Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.3 LAccepted-AOC NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹5.5 L+₹21,255 (3.99%)Rejected-Finance NO 12 5TH B CROSS SHARADAMBA NAGAR M E S ROAD BANGALORE 560013 | BANGALORE | BANGALORE | KARNATAKA | 560013 | L2 | Rejected-Finance Being not L1 | |
| 3 | L3₹5.7 L+₹33,682 (6.32%)Rejected-Finance | L3 | Rejected-Finance Being not L1 |
Tender Value
₹6.7 L
EMD Value
₹13,400
Closing Date
23 Oct 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col Subhro Banerjee CWE
Commander Works Engineers AF South Gangamma Circle Opp Guard Room 410 AFS Jalahalli Bangalore 560013
REPAIR MAINTENANCE OF EXTERAL HT ELECTRIC SUPPLY DISTRIBUTION SYSTEM AND (GEN SETS) AT CQAE YELAHANKA
2021_MES_478097_1
86112/E8
Open Tender
Civil Works
Item Rate
120 days
GE (AF) Yelahanka
As per tender documents
7 documents required · 7 mandatory
₹500
GE (AF) Yelahanka
₹13,400
Yes
24 Dec 2021
27 Sept 2021
25 Oct 2021
27 Sept 2021
23 Oct 2021
11 Oct 2021
27 Sept 2021 - 5 Oct 2021
60 days
Amount
Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cable, foundation etc, and getting out in hard /dense soil all as directed.
Returning filling in including spreading, leveling Watering and well ramming in layers not exceeding 25cm all as directed.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed.
Supply and spread fine river sand in trenches, as in cable cushioning all as directed. Note: Punned thickness will be considered for payment.
Dismantling insulators of any type and size all as directed.
Supplying and fix in repair insulator including one galvanised mild steel spindle, two galvanised iron nut 150mm heightm 150mm dia for 11000 volts grade all as specified and as directed.
Supplying and fix in repair 255mm dia ball and socket type, white, brown of green single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts grade all as specified and as directed
Supply and fix in repair replace danger notice plate of 1.6mm thick mild steel sheet with vitreous enamelled white with letter figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT, 25 x 20cm all as directed and as specified.
Dismanting air break gang operated switches verticl/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worm out components and insulators etc all as directed.
Supply and fix in repair for replacement of switch air break, gang operated triple pole, mechanically operated (with GI operating rod), mounted on insulator and steel frame with operating mechanism worked from ground level, vertical type for current rating upto 400 Amps on HT 11000 volts working pressure, including locking arrangement with 06 lever lock and painting the steel surfaces with two coats of synthetic enamelled paint over a coat of red oxide primer etc all as specified and as directed.
Supply and fix in repair for replacement of expulsion / drop out / horn gap type fuse carrier assembly (DO Fuse) outdoor type 200Amps capacity including fuse element upto 25 Amps and insulator conforming to IS specifications suitable for 11000 volts (HT) all as specified and as directed.
Supply and fix in repair for lightning arresters for outdoor use expulsion type suitable for 11000 volts (HT) complete with all fittings, transmission class, discharge capacity 10 KA including taking down existing lightening arresters of any type and size all as directed.
Material and labour for replacement of galvanised iron strip 32 x 6mm buried in ground or fixed on pole with all accessories including dismantling old one all as specified and as directed.
M&L for earthing complete with galvanised iron earth plate electrode of size 600mm x 600mm x 6 mm thick buried directly under ground vertically to a depth not less than 2.25 metre below ground level with top edge of the earth plate at a depth not less than 1.5 metre below ground level connected to and including galvanised iron earth strip 32 x 6mm by means of bolts, nuts, check nuts, washer including test point by means of bolts, nuts, check nuts, and washers of galvanized iron and connected to main switch / control board up to 7.5 metre away from earth electrode and including GI pipe light grade 40 mm bore protection pipe & necessary excavation and earth work in any strata, PCC chambers in PCC 1:3:6 type B1, RCC 1:2:4 type B1 cover slab 50mm thick with 8mm dia TMT bars at 140mm C/C both ways, with lifting handle, watering pipe of GI medium grade 20mm dia, wire mesh, funnel, lugs and charcoal, salt etc all as applicable and as per plate No 3 of SSR Part-I including taking out old earthing materials all as specified and as directed
Supply, lay, test in inshort length of XLPE insulated screened PVC bedded, galvanised steel strip or wire, armoured, heavy duty electric power cable (Heavy duty earthed), 11000 volts grade with stranded aluminium conductor of size 3 core 120 Sqmm all as specified and directed.
Supply, lay, test in inshort length of XLPE insulated screened PVC bedded, galvanised steel strip or wire, armoured, heavy duty electric power cable (Heavy duty earthed), 11000 volts grade with stranded aluminium conductor of size 3 core 95 Sqmm all as specified and directed.
Material and labour for cable jointing kit for 11KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size including testing after jointing all as specified and as directed.
120 Sqmm size
95 Sqmm size
Material and labour for cable jointing kit for 11KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size including testing after jointing all as specified and as directed.
120 Sqmm size
95 Sqmm size
Material and labour for cable jointing kit for 11KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size including testing after jointing all as specified and as directed.
120 Sqmm size
95 Sqmm size
Supply and ley galvanised iron tubing light grade 100mm dia bore galvanized with all fitting laid in trenches / road crossing for UG cable protection all as specified and as directed.
Supply and fix in repair for jumper connections between GOD and drop out fuses and transformers with ACSR conductors 6/1 x 3.35mm (Rabbit) including necessary lugs wherever required / aluminium heavy duty PG clamps / binding properly without any loose contact after removing the old jumpers including PVC sleeves all as specified and as directed.
Surface dressing in hard / dense soil not exceeding 15 cm deep and clearing all the grass weeds etc in the sub station yards after removing stone aggregate aside all as directed at site including setting / spreading back the aggregate including levelling complete all as specified and directed by Engr in Charge. Note:- (i) The rate shall be deemed to be included the cost of removing the grass, weeds, debris, excess soil etc. to a distance not less than 50 m and keeping the excavated surface clean and levelled complete all as specified and directed. (ii) All the sub station yards shall be kept clean through out the contract period by removing the grass/weeds as many as times required depending on the growth of the grass.
Filtration of transformer oil of transformers installed at various locations to achieve di-electric strength not less than 60 KV for 1 minute at 2.5 mm gap as per relevant IS with portable filtration plant, testing of the oil for the di-electric strength before filtration and after filtration complete all as directed by the Engineer-in-Charge. Note :- a) The rate quoted shall be deemed to include for taking necessary conections to filteration plant from transformer and switch gear oil duly removing the inlet and out let connections. (b) Electric supply for the filteration plant will be made available free of cost. (c) The dielectric strength value of the transformer oil shall be tested before & after filtration. (d) Test Certificate duly signed by the contractor and rep of MES shall be submitted in the format as directed by Engr in Charge.
Supply and topping up or replacement of transformer oil with di-electric strength not less than 60 KV in to the conservator tank/ body tank of the transforme etc at various locations complete all as specified and as directed. Make: Poweroil/ Transol/ Sabitha Chemicals
Material and labour for replacement of silica gel breather assembly for HT distribution transformers of upto 250 KVA capacity including dismantling old one all as specified and as directed
Material and labour for replacement gun metal drain valves of transformers for upto 250 KVA capacities including dismantling old one all as specified and as directed. MAKE :- UPADHYAY/ LEADER/ ZOLOTO/ VAG
Material and labour for replacement of the LT porcelain bushings complete of transformer upto 250 KVA capacity distribution transformers of existing transformer make/ size/ type including dismantling old one all as specified and as directed .
Material and labour for replacement of the HT porcelain bushings complete of Transformer upto 250 KVA capacity distribution transformers of existing transformer make/ size/ type including dismantling old one all as specified and as directed .
Material and labour for replacement of the LT bushing rod made out of gun metal with threading & of suitable length/ size all as per existing including metal rings/ bolts/ washers/ rubber rings etc. complete for upto 250 KVA capacity distribution transformers of any make/ size/ type including dismantling old one all as specified and as directed
Material and labour for replacement of the HT bushing rod made out of gun metal with threading & of suitable length/ size all as per existing including metal rings/ bolts/ washers/ rubber rings etc. complete for upto 250 KVA capacity distribution transformers of any make/ size/ type including dismantling old one all as specified and as directed
Material and labour for replacement of (OTI) Oil Temperature indicator for upto 250 KVA capacity distribution transformers including dismantling old oneall as specified and as directed
Material and labour for preparation of old painted surfaces of transformers with coarse cloth/ brush and painting throughout externally on exposed surfaces with two coats of smoke grey colour synthetic enamel paint or approved colour as directed including writing of transformer details on plinth in white enamel paint on black enamel paint back ground complete including one coat of white wash for base foundation all as specified and directed by Engineer-in-charge for upto 250 KVA capacity indoor / outdoor type transformer.
Repair and servicing of HT 11 KV RMU of Make - ABB, Capacity 400 Amps out door type by opening and checking tripping circuit and resetting trip values and the nuemerical relays and checking tripping machnism and operating mechanism including servicing the LBS fully by engaging well experianced technicians as per manufacturer recommendation and all as directed by Engr-in-Charge and replacing all the defective parts/spares. Note Service sheet to be prduce by the contrator before claming of payment.
Material and labour for repair and servicing of HT 11KV two pole structure by repalcing galvanized PG clamps, GI bolts and nuts, pieces of ACSR conductor with insulation of any size as jumpers including lubricating the moving pars of AB switch and cleaning of all disc/pin insulators and applying silicon compound for prevention of arcing due to dust/salt deposits over the surfaces including applying one coat of red oxide primer on rusted portions after preparation of surfaces & applying a coat of aluminium paint to the entire steel structure complete all as specified and directed.
M&L for stone aggregate of size not exceeding 40 mm deposited spread and leveled in layers not exceeding 15 cm to a true surface of broken stones for transformer yard and pole structure area.
Cheaking, maintanance and servicing of following mentioned Diesel Generator sets including Alternator, Non AMF panels of connected DG set and carrying out routine 'A' check of the engine for smooth functioning complete all as per manufacturer's instructions and as directed by Engineer-in-Charge..
DG Set of capacity 125 KVA
DG Set of capacity 40 KVA
DG Set of capacity 20 KVA
Notes for Item No. 37
Control switches such as MCCB, Main switch, contactors, multi display meter shall be out of scope of the item of work and the rate quoted shall be exclusive for servicing/ maintenance of the above.
Servicing of DG set alongwith connected Alternator and Panel Board including 'A' check of the Engine shall be carried out minimum once in every month (Except during the month when 'B' check is carried out) as directed by the Engineer-in-Charge and the Contractor shall carry out periodical check during the maintenenace period and he shall be responsible for the smooth functioning of the DG set for a period of 30 days from the date of service and shall also attend all the maintenence works as and when required in that period except in case of major repairs.
Spare parts required for replacement during the maintenance period shall be measured and paid separately at supply only rates and cost of labour for fixing these spares shall be deemed to be inluded in the rate quoted for maint/per every month.
The contractor shall also attend to the breakdown calls and depute necessary technician for repair/maintenence works as and when required with out delay during the maint period.
Cost of all consumables required during the maintenance period shallbe deemed to be included in the rate quoted for this item.
List of checks to be carriedout under 'A' check is as follows:-
Check Engine oil level and topping up as and when required [Engine oil will be measuered paid seperately]
Check Engine Coolant oil level if required top up.[Coolant oil measured and paid seperately]
Check Belts if there is belt slippage adjust or replace
Check oil bath cleaner oil level .
Check Exhaust System for leackage and rectification.
Drain sediment and cleaning from Fuel filter & Fuel Tank.
Check dry type air filter element and clean or replace[Replacement required shall be measuered paid seperately].
Check engine alternator coupling and mounting bolts.
Tight all bolts and nuts in Alternator Terminal Box.
Check carbon brushes[Brush type] and connections in Altenator.
Check and tight all Electric connections in DC control wiring.
Check all Radiator rubber Hoses.
Record oil pressure , water and oil Temp.
Record RPM , Voltage, Current & Frequency
Check Anti Vibrating Mountings.
Check throttle linkages.
Check starting battery electrolyte level, specific gravity and top up level if required.
M&L for carrying out scheduled maintenance tasks as per 'B' check of the following Diesel Generator Sets including connected alternator and carrying out routine servicing of the engine as specified in manufacturer's instructions including consumables complete for smooth functioning of the set all as specified and as directed by Engr in Charge.
DG Set of capacity 125 KVA
DG Set of capacity 40 KVA
DG Set of capacity 20 KVA
Note :- Control switches such as MCCB, Main switch, contactors, multi display meter and engine control unit shall be out of scope of the item of work and the rate quoted shall be exclusive for servicing/ maintenance of the above.
'B' check shall be carried out once in every six months or 250 hours of running of DG Set whichever is earlier. Servicing of DG Set alongwith connected Alternator and Panel Board including items covered in 'A' check of the Engine shall also be carried out in that month as directed by the Engineer-in-charge and the Contractor shall carry out periodical check during the maintenance period and shall be responsible for the smooth functioning of the DG Set for a period of 30 days from the date of service and shall also attend all the maintenance works as and when required in that period except in case of Major repairs.
Spare parts like filter elements, engine oil, distilled water and radiator coolant liquid required for replacement during the maintenance shall be measured and paid separately at supply only rates and cost of labour for fixing these spares/filling of oil shall be deemed to be included in the rate quoted for maint as mentioned above.
Cost of all consumables required during the maintenance period shall be deemed to be included in the rate quoted for this item.
List of checks to be carried out under 'B' check are as under :-
FUEL SYSTEM
Check Hydraulic Governor oil
Check Throttil Leakage
Lubricate ball joints of the throttle linkage of hydraulic Governor
Change fule filter
Clean fule tank breather
AIR SYSTEM
Clean/Change Crankase Breather
Check Air pipings
COOLING SYSTEM
Check coolant in radiator
ADD coolant concentrate if required
Check heat exchanger zinc plugs
Servicing & Maintenance of AMF panels pertains to the following DG sets for smooth functioning including repairs to the u/s ammeter, voltmeter, oil pressure sensor, push buttons, indicator lamps, relays,control fuse and replace minor parts like, cleaning & servicing all contact points etc completely all as directed (Note:Spares such as power contactors,ACB's timers, Multi Display Meter, Battery,charger etc.shall be measured & paid separetly)
DG Set of capacity 125 KVA
DG Set of capacity 40 KVA
DG Set of capacity 20 KVA
Note for Item No. 38 :-
The rate deemed to be included all the minor spares such as screws, washers, clips etc and all other spares required will be measured and paid seperately under supply only items.
General maint shown above are indicative only, contractor has also to do any other maint task required for serviceability of DG set at site as directed by Engr-in-Charge.
The contractor has to attend the breakdown calls and depute technician as and when required without any delay to keep the DG set 100% serviceable all the times as directed by Engr-in-Charge.
Supply only set of fuel filter elements
DG Set of capacity 125 KVA
DG Set of capacity 40 KVA
DG Set of capacity 20 KVA
Supply only set of lube /engine oil filter/catridges as per sample and make of the following capacities of DG sets
DG Set of capacity 125 KVA
DG Set of capacity 40 KVA
DG Set of capacity 20 KVA
Servicing of radiator assembly of DG Set of capacity 125 KVA complete including cleaning the radiator, cooling water spaces, inner cooler with appropriate cleaning agent, descaling by means of scale solvent as well as neutralizing agent and arrest leackages by means of brazing, painting the radiator with enamelled paint after scrapping the existing oil paint, replacing the U/S rubber hoses pipes, circlip, clamps etc, reinstalling and commisioning all as directed for the following DG sets
_do_ but 40 KVA
_do_ but 20 KVA
Note : The rate qouted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges.
Supply and filling engine oil of grade 20W40, Make Castrol CRB Plus
Supply and filling radiator coolant
Supply and filling distilled water
Supply only fan belts for replacement of u/s fan belts of following capacities of DG set as per sample size all as directed.
DG Set of capacity 125 KVA
DG Set of capacity 40 KVA
DG Set of capacity 20 KVA
M & L for disconnecting from the engine, transporting to work shop for checking, servicing and calibration of fuel injection pump / PT pump with injectors of following capacities of DG sets as per calibration procedure and norms specified by OEM guide lines including replacement of wornout injector nozzles, plungers and cups, sealing rings, "O" rings and gaskets as required and refixing to the engine and testing to its full efficieny complete all as specified and as directed by Engr in Charge.
DG Set of capacity 125 KVA
DG Set of capacity 20 KVA
Cleaning throughly and preparing surface of 125 KVA DG Set by removing rust, dust and oil stains and painting of complete DG Set with two coats of existing colour code including control / AMF panel board complete all as specified and directed by Engr-in-Charge. Note:- (i) Painting should be done with existing colour codes and paint should apply with the help of spary gun using air compressor. 2. Quoted rate shall deemed to be inclusive of preparation of old painted surface and applying zinc chrome primer in patches over rusted portion all as directed.
All as per item No. 50 here in before but for 20 KVA DG set
Supply only Voltage Regulator (AVR) suitable for DG set of capacity 100 KVA to 125 KVA
Supply only battery lead with copper cable not less than 35 Sqmm size and 1.20 Mtr long with terminals/lugs.
Supply only A series electronic timer on delay function model AIDI/AIDCS 12V DC with time range 0.3 sec to 30 Min suitable for panel.
Supply only B series electronic timer model BIDCA-X adjustable cyclic function 240 volts AC suitable for AMF panel.
Supply only PLA relay suitable for AMF panel.
Supply only stopping solenoid 12 Volt suitable for 20/40/125 KVA DG set
Supply only battery terminal made of brass
Supply only Benjo bolts of suitable sizes
Supply only Hose plain for water pump suitable for the following DG sets
DG Set of capacity 125 KVA
DG Set of capacity 20 KVA
Replacement of Air Filter elements of following DG set as given bellow
DG Set of capacity 125 KVA
DG Set of capacity 40 KVA
DG Set of capacity 20 KVA
Supply only main contactor 185 Amps triple Pole complete suitable for AMF panel of 125 KVA DG Set.
Overhauling of self starter assembly 12 Volt DC [Make - Lucas TVS] of DG Set by disconnecting and removing from the engine, cleaning all accessories, replace the wornout parts like brushes, bushes, contact plates, jumping leads and seals, revarnishing the field coil, armature and reassembling the same, refitting the engine and including testing all as per manufacturer's instruction and as directed .
Taking down old MCCB and Supply and fixing MCCB, 4 pole 100 Amps rating , adjustable thermal and fixed magnetic release , 25 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified . Note :- Make : Indo Asian / Havells / Legrand / Crompton Greaves.
Taking down old MCCB and Supply and fixing MCCB, 4 pole 630 Amps rating , adjustable thermal and fixed magnetic release , 50 KA breaking capacity, 415 V, 50 Hz AC supply including making all connections complete all as specified . Note :- Make : Indo Asian / Havells / Legrand / Crompton Greaves.
Shanthi Construction
RAMESH BABU CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .