing of earthing Al / GI strips at various locations of size 25mm to 50mm width of thickness 3mm / 5mm / 6 mm by using welding rod material including removing of existing nut, bolt and insulator and refixng after brazing complete all as specified and directed. Note :- 1. Any damage of building portion during working time will be repaired and made good deemed included in quoated rate of item.
S & F in repair white polished PVC Plastic water Tap of size 15 mm light weight , wear resistant , non deforming for pouring of water in watering pipe complete all as specified and directed.
S & F 40 mm bore HDPE pipe for protection of earthing strip including fixing on wall or laying in ground complete all as specified & directed.
Taking down old unsv earthing and M&L for earthing complete with pipe in pipe copper electrode, zinc coated, 80-100 micron at out electrode, and including filling of highly conductive and anti-corrosive mixture at a depth of minimum 3.3m and as per IS 3043: 1987 including copper strip 20 x 3.15mm connection by means of nuts, bolts and washers and excavation, returning filling as required. (a) Earthing strip protected by galvanized iron or steel pipe 50 mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be inclusive of excavation and earth work in any type of back fill compound, funnel complete all as specified and directed by Engineer-in- Charge. Note: - (a) Earth strip beyond test point shall be measured and paid separatedly. (b) Earthing resistance result shall be less than 1 Amp. If the result more than 1 Amp then earthing will be redone at no extra cost to Govt. (c) Pouring of chemical in earth pit shall be measured and paid separately.
ANIKET TRADERS (BID ID -3412220)
MOHAN LAL AND SONS (BID ID -3418870)
shivom builders (BID ID -3412994)
slathia construction works (BID ID -3412858)
ASIA BUILDER (BID ID -3411963)
PROACH ASSOCIATES BUILDERS & ENGINEERS (BID ID -3418895)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .