Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.5 LAccepted-AOC GURDASPUR ROAD NEAR SAINIK MANDIR PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹31.5 L+₹1.0 L (3.33%)Rejected-Finance HYDERPORA NEAR ELLAQUAI DEHATI BANK SRINAGAR KASHMIR J K 190014 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190014 | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹31.7 L+₹1.2 L (4.07%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 4 | L4₹32.9 L+₹2.4 L (7.89%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 5 | L5₹32.9 L+₹2.4 L (7.92%)Rejected-Finance SHIVAJI NAGAR GALI NO 1 DHANGU ROAD MODEL TOWN PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L5 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | Pyramid constructions L7 | KEWAL SONS L5 | SAINI AND SAINI BUILDERS L1 | ANIKET TRADERS L6 | M/S JIWAN SINGH L3 | FANGALIA TRADERS L8 | Continental Enterprises L4 | M/S ZAHOOR AHMAD KHAN L2 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supply,install ,testing, commissioning of 'Silent type' with continuous operation diesel generating set outdoor type alongwith having prime power rating of 200 KVA/160 kW at NTP, 415 Volt, 75 db noise level at 1 mtr distance from DG Set with suitable Engine to develope 200 KVA, AC 415 Volt at 1500RPM , 0.8 lagging power factor at 415 volts suitable for 50 hz 3 phase system and ,confirming to CPCB-IV norms / latest CPCB emission norms , acoustic enclosure,anti vibration mountings, control panel and foundation.The DG set should be robust in construction factory tested and assembled to ensure perfect alignment of Engine and Alternator on a common base frame with same manufacturer. The DG set shall be comprising of following item as under: | 1 | Each | 31,00,000 ₹31,00,000 | 29,98,000 ₹29,98,000 | 27,90,000 ₹27,90,000 | 31,00,000 ₹31,00,000 | 28,52,222 ₹28,52,222 | 29,90,000 ₹29,90,000 | 29,50,000 ₹29,50,000 | 27,78,000 ₹27,78,000 Lowest |
| 1.01(a) Diesel Engine : The diesel engine shall be of four stroke cycle multi-cylinder, direct injection, water cooled, turbo charged, Air to air after cooling and optimised turbocharger for increased altitude capabilities, developing suitable BHP @ 1500 RPM under tropical condition of Jammu of BS 5514/ISO 3046 with an over load capacity of 110% for one hour in any specified 12 hrs of continuous operation. The engine shall confirm to IS:10000/BS:649/BS 5514.The engine shall have the following accessories: - (i) Cooling fan and radiator. (ii) DM water cooling systems with pre-mix anti-corrosive additive. (iii) Turbocharger. (iv) Fly wheel with fly wheel housing. (v) Electrical engine starter motor (disengagement after start-up) with Batteries. (vi) Battery charging systems. (vii) Stainless steel exhaust flexible elbow. (viii) Thermal sealing of exhaust pipe and aluminium cladding for complete exhaust pipe and silencer. (ix) Required filters for fuel, lube oil, air etc. (x) Sets of flexible hoses as required. (xi) Suitable rubber coupling to Alternator with guard. (xii) Suitable Engine controller for protection of the engine. (xiii) Coolant heater and crankcase heater. (xiv) Oil drain Pump. (xv) Heavy duty air cleaner etc. | |||||||||||
| 1.02(b) Engine protections: (i) High coolant temperature warning & trip (ii) Low lubricating oil pressure warning & trip (iii) Low coolant level warning & trip (iv) Fail to crank trip (v) Over crank trip (vi) High and Low speed trip (vii) Low or High battery voltage alarms. (viii) Clogged filter warning (ix) Lack of fuel (x) High Canopy Temperature (xi) Set fail to start protection after failure of the set to start after successful three consecutive start attempts. | |||||||||||
| 1.03(c) Governor: The governor shall be of electronic type suitable for monitoring constant engine speed within the specified limits for auto parallel and auto load sharing operation. | |||||||||||
| 1.04(d) Exhaust : The exhaust piping system shall be supplied with a hospital grade silencer and catalytic converter suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB-IV compliant.The exhaust piping and the silencer shall be wrapped with rock wool and/or calcium silicate. The outside shall be neatly wrapped with aluminum cladding. The exhaust line shall be extended beyond the height of the utility building roof as required by pollution control norms. Suitable supporting structure for installation shall be provided. | |||||||||||
| 1.05(e) Hot air exhaust (Radiator cooling): As per OEM recommendation if sufficient exhaust for radiator is not available , the contractor has to provide GI duct for hot air exhaust from DG set up to designated place of duct outlet. The duct shall be made of 14 Gauge thick GI Sheet including necessary civil work. | |||||||||||
| 1.06(f) Fuel Tank : Inbuilt/internal bottom mounted (with-in DG set or with-in base frame) diesel tank of suitable capacity with mounting brackets, complete with fuel inlet, out let, air vent, drain plug, level indicator, inter connection pipes from tank to diesel generator as required. Suitable barrier shall be provided between Diesel tank and the Engine. Fuel tank shall be fabricated as per tropical condition of Jammu with approx. capacity or designed capacity shall be suitable for 8 hrs continuous operation or 14 hours capacity at 75% load. In case the inbuilt base frame tank is not capable to hold POL for 8 Hrs continuous operation, contractor shall provide additional tank made up of MS Sheet capacity separately as per manufacturer recommendation. | |||||||||||
| 1.07(g) Starting system :The engine starting shall be by means of totally enclosed axial type electric starter suitable for 12/24 volts DC starting system comprising of starter motor, voltage regulator and arrangement for initial excitation complete with suitable number of batteries as Per OEM Specification ,Sealed Maintenance Free (SMF) Lead-Acid type suitable for Jammu .The battery shall be supplied with a suitable floor mounted MS stand treated with seven tank treatment, two coats of red oxide /primer & acid resistant paint with wooden base, adaptor box etc . with copper conductor battery leads of required length and socket/clamps | |||||||||||
| 1.08(h ) Alternator: (i) 200 KVA 3 phase 0.8 PF 415V, 4 wire 1500 rpm self-excited and self regulated through electronic AVR confirming to IS :4722/BS 2613 suitable for tropical condition with brush less exciter, housed in screen protected drip proof enclosure. The alternator shall be confirming to IS 13364 Part-2 & IS 15999 Part-1/ IEC 60034 Part-1 capable of delivering rated output at rated power factor of 0.8, with a Terminal voltage differing from the rated value by not more than +/- 5%. (ii). Frequency differing from the rated value by not more than +/-0.5%. (iii). Short circuit capacity of 300% for 10 seconds. (iv). Over load capacity of 110% for one hour. The insulation class of the Alternator shall be class F/ H. The temperature rise shall be limited to class B and Ingresses enclosure protection shall IP23 or better. The out put terminals of each Alternator shall be connected to an MCCB of suitable capacity microprocessor based , adjustable type through a cable system. The control Panel shall be housed inside the acoustic enclosure. Make of alternator :- Stamford/Kirloskar electric/Jyoti/Cummins Electric/Crompton Greaves | |||||||||||
| 1.09(j) Alternator Protection: Alternator should have following protections: - (i) Over and Under voltage (ii) Under and Over frequency warning and trip (iii) Loss of excitation (iv) Over current and Earth Fault and Short Circuit Protection (v) Unbalanced loads (vi) Restricted Earth Fault Protection. (vii) Differential protection. (viii) Diode Failure. | |||||||||||
Tender Value
₹34.2 L
EMD Value
₹68,400
Closing Date
19 Nov 2025, 6:00 pmClosed
GE AF Jammu
GE AF Jammu
PROVN OF DG SET AGAINST OLD DG SET AT POWER HOUSE PDDE NC JAMMU UNDER GE AF JAMMU
2025_MES_737371_1
CA NO GE/AFJ-57/2025-26
Open Tender
Civil Works
Item Rate
180 days
JAMMU
Pls refer tender documents
8 documents required · 8 mandatory
₹500
GE AF JAMMU
₹68,400
Yes
12 Jan 2026
29 Oct 2025
25 Nov 2025
29 Oct 2025
19 Nov 2025
12 Nov 2025
Amount
Supply,install ,testing, commissioning of 'Silent type' with continuous operation diesel generating set outdoor type alongwith having prime power rating of 200 KVA/160 kW at NTP, 415 Volt, 75 db noise level at 1 mtr distance from DG Set with suitable Engine to develope 200 KVA, AC 415 Volt at 1500RPM , 0.8 lagging power factor at 415 volts suitable for 50 hz 3 phase system and ,confirming to CPCB-IV norms / latest CPCB emission norms , acoustic enclosure,anti vibration mountings, control panel and foundation.The DG set should be robust in construction factory tested and assembled to ensure perfect alignment of Engine and Alternator on a common base frame with same manufacturer. The DG set shall be comprising of following item as under:
(a) Diesel Engine : The diesel engine shall be of four stroke cycle multi-cylinder, direct injection, water cooled, turbo charged, Air to air after cooling and optimised turbocharger for increased altitude capabilities, developing suitable BHP @ 1500 RPM under tropical condition of Jammu of BS 5514/ISO 3046 with an over load capacity of 110% for one hour in any specified 12 hrs of continuous operation. The engine shall confirm to IS:10000/BS:649/BS 5514.The engine shall have the following accessories: - (i) Cooling fan and radiator. (ii) DM water cooling systems with pre-mix anti-corrosive additive. (iii) Turbocharger. (iv) Fly wheel with fly wheel housing. (v) Electrical engine starter motor (disengagement after start-up) with Batteries. (vi) Battery charging systems. (vii) Stainless steel exhaust flexible elbow. (viii) Thermal sealing of exhaust pipe and aluminium cladding for complete exhaust pipe and silencer. (ix) Required filters for fuel, lube oil, air etc. (x) Sets of flexible hoses as required. (xi) Suitable rubber coupling to Alternator with guard. (xii) Suitable Engine controller for protection of the engine. (xiii) Coolant heater and crankcase heater. (xiv) Oil drain Pump. (xv) Heavy duty air cleaner etc.
(b) Engine protections: (i) High coolant temperature warning & trip (ii) Low lubricating oil pressure warning & trip (iii) Low coolant level warning & trip (iv) Fail to crank trip (v) Over crank trip (vi) High and Low speed trip (vii) Low or High battery voltage alarms. (viii) Clogged filter warning (ix) Lack of fuel (x) High Canopy Temperature (xi) Set fail to start protection after failure of the set to start after successful three consecutive start attempts.
(c) Governor: The governor shall be of electronic type suitable for monitoring constant engine speed within the specified limits for auto parallel and auto load sharing operation.
(d) Exhaust : The exhaust piping system shall be supplied with a hospital grade silencer and catalytic converter suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB-IV compliant.The exhaust piping and the silencer shall be wrapped with rock wool and/or calcium silicate. The outside shall be neatly wrapped with aluminum cladding. The exhaust line shall be extended beyond the height of the utility building roof as required by pollution control norms. Suitable supporting structure for installation shall be provided.
(e) Hot air exhaust (Radiator cooling): As per OEM recommendation if sufficient exhaust for radiator is not available , the contractor has to provide GI duct for hot air exhaust from DG set up to designated place of duct outlet. The duct shall be made of 14 Gauge thick GI Sheet including necessary civil work.
(f) Fuel Tank : Inbuilt/internal bottom mounted (with-in DG set or with-in base frame) diesel tank of suitable capacity with mounting brackets, complete with fuel inlet, out let, air vent, drain plug, level indicator, inter connection pipes from tank to diesel generator as required. Suitable barrier shall be provided between Diesel tank and the Engine. Fuel tank shall be fabricated as per tropical condition of Jammu with approx. capacity or designed capacity shall be suitable for 8 hrs continuous operation or 14 hours capacity at 75% load. In case the inbuilt base frame tank is not capable to hold POL for 8 Hrs continuous operation, contractor shall provide additional tank made up of MS Sheet capacity separately as per manufacturer recommendation.
(g) Starting system :The engine starting shall be by means of totally enclosed axial type electric starter suitable for 12/24 volts DC starting system comprising of starter motor, voltage regulator and arrangement for initial excitation complete with suitable number of batteries as Per OEM Specification ,Sealed Maintenance Free (SMF) Lead-Acid type suitable for Jammu .The battery shall be supplied with a suitable floor mounted MS stand treated with seven tank treatment, two coats of red oxide /primer & acid resistant paint with wooden base, adaptor box etc . with copper conductor battery leads of required length and socket/clamps
(h ) Alternator: (i) 200 KVA 3 phase 0.8 PF 415V, 4 wire 1500 rpm self-excited and self regulated through electronic AVR confirming to IS :4722/BS 2613 suitable for tropical condition with brush less exciter, housed in screen protected drip proof enclosure. The alternator shall be confirming to IS 13364 Part-2 & IS 15999 Part-1/ IEC 60034 Part-1 capable of delivering rated output at rated power factor of 0.8, with a Terminal voltage differing from the rated value by not more than +/- 5%. (ii). Frequency differing from the rated value by not more than +/-0.5%. (iii). Short circuit capacity of 300% for 10 seconds. (iv). Over load capacity of 110% for one hour. The insulation class of the Alternator shall be class F/ H. The temperature rise shall be limited to class B and Ingresses enclosure protection shall IP23 or better. The out put terminals of each Alternator shall be connected to an MCCB of suitable capacity microprocessor based , adjustable type through a cable system. The control Panel shall be housed inside the acoustic enclosure. Make of alternator :- Stamford/Kirloskar electric/Jyoti/Cummins Electric/Crompton Greaves
(j) Alternator Protection: Alternator should have following protections: - (i) Over and Under voltage (ii) Under and Over frequency warning and trip (iii) Loss of excitation (iv) Over current and Earth Fault and Short Circuit Protection (v) Unbalanced loads (vi) Restricted Earth Fault Protection. (vii) Differential protection. (viii) Diode Failure.
(k) Voltage regulator: A rapid response voltage regulator shall be provided to regulate the generated voltage. The overall regulations from no load to full load, including cold to hot variation and load power factor of 0.8 lag to unity shall be within 2% of the normal voltage. The excitation system shall be designed to promote rapid voltage recovery following sudden application and disconnection of load.
(l) Acoustic enclosure : The acoustic enclosure should be supplied along with DG set from the manufacturer outlet itself as per latest CPCB norm. Acoustic enclosure shall be of powder coated and fabricated out CRCA MS sheet. The canopy shall have hinged doors, one door with glass window to view proper parameters on the control panel. The canopy and doors shall have inside lining of fire retardant foam/glass wool as acoustic materials. The base frame shall be fabricated in ISMC channel or in sheet metal, with lifting hooks for convenient lifting of complete set i.e. along with canopy, engine and alternator. The sound level shall have less than 75 db (A) at a distance of 1 meter. High quality noise absorbent and fire-retardant grade acoustic Insulation material (P.U. Foam) complying to IS 8183. The allowable temperature raise inside the canopy is 5 to 7 deg. Centigrade. The Measurement of noise should be as per ISO 3744/ ISO 8528 (Part 10) standard. The canopy has the provision of emergency push button, external to the canopy. Note : The acoustic enclosure shall be made by the OEM of original engine Manufacturer of load.
Note for Item No 1 : (i) Cost of DG set foundation as per OEM recommendation is deemed to be included in cost of item. (ii) Contractor should submit necessary drawing to GE/Engr-in-Charge before placing the order for approval. (iii) The Gen set must be affixed with label meeting the following requirement (The label shall be durable and legible) (a) Name and address of the engine manufacturer. (b)Certificate that the engine conforms to the CPCB IV emission/ latest CPCB emission norms shall be provided (c) Type and approval certificate number. (d) Date of manufacturing of Gen set. (iv) The complete DG Set including Engine / Alternator shall be factory assembled by manufacturer or its authorized OEM as approved for assembling of the DG set. A certificate in this connection shall be submitted to the GE. (v) The quoted rate shall be deemed to be inclusive of first fill of engine oil (vi) The quoted rate shall be deemed to be inclusive of minimum 12 hours test run at site as specified in PS in presence of IEM/ rep of accepting officer, all testing arrangements / equipments for water load test/ suitable strip heater load shall be made available by the contractor for tests. POL shall be arranged by contractor for testing and cost deemed to be included in quoted rate. (vii) The contractor shall arrange load / resistive load / water load for testing for final testing of DG set at site and the cost is deemed to be included in quoted rate. (viii) DG set should be sound proof as per latest policy/ latest CPCB Norms. (ix) Drawing for Plinth of DG Set shall be provided by OEM and approved by GE. Further the PCC foundation shall be made by the contractor and quoted rate is deemed to be included this provision.
Supply, Installation, Testing and commisioning laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade ISI Marked with stranded aluminium conductor of size 185Sqmm 3.5 core complete all as specified.
M&L for LT Onload change over switch panel, CPRI approved, made out of 3.15 mm thick MS sheet, powder coated, dust & vermin proof, IP-66 Protection, Outdoor type factory made cubical totally enclosed type with front and rear door opening as per engineering practice provided with locking arrangement for opening of panel with provision of seperate chamber in upper part to enclose aluminium busbar of cap 300 Amps, TPN on epoxy insulators in horizontal position and stepped manner with min 20cm distance between busbars & panel body and 06 Nos separate chambers of adequate size embedded in 40mm thick PCC 1:2:4 type B-1 (using 20mm graded aggregate), on angle iron of size minimum 40x40x6mm with footing 30 cm clear space between bottom of panel and flooring including all accessories prewired with insulated copper wires of suitable size. The panel shall compromise of the following fittings and fixture: INCOMING : (a) MCCB Four pole 250 Amps Icu =36 KA at 415 volts with micrprocessor release - 01 No (I/C) It should be with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu and with adjustable thermal setting, front face with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier, single phase preventer etc (b) ON LOAD change over switch 415V, front operated 4 pole of capacity 250 Amps complete all as specified and as directed. OUTGOING (i) MCCB Four pole 250 Amps Icu =36 KA at 415 volts with thermal magnetic release - 01 No (O/G) .It should be with adjustable over load setting Ir = (0.8 to 1.0) x In,Ics = 100 % Icu with positive break indication with double break contacts, Standard extended rotary handle, Spreaders, Phase barrier etc. (ii) Indicating lamps Led type (RYB). (iii) Digital Voltmeters 96 X 96 MM -01 No (iv) Digital Ammeters 96 X 96 MM with suitable CT ratios -01 Nos
M& L for Cable jointing kit for 1.1 KV (Earthed) grade LT cable for end termination heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 185 sqmm, indoor type complete all as specified and as directed by Engineer-in-Charge.
M&L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal ground level) with top edge of plate not less than 1.5 M below normal ground level, connecting to the 25X4 mm GI strip as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron and earth strip protected by provision of GI light grade pipe 40mm bore including provision of concrete pit in PCC (I:2:4) type B-1 using 20mm graded stone aggregated with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 Kg/Sqm) and frame of angle iron 40x40x6mm with lugs 02 Nos and handle of 6mm dia MS bar made to shape, GI light grade 20mm bore pipe for watering, perforated at bottom and connecting to earth test point all as specified
NOTE:- SCHEDULE 'A' PART-II (Schedule of credit) Credit amount of Rs (Refer schedule of credit) for retrieved material mentioned in Sch 'A' Part-II of Tender documents in PDF form will be deducted offline during acceptance of tender of lowest bidder.
M/S ZAHOOR AHMAD KHAN (BID ID -3477722)
M/S JIWAN SINGH (BID ID -3482586)
Continental Enterprises (BID ID -3483306)
KEWAL SONS (BID ID -3478017)
ANIKET TRADERS (BID ID -3477677)
Pyramid constructions (BID ID -3477608)
FANGALIA TRADERS (BID ID -3477028)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
tender57.pdf
Tender Documents • 1.15 MB
BOQ_825631.xls
BOQ • 1.00 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .