GARRISON ENGINEER (MIS) MHOW
Garrison Engineer (Maint) Infantry School , Mhow -453441
REPAIR AND MAINT OF LT PANEL UG CABLE LT DISTRIBUTION SYSTEM AND REPAIR MAINT OF STREET LIGHT FLOOD LIGHT HIGH MAST LIGHT GATE LIGHT AND OTHER CONNECTED WORKS AT ALL AREAS OF INF SCHOOL UNDER GE MIS MHOW
2024_MES_652379_1
8674/GE (MIS)/Mhow
Open Tender
Civil Works - Others
Item Rate
210 days
GARRISON ENGINEER (MIS)
All as per Tender document
7 documents required · 7 mandatory
₹500
GE (MIS) Mhow
₹96,000
Yes
5 Jul 2024
4 May 2024
3 Jun 2024
4 May 2024
1 Jun 2024
18 May 2024
Amount
Excavating in trenches, in any type of soil not exceeding 1.5m wide and not exceeding 1.5m in depth for laying cable, pole foundation etc complete all as specified.
All as per item No 02 above depth exceeding 1.5m but not exceeding 3.0m
Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete.
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete.
M&L for sand cushioning with fine dry unwashed sand in trenches for protection of cables complete. Note :- Thickness shall be measured after punning
M&L for old size sub class ‘B’ bricks, laid in trenches as a cable covers complete.
S&F steel tubes, galvanised, light grade, ISI marked 40mm bore for protection of cable under floor, road and on wall complete.
S&F steel tubes, galvanised, light grade, ISI marked 80mm bore for protection of cable under floor, road and on wall complete.
M&L for attending external electric complaints by opening / disconnecting the electrical connection of defective / burnt out underground LT cable of any size & any core from main switch / DB / junction box / LT panel / L T O/H line etc. and taking out the required length of cable from existing loop and remove/ cut the defective cable,replace the same with new cable as per existing size including providing necessary thimbles / connectors at cable end and reconnecting the cable in previous location with existing main switch / DB / Junction box / LT panel / OH line etc. and make electic connection as functionable in all repspects including testing on completion all as specified and directed by Engineer-in-charge.
Note:- (A) The quoted rate shall be inclusive of the following: (i) Necessary earth work excavation as required for finding/attemding faullt /in any type of soil, returning filling and removing extra soil. (ii) Existing bricks, sand,GI protection pipe etc. shall be removed carefully and stacked neatly near site and re- laid the same in position after attending fault/defect. (iii) Distrubed surface of road, floor etc. shall be make good to match with existing surface. (iv) Required numbers of electrician and helper shall be deployed for attending complaints regulerly on daily basis and contractor shall collect the complaints details from complaint cell of AGE E/M No.1 and same shall be rectified/ attanded within an hour and report shall be submitted to Engineer-in-charge or their authorised representative. (B) Please note that payment shall be made to contractor one time only for this items. if any fault/ default occured again on the same location/ DB/junction box/panel during currency of contract, the same shall be rectified by the contractor without any extra cost to Govt. in terms of condition 46 of IAFW 2249 of Genral condition of contracts. (C) Additional bricks,sand,GI pipe etc. as required for cable protection and cushioning shall be measured and paid separetely under relevant item.
M&L for dismantling / disconnecting / removing the faulty / burnt out overhead conductor of any type / size from insulator of HT / LT pole any type by making proper shutdown from department and removing of tree / branches if any fell on Over Head Line, loose the binding wire in each insulators and disconnecting cable connection as required, remove the burnt / damage conductor / earth wire and making necessary joint with new ACSR conductor of suitable size as per existing as directed, restretching all loose spans of ACSR conductors, earth wire etc. with insulator and providing binding wire of existing size to tigheting and making LT/HT cable in existing position and make electric connection as functionable in all respects including testing on completion allas specified and directed by Engineer in charge.
NOTE: (a) The quoted rate shall be inclusive of the following:- (i) Tools and plants such as ladder,rope, cutter, axes, knife etc. as required for cutting and removing tree/branches if any fall on OH line. (ii) Insulator,binding wire etc. as required in addition to existing shall be provided by the contractor. (iii) Required numbers of Elecrician and helper shall be deployed for attending complaint regularly on daily basis and contractor shall collect the complaint details from complaint cell of AGE E/M No. 1 (b) Additional ACSR conductor and earth wire shall be measured and paid separetely under relevant items.
S&F in replacement of LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.
S&F in replacement of LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.
M&L for Painting of transformer of capacity up to 750 KVA, 11/.433 KV by applying two coats of synthetic enamelled paint over a coat of primer by using spraying machine including preparation of transformer surface and removal of rusted portion complete all as specified and directed.
M&L for Tracing out fault upto 11KV underground cable of any size by using fault tracing machine and rectifying the same by cutting and removing defective cable ,providing necessary cable of same size and jointing with existing cable all as specified and directed by Engineer-in-Charge to restore the electric supply complete all as specified and directed by Engineer-in-Charge. Note: (i). Joint kit shall be measured and paid separately. (ii) Earth work eacavation shall be measured and paid separately. However, width of trenches shall be allowed for payment as per authorized width as given in SSR part I for each size of cable. (iii) All other necessary arrangements suitable for locating the faults such as fault checking instrument etc shall deemed to be included in the unit quoted rate . (iv) T&P required for the entire job shall be provided by the contractor at his own end and nothing extra shall be admissible on this account. (v) Cable required, if any shall be measured and paid for separately.
M&L for trimming /pruning of tree branches touching to the LT over head line or near to the LT over head line as per direction of Engineer-in- charge complete including removing the tree branches from site complete all as specified and directed . NOTE : (a) A written shut down shall be obtained from concerned JE / AGE E/M before carrying out the trimming work in hand by contractor (b) Approximate span between poles shall be 30 to 50m. (c) T & P such as ladder , rope, cutter , axes and other related material shall be provided by the contractor.
Supplying and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and over all PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of size 10 sqmm.
Supply and Laying LT UG cable 1100 Volts grade XLPE insulated PVC sheathed amoured, heavy duty, in trenches/walls/poles/passing through pipes with multistranded aluminium conductor including lugs/thimble/ferules connection, testing and commissioning complete including taking out old unserviceable UG cable for the following sizes. Note: Earth work, excavation, sand cusioning, bricks for protection, GI pipe etc shall be measured and paid separately under relevant items of this schedule .
10 sqmm 4.0 core
16 sqmm 4.0 core
25 sqmm 3.5 core
35 sqmm 3.5 core
50 Sqmm 3.5 core.
70 Sqmm 3.5 core.
95 Sqmm 3.5 core.
120 Sqmm 3.5 core.
185 Sqmm 3.5 core.
S&F in replacement of MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA
S&F in replacement of MCCB 3 Pole, 415 V, fixed type, 125 Amps with breaking capacity 16 KA
S&F in replacement of MCCB 3 pole, 415 volts, adjustable type 160 Amps with breaking capacity 36 KA
S&F in replacement of MCCB 3 pole, 415 volts, adjustable type 200 Amps with breaking capacity 36 KA
S&F in replacement of MCCB 3 pole, 415 volts, adjustable type 250 Amps with breaking capacity 36 KA
S&F in replacement of MCCB 3 pole, 415 volts, adjustable type 350 Amps with breaking capacity 36 KA
S&F in replacement of MCCB 3 pole, 415 volts, adjustable type 400 Amps with breaking capacity 36 KA
S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 250 Amps with breaking capacity 36 KA
S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 350 Amps with breaking capacity 36 KA
S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 400 Amps with breaking capacity 36 KA
M&L for replacement of broken over head conductor of any type and length as required at site supply and fix ACSR conductor of size and type as per existing complete all as specified and directed .
M&L for Restringing of loose over head conductor / GI earth wire of any size and type after untyeing binding wire from insulators / cross arms to achieve permissible sag limit of over head line including new binding wire of proper size and pruning of tree branches of concerned spans and jointing of jumpers properly complete all as specified and directed at site. Note:- (i) Each span shall consist of 3 phase , 4-wire over head line. (ii) The distance of one span between poles shall be 30 to 50 metre .
S&F in repalcement of straight through joint ( Epoxy joint) for following size PVC insulated and sheathed aluminium conductor cable complete for following sizes :-
3.5 core 50 sq mm
3.5 core 70 sq mm
3.5 core 95 sq mm
3.5 core 120 sqmm to 150 sqmm
3.5 core 185 sqmm
M&L for repairing damaged /corroded portion of existing LT panel board of any size by providing and welding MS sheet of existing thickness, replacing hinges, aldrop bolt as required and made for proper locking system and painting internal and external surface of LT panel with one coat of synthetic enamel paint of approved colour all as specified & directed by Engineer-in-charge.
M&L for Maintenance of indoor sub stations, including cleaning of premises and surroundings upto 5m from outer face of wall, checking the oil level of transformers, cleaning and dusting out of transformers, panel boards, cleaning of earth pits to keep free from vegetation complete all as directed by Engineer-in-Charge .
All as per item No 33 here in before but for out door sub station / RMUs / Surrounding LT Panells including levelling of loose filled aggregate in proper manner around substation
S&F in repairs mild steel galvanised stay assembly set complete comprising of 20mm dia, 400mm long stay bow, 1800 mm long stay rod 20mm dia, 300mm x 300mm x 6mm stay plate, thimble, GI stay wire of 7/8 SWG upto required length including loop type insulator of vitreous porcelain, small size with overall dimensions 90x140mm, clearance of hole 25.5mm, all as shown in electrical plate No.1 of MES Schedule part I 2009 complete all as directed.
M&L for replacement of Danger notice plate of size 20x15 cm for LT cable and 25x20cm for HT cable with 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size complete all as directed by Engineer-in-charge.
M&L for preparing surface of street light ,steel tubular swaged/ swan neck pole of any type and painting with two coats of aluminium paint over a coat primer from top to bottom including painting to cross arms /FI clamps/street light brackets of any type including making painting alternative bay with blak and yellow strip with synthethic enemelled paint up to 1.5 meter height from ground level and writing of pole numbers with black paint on poles complete all as specified
M&L for preparation of old painted surface of LT PCC street light pole 9m long with one coat of acrylic paint over a two coats of cement base paint and making pole surface smooth including painting cross arms, clamps etc with two coats of aluminum paint and painting up to 1.50 m height from top of PCC foundation block and painting the pole in alternative strips with black and yellow paint (each strip 30cm high) and including writing pole nos. and applying one coat of cement base paint on exposed surface of PCC coping and foundation blocks complete all as specified and as directrd by Engineer-in-charge.
Supply, fabrication, installation, testing and commissioning of out door type LT panel board of size 600x600x300 mm cubical type,made out of 3.15mm thick CRCA sheet , factory made,with slanting top ,minimum 10 Cm projection all around, inbuilt industrial type ,fabricated with 50x50x6mm angle iron frame work with front openable single hinged door / shutter with locking arrangments, floor mounting type duly spray painted with two coat of gray synthetic enamel paint over one coat of red oxide zinc chrome primer after preparation of the surface , with required civil work & wiring with copper cable of suitable size, connecting including indication lamp LED type for each phase, Aluminium bus bar - 400 Amps rating - 03 Nos. for phases and 400 Amp rating - 01 No. for neutral fixing with suitable, clamps,nuts, bolts wahers ,danger notice board , feeder marked including necessary earth work excavation , PCC foundation etc as required at site complete all as specified and directed by Engineer-in-Charge
S&F cable path indicator made of MS sheet of size 200 mm x 150 mm x 3 mm thick and spot welding with angle iron of size 40 x 40 x 5 mm thick, 750 mm long embedded in PCC 1:2:4 type B1 using 12.5 mm graded granite stone aggregate including applying one coat of synthetic enameled black paint over a coat of red oxide primer and sign writing with white paint duly showing size of HT/LT cable complete all as specified and directed.
M&L for cutting the existing bituminouse road to a width n.exc 0.50m for passing of UG Cable as in road crossing and making good the disturbed surgace of road with PCC 1:2:4 type B1 using 20mm graded stone aggregate complete all as specified and directed
S&F in repairs moulding compound Street light junction box of size 250 mm x 200 mm x 105mm complete with shock and rust proof, termite resistant, tamper proof , front openable type and including suitable provision for single phase, two wire cable (size upto 25 Sqmm 2 Core) incomming & outgoing loop -in loop connection and including one no. MCB SP 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole / wall complete. Make : Sintex Cat part No GSJB 2520 or equivalent in Hensel/ABB.
S&F in repairs moulding compound street light junction box of size 250 mm x 250 mm x 160mm complete with shock and rust proof, termite resistant, tamper proof , front openable type and including suitable provision for three phase, four wire cable (size upto 25 Sqmm 4 Core) incomming & outgoing loop -in loop connection and including one no. MCB SP 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole / wall complete. Make : Sintex Cat part No GSJB 2525 or equivalent in Hensel/ABB.
Supply, install,testing and commissioning including replacement of street light control box , pole mountable enclosure conforms to IP-64 suitable for 440/230V, AC, 50 Hz, consisting of a light sensitive control system, power contactor for load switching, MCB and terminal suitable for Single- phase, 5 KW load blocks complete all as specified Make: Swadeep Nature Swith model No 02EC5kW1P or equivalent in CG/L&T/phillips
Supply, install , testing and commissioning replacement of street light control box as a pole mountable enclosure conforms to IP-64 suitable for 440/230V, AC, 50 Hz, consisting of a light sensitive control system, power contactor for load switching, MCB and terminal suitable for Three- phase, 5 KW load blocks complete all as specified Make: Swadeep Nature Swith model No 02EC5kW3P or equivalent in CG/L&T/phillips
Supply and fix in repairs MCB TPN, 415V, 40 Amps,
Supply and fix in repairs MCB TPN, 415V, 63 Amps,
Supply and fix in repairs MCB SPN, 415V, 40 Amps,
Supply and fix in repairs MCB SP 5 to 32 Amps 230 Volt
M&L for Earthing complete with galvanised steel earth plate electrode of size 60cm×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metre below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion.
Supply, fabrication, installation, testing and commissioning of out door type LT panel board of size 1500mm x 1200 mm x 500 mm cubical type,made out of 3.00mm thick CRCA sheet , factory made,with slanting top ,minimum 10 Cm projection all around, fedder pillar type,fabricated with 50x50x6mm angle iron frame work with front and back side openable single hinged door / shutter with locking arrangments, floor mounting type, busbars made of copper duly insulated with heat retardent fire proof (HRFR) heat shrinkable sleeves of relevant colours,bus bar shall be properly supported/mounted on epoxy insulators ,all live parts and joints shall be insulated with (HRFR) shrouds, conforming to IS, including provision for connecting suitable earth strips,painting with one coat of anti corrosive coating and finally epoxy polyester powder coating, and confirming relavent IS, comprising the adequate arrangement to supply & fix the following accessories,including connecting cable glands,enamelled danger notice plate of 1.60mm thick miled steel sheet of size 200mm x 150 mm and cable lugs,fixing of earth lead to earth terminal of panel including necessary earth work excavation , PCC foundation etc as required at site complete all as specified and directed by Engineer-in-Charge.Note:- Quoted rate shall inclusive for all following accessories
Incoming Aluminium bus bar - 250 Amps rating - 03 Nos. for phases and 250 Amp rating - 01 No. for neutral
MCCB 4 pole 200 Amps, 415 volt, 36 KA - 01 No.( incoming)
ON/OFF LED type indication lamp with toggle switch - Set of 03
Out going:- MCCB 4 pole 100 Amp, 415 volt, 16 KA - 02 Nos
MCCB 4 pole 63 Amp, 415 volt, 16 KA - 02 Nos
MCB TPN 40 Amp, 415 volt, - 2 Nos
M&L for repairing street / security light of any type and flood lights / post top lanterns or any other external lights in its position fixed pole / building structure or by taking down to ground, if required and testing all the components / parts, wiring etc, identifying and replacing the defective components like choke (ballast), electronic driver (in case of LED Lights), ignitor, capacitor, lamp, lamp holder, connector, connection wires/ cable, MCB etc and refixing the fitting in its original position (if taken down), including repairing of street light control timer & junction box and makethe light fitting functionable in all respects complete all as directed by Engineer-in-charge.
Note:- (a) Spares such as choke (ballast), electronic driver, Ignitor, capacitor, lamp, lamp holder, connector, connection wire, MCB, timer spares etc shall be measured & paid separately under respective items. (b) The contractors / Representative shall report to concerned JE E/M at 09.00 hours daily to collect the details of complaints of defective street light fittings and shall submit the completion report of complaints of fitting on the same day before 17.30 hours to JE E/M. (c) The contractor shall rectify the defects / repair and make the street light functional within 24 hours from the time of handing over of complaint over by the concerned JE E/M. An amount of Rs 150/ day per complaint shall be recovered from contractor if street light shall not be repaired and functionable within 24 hours.
(d) Contractor shall arrange requisite and sufficient no of labours,ttransport and vehicle mounted hydraulic ladder etc at his own arrangement. (e) The contracor shall maintain proper record of repair/maint of light fittings in a binded register duly showing the details of spares replaced on each and every street light and get it authenticated from concerned JE E/M on daily basis. The contractor shall show the record register to Engineer-in-charge for inspection every Monday or as and when asked for. (f) The contractor shall be fully responsible for the safety of his men engaged for executing this work and provide all requisite safety equipment and clothings etc to Electrician & Helper. Contractor shall be fully responsible for any kind of mishappening /accident / injury etc if any to his employed labours.
(g) The contractor shall maintain sufficient stock of spares/material as required for repair/maint of street lights. (h) Contractor quoted rate shall be inclusive for screws, insulating tapes, internal wiring wire, gaskets and other minor items as required for repairing and making the street light fittings/security light fittings in serviceable condition.
All as per item No 60 above but for light fittings from high mast poles of 11 to 13 m long.
Taking down high mast fitting from high mast structure through motorised system of 16/20m high and cheking all fittings including cleaning & lubricating of steel rope and repair the light fittings to make functional by replacing flood light. complete all as directed by Engineer-in-charge. Note:- Flood light and connecting cable shall be measured and paid seperately under respective items .
S&F in replacement of energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP 66 flood light (Area light) of 30 Watts suitable for highlighting architectural façade and general purpose lighting including all necessary fixing arrangments complete.
S&F in replacement of LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistance complete with driver and lamp.
S&F in replacement of post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete. Make:- BAJAJ CAT PART NO- BGCTNP 20W LED WH/WW or equivalent in PHILIPS / WIPRO
S&F in replacement of LED bollard with opal diffuser and aluminum reflector capacity 09 watt including all necessary fixing arrangments as per site requirement including PCC work of suitable size and taking down existing unserviceable one complete all as directed at site. Make : BAJAJ Cat Part No.BGBOL 605 9W LED WW or equivalent in PHILIPS/ Wipro
M&L for repairing the existing junction box/ control box of street light by disconnecting all connection and reconnect the same after repairing including dusting, proper insulation with LT tape, replacement of lugs, nuts , bolts washer etc as requried including provision of 01 No of MCB 06 Amps and making the junction box funcationable complete all as specified and directed by Engineer - in -Charge.
Supply only LED driver for FLOOD LIGHT of capacity 150 watts rating 240 Volt, 50 Hz. Make:- Philips, Bajaj, Havells
Supply only LED driver for FLOOD LIGHT of capacity 120 watts rating 240 Volt, 50 Hz. Make:- Philips, Bajaj, Havells
Supply only LED driver for FLOOD LIGHT of capacity 80/100 watts rating 240 Volt, 50 Hz. Make:- Philips, Bajaj, Havells
Supply only LED driver of capacity 60/70 watts rating 240 Volt, 50 Hz. Make:- Philips, Bajaj, Havells
Supply only LED driver for Street Lights,of capacity 30/36/45 watts rating 240 Volt, 50 Hz Make:- Philips, Bajaj, Havells
S&F in repairs two-core PVC insulated copper cable with multistranded copper conductor of size 1.0 sqm x two core and drawn into existing GI pipe bracket and connected to street light fittings complete all as specified
M&L for street light bracket made out of 40mm dia medium grade GI pipe of 1.2m length bent to required shape suitable for fixing street light / security light fitting on M&L for street light bracket made out of 40mm dia medium grade GI pipe of 1.2m length bent to required shape , suitable for fixing street light / security light fitting on Steel tubular pole / RCC pole / building wall including two Nos of clamps made out 30mm X 5mm flat iron with suitable nuts and bolts (clamp type - as per site requirement ) including two coats of aluminium paint over a coat of red oxide primer and taking down the existing unserviceable rusted street light brackets with clamps, nuts and bolts etc complete all as directed. Make:- TATA/JINDAL/SWASTIK
S&F in repairs MCCB 125 Amps, 16 KA, FP, 415 volts with neutral link including al cable lugs all as specified. Make:- ABB/L&T/Schneider/ Havells/ Indoasian/Legrand
All as per item No 75 above but for capacity 100 Amps, 16 KA.
All as per item No 75 here in before but of capacity 200 Amps, 26 KA.
S&F in replacement of single phase contactor 5kW of load capacity 40 Amps, Incoming-Outgoing MCB rating 32-40 Amps & circuit wiring minimum 10 Sqmm complete all as specified and as directed Make:- ABB/L&T/Schneider
S&F in replacement three phase contactor 5kW of load capacity 20-25 Amps, Incoming-Outgoing MCB (03 Nos each) rating 20-25 Amps complete all as specified and directed Make:- ABB/L&T/Schneider
S&F Nature switch sensor illuminate level for switching on is < 30 lux and for switching off > 10 lux alongwith part night operation facility of 4-12 Hrs. Make : Swadeep or equivalent in CG
S&F in repairs Digital Timer switch for 1x 24 Hrs for controlling street light timimng with 150 hrs back up Make:- ABB/L&T/Schneider
S&F in repairs PVC tubes, medium grade, 20mm bore for laying of sub-main wire/cable on Street Light Poles and on wall, including necessary accessories & fixing arrangments like PVC band, clamps, nut ,bolts etc.complete all as specified and as directed.
M&L for plain cement concrete 1:2:4 type B2 using 40 mm graded stone aggregate as in foundation, filling and mass concrete all as specified
M&L for plain cement concrete 1:4:8 type D2 using 40 mm graded stone aggregate as in foundation, filling and mass concrete all as specified
M&L for plain cement concrete 1:3:6 type C1 using 20 mm graded stone aggregate as in roof kerbs or pole coping of size 300x300 mm , chamfered on edges including necessary form work etc complete all as specified and directed.,
M&L for dismantaling old cracked /unserviceable PCC poles /MS pole struts of any type and size including deposited at a suitable location not more than 50 metre away complete all as specified and as directed by Engineer-in- Charge.
M&L for Steel tubular swaged poles complete with base plate 8mm thick welded with pole, finial taper plug, bolt, nut and screws as specified type 410 SP-31 (9m long) including one coat of red-oxide zinc chrome primer and two coats of aluminium paint on surfaces exposed to view and making 30cm wide strips (total 5 Nos) with white and black paint alternately on external surface above PCC benching including numbering with black paint and painting with bituminous paint internally complete and externally complete all as specified and directed. Note : Excavation & earth work and PCC shall be measrued and paid separately under relevant item. Make : India Tube and Co, Kalinga tubes, The National tubing company, India Electric Poles Mfg Co
M&L for disconnecting conductor,insulator,channel,street light bracket etc from LT pole of height 9 to 11 meter and remove LT Pole carefully from safe ground, lifting the LT pole and load the same in a suitable vehicle and transport /shifting to a distance not exceeding 3KM and unloading the pole , re-fixing the same in new location including necessary earth work excavation,PCC foundation,PCC coping etc complete all as specified and as directed by Engineer- in- charge.
SAHYOG ELECTRIC
sanjay traders
Sameer Auto Engineers
ENVIRO TECH SERVICES
Auto Traders
Vinayak Trading House
Mighty Steel Sales Crop
SUNIL ENTERPRISE
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .