| 1 | Accepted-Technical | Accepted-Technical accepted |
| 2 | Accepted-Technical 5 B 2 1ST FLOOR OPP METRO PILLOR 484 TILAK NAGAR DELHI 110018 | WEST | DELHI | 110018 | Accepted-Technical accepted |
Tender Value
₹49.6 L
EMD Value
₹99,229
Closing Date
7 Apr 2026, 3:30 pmClosed
Executive Engineer (E ) BM-II
BM-II (E) Div. Gyan Mandir Office Complex, Tees January Lane, New Delhi - 110011
Replacement of old/outlived 125 KVA DG sets with new 02 no. 125 KVA Silent Type (CPCB - IV Plus compliant) DG Sets including earthing at Charak Palika Hospital, Moti Bagh, New Delhi.
2026_NDMC_289233_1
110/EE(E)BM-II/2025-26
Open Tender
Electrical Works
Percentage
90 days
Charak Palika Hospital, Moti Bagh
As per NIT
2 documents required · 2 mandatory
₹0
₹99,229
1 Jun 2026
24 Mar 2026
7 Apr 2026
24 Mar 2026
7 Apr 2026
24 Mar 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying, Testing and Commissioning of ‘Silent Type’ (CPCB - IV+ Compliant) Diesel Generating set along with having Prime Power Rating of 125 KVA, 100 KW, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system and consisting of the followings: (i) Diesel engine 4 stroke liquid cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C conforming to BS 5514, BS 649, IS 10000. The engine will be fitted complete with all the required accessories. (MRI SIDE DG SET and Emergency Side DG Set) inclusive of GST. Make : Kirloskar, Cummins, Greaves or any other similar superior make (ii) Engine mounted Instrument Panel fitted with and having digital display for various functionalities such as engine hours indication, battery charging indication, RPM indication, lubrication oil pressure/temperature indication, over speed indication, low lubrication oil trip indication etc. (iii) Synchronous alternator rated at 125 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS/IEC 60034-1 suitable for tropical conditions. (iv) Daily service fuel tank of capacity of minimum 230 liters or as per manufacturer standard fabricated with suitable gauge of M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. (v) Base frame and foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arragement as per recommendation of manufacturer (vi) Fuel Tank: Daily service fuel tank of capacity of standard size as per manufacturer standard fabricated with suitable gauge of M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class ‘C’ pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications (vii) Exhaust System: Dry exhaust main fold with hospital exhaust silencer and catalytic convertor (CPCB - IV+ Compliant) (viii) 12V/24V DC starting system 12V/24V DC starting system comprising of starter motors : voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (suitable capacity) as required as per specifications. | |||||
| 2Supplying, testing and commissioning of automatic mains failure (AMF) control panel suitable for 125 KVA silent type (CPCB - IV+ Compliant) DG Set complete with relays, timers, set of CT's for metering, protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, KVARH and provision for overload, short circuit, restricted earth fault, under frequency, control cabling from AMF panel to diesel engine and elsewhere, if required, all complete and inclusive of GST and interlocking the following Suitable for 125 KVA DG Set 4 Pole MCCB 50 KA with electronic release (Ics=100% Icu) - 2 Nos. Microprocessor based supply failure and restoration timer Microprocessor based 3 impulse automatic engine start / stop logic mains / Generator voltage and frequency sensing Multifunctional meter with scrolling reading for : (a) Lub oil pressure, water temperature and running hours for engine. (b) Voltage / ampere / frequency / KVA for Alternator (c) Battery voltage Protection: (i) Lub oil pressure, water temperature (LOW, High and week battery voltage) (b) Under / over voltage & frequency, loss of AC voltage sensing (c) Cranking lockout and fail to Start / stop shutdown. Indication LED DG ON, load on DG, main ON, load on main battery charger ON Installation of Both the DG sets for Emergency Side and MRI side | |||||
| 3Lifting and installation of ‘Silent Type’ (CPCB - IV+ Compliant) Diesel Generating set along with having Prime Power Rating of 125 KVA, 100 KW, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system as well as standard AMF panel including the cost of heavy labour and crane charges for unloading the DG set and AMF panel at the required location at site. | |||||
| 4Providing suitable C.C. foundation for installing self supported steel support structure using 1:2:4 cement concrete mixture of standard 400 mm depth M-20 grade i/c excavation complete as required suuitable for the installation of DG set and automatic mains failure (AMF) control panel as per the given standard respective sizes. | |||||
| 5Supplying and fixing exhaust gas piping of 300 mm dia. welded black MS C Class pipe conforming to IS : 1239/3589 cut to required lengths and installed with necessary bends, supports and clamps, antivibration mountings, insulation of exhaust system with mineral wool / Rock wool, 50 mm thick wire mesh & Al. cladding etc as required as per CPWD specification inclusive for both the DG sets | |||||
| 6Design and fabrication of 'self-supported steel support structure (35 mtr. lenght including both the DG sets) for exhaust pipe of MS channel 100mm x 50 mm with M.S. base plate of size 250 mm x 250 mm x 25 mm by welding complete with all material. | |||||
| 7Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. (a) Above 95 sq. mm and upto 185 sq. mm (clamped with 40x3mm MS flat clamp) | |||||
| 8Supplying of following size XLPE insulated Aluminium conductor armoured power cable suitable for rated voltage of 1.1 KV grade as amended upto date (ISI marked) on following manners etc complete as required. Make : Polycab, Havells, Finolex, RR Kabel (a) 3.5 X 185 sq mm | |||||
| 9Fabricating and installing following size of perforated MS cable trays including horizontal and vertical bends reducers, tees, cross members and other accessories as required, and duly suspended from the ceiling with MS suspenders including painting etc of size 450 mm x 50 mm x 2 mm thickness (NR) etc as required | |||||
| 10Supplying and laying of 1.1 kV grade, 6 X 2.5 sq. mm LT PVC control cable with multi stranded (rm) copper conductor, PVC insulated, galvanized steel wire/strip armoured and overall PVC outer sheathed as per IS: 1554 Part-1/1988 with up to date amendments. Make : Polycab, Havells, Finolex, RR Kabel Earthing | |||||
stage.html
html • 0.02 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.04 MB
BOQ_384054.xls
BOQ • 0.41 MB
NIT110.pdf
PDF • 2.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .