Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.8 LAccepted-Finance | L1 | Accepted-Finance Ist Lowest bidder | |
| 2 | L2₹4.9 L+₹12,150 (2.55%)Accepted-Finance | L2 | Accepted-Finance IInd Lowest bidder | |
| 3 | L3₹5.0 L+₹24,350 (5.11%)Accepted-Finance | L3 | Accepted-Finance IIIrd Lowest bidder |
Tender Value
₹4.9 L
EMD Value
₹4,900
Closing Date
20 Apr 2024, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
EDC I Saharanpur
Business Plan Work in the area of EDSD Sarsawa under EDD I SRE
2024_PVVNL_922190_1
335/W/EDC-I/SRE/2023-24
Open Tender
Electrical Works
Lump-sum
45 days
Saharanpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SE EDC I SRE
₹4,900
26 Apr 2024
13 Apr 2024
20 Apr 2024
13 Apr 2024
20 Apr 2024
13 Apr 2024
Amount
Detail of Work
Safe Removal and carriage of old & Damage 1 No I/C VCB & 1 No O/G VCB from site of work to ESC SRE including loading and unloading at both ends.
Safe carriage of 11 KV 1 No I/C VCB & 1 No O/G VCB from ESC SRE to Site of work including loading and unloading at both ends.
Safely installation of 11 KV 01 No I/C VCB & 1 No O/G VCB and connection properly.
water level Earthing of VCB by boring of till water level minimum 60 Ft deep & fixing of G.I pipe 11/2" Dia (Jindal Class B) and connecting with G.I. Strip of size 50x6 mm and copper strip at bottom of G.I pipe to the VCB providing of required charcoal & salt in the pipe
Safely Carriage of XLPE Cable 3x185sq.mm form ESC SRE to site of work including loading and unloading at both ends.
Laying of XLPE Cable 3x185 sq.mm.
Making and fixing of 11 KV Jointing Kit 3x185 sq.mm I/D and O/D side
Safe carriage of 1 No 33 KV VCB, 01 No 33 KV Control Pannel for Single T/F from ESC SRE to Site of work including loading and unloading at both ends.
Safely installation of 1 No 33 KV VCB & 01 No 33 KV Control Pannel for Single T/F and connection properly.
Chemical Earthing for VCB & Control Pannel
Safely Carriage of XLPE Cable 3x185sq.mm form ESC SRE to site of work including loading and unloading at both ends.
Laying of XLPE Cable 3x185 sq.mm.
Making and fixing of Jointing Kit 3x185 sq.mm I/D and O/D side
Laying of Control Cable 4x2.5 sq.mm
Laying of Control Cable 2x2.5 sq.mm
Safely removal of Battery Set with Charger 24 Volt from site of work to ESC Sre including loading and unloading at both ends.
Safely carriage of 33 KV CT from ESC SRE to site of work including loading and unloading at both ends.
Safely installation of 33 KV CT properly and making connection to C&R Pannel.
Providing of Fire Extinguisher (Dry Power Types)5 KG
Providing of Sand Bucket with stand (03 Bucket)
Safely Carriage of Battery Charger 24 Volt 1 No, Battery Set 24 Volt 1 No from ESC SRE to site of work including loading and unloading at both ends.
Safely Fixing of Battery Charger 24 Volt & Battery Set 24 Volt properly
Safe carriage of 1 No 33 KV VCB, 01 No 33 KV Control Pannel Double for T/F from ESC SRE to Site of work including loading and unloading at both ends.
Safely installation of 1 No 33 KV VCB, 01 No 33 KV Control Pannel Double for T/F and connection properly.
Pipe/Water Level Earthing of 33 KV VCB (1 No body & 1 No. neutral earthing) & 1 Control Pannel Double T/F 01 No by boring of 60 Ft deep & fixing of 60 ft. G.I pipe 11/2" Dia (Jindal Class B) and connecting with G.I. Strip of size 40x5 mm and G.I wire at bottom of G.I pipe to the VCB/Control pannel providing of required charcoal & salt in the pipe
Fabrication & grouting of MS Structure for installation of Out Door CT
SAINI ASSOCIATES
FAGGU RAM & COMPANY
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .