Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.0 LAccepted-AOC HIMACHAL BUILDING SHOP NO 10 CD BARFYWALA ROAD JUHU LANE ANDHERI W MUMBAI 400058 | MUMBAI SUBURBAN | MAHARASHTRA | 400058 | ₹47.0 L | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹56.3 LRejected-Finance 1 A BASEMENT 30 31 RAJA HOUSE NEHRU PALACE NEW DELHI 110 019 | SOUTH EAST | DELHI | 110019 | ₹56.3 L | L2 | Rejected-Finance NOT BEING LOWEST |
| 3 | L3₹57.4 LRejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | ₹57.4 L | L3 | Rejected-Finance NOT BEING LOWEST |
| 4 | L4₹65.4 LRejected-Finance | ₹65.4 L | L4 | Rejected-Finance NOT BEING LOWEST |
| 5 | Rejected-Technical | - | - | Rejected-Technical SINCE TURNOVER IS LESS THAN 50.00 LAKH AND EXPERIENCE NOT OF SIMILAR WORK |
| Sl No | Description | Qty | Unit | M/S JVS ENGINEERING L4 | MONA GENERATOR SEVICES PVT. LTD. L2 | Vijaypower Generators Limited L3 | M/s PIONEER CONTRACTORS L1 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supplying Installing testing & commissioning diesel engine driven generating set 415 V, 3 Phase, 4 Wire as per BS 5514/IS-10002 of capacity continuous rating 500 KVA conforming to CPCB IV+/latest norms at NTP conditions with acoustic enclosure considering all derating factors and comprising of the following :- (a) ALTERNATOR : Closed type regulated with brushless self excitation 415 V, 3 Phase, 4 Wire, 50 HZ, 0.8 PF 1500 RPM with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load Anti vibration mounted drip proof type with class 'F' insulation, steel ball/roller bearings at both ends of the alternator shaft, with necessary controls as recommended by the manufacturer confirming to BS-5000/IS-4772 capable of supplying unbalanced load, alternator make: as specified in tender documents. (b) Engine : Multi/cylinder compression ignited, heavy duty, turbocharged, compact diesel engine water cooled through radiator with water pump hydraulic governing mechanism, all as per BS-5514/IS-3046, 1500 RPM class A1 governing/ control gauges. RPM/Hours meters etc suitable for generating application and capable of giving an output of 500 KVA for coupled alternator under NTP conditions, complete with following :- (i) Flywheel with housing ad mesh protection. (ii) Flexible coupling set directly mounted to engine and alternator with coupling guard. (iii) Air-cleaner dry type with vacuum indicator. (iv) Fuel pump FIP/CRDI and fuel piping 15mm MS Pipe with bends, flanges etc. (v) Fuel filter with water separator and filter element. (vi) Lub-oil filter with filter element. (vii) DC heavy duty starter 24 Volts. (viii) Maintenace free DC batteries 180 AH 24 Volts. (ix) Engine overspeed stop/trip switch. (x) Radiator with fan, thermostat. | 1 | EACH JOB | 61,88,805 ₹61.9 L | 51,23,282.6 ₹51.2 L | 52,41,000 ₹52.4 L | 41,49,000 ₹41.5 L |
| 1.01(xi) Dynamo/Alternator for battery charging. (xii) Corrosion inhibitor coolant. (xiii) Engine control panel electronic digital display type consisting of battery voltage indicator lub oil temp and pressure gauges, coolant water temp gauge RPM indicator cum hour meter with indications of battery charging failure, over speed, under speed, over current, under voltage, over voltage, over KW & control for phase sequence, monitoring, phase mising, common alarm, hooter out put etc complete. (xiv) Safety controls for alram due to high water temp (HWT) and low luib oil pressure (LLOP). (xv) Any other devices/ accessories recommended /supplied by the manufacturers as standard eqpt. Engine make: as specified in tender documents. (c) The engine and alternator will be coupled, aligned and mounted on a specially designed common base frame fabricated from MS channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads, Make Dunlop/ Polybond of reqd size and numbers as recommended by the OEM for mounting of 500 KVA DG Set. (d) Diesel tank of adequate capacity for 24 hrs continous run on full load, with caliberated scale (fuel level indicator) dip stick, fuel inlet/outlet, Air vent drain plug and intlet arragement for direct filling, incl suitabsle size gate valve in outlet, tank to be fitted at suitable height. (e) Acoustic encloser with canopy cover to be provided as per CPCB IV+ norms. | |||||||
| 1.02(f) PCC/RCC foundation complete as per OEM design. (g) Documents : Three sets of following documents:- Maintenance and operation manuals for engine and alternator, spare parts catelogue, warranty/test certificates, schematic diagrams of control pannels. (h) Misc items : List of tools and two years normal maintenance spares as per OEM recommended lists, duly prices item wise. Note: (i) Contractor shall satisfactorily conduct load tests of DG Set for 12 hrs incl run on 10% overload for 1 hr. (ii) Testing eqpt and man power required shall be arranged by the contractor at his own risk & cost. (iii) Fuel/ lubricats required for 1st load test shall be arranged by by the contractor at his own risk & cost. (iv) All connection with M & L for appropriate approved size XLPE armoured heavy duty 1100 V grade aluminium conductor cable from DG set to LT FPB for power and control cables are deemed to be included in quoted rates. | |||||||
| 2.00 | Supply, testing of four wheel trolley suitable for mounting of 500 KVA DG Set made of high tensile MS section. The Size of trolley 6.0 mtr x 3.0 mtr (+/- 10%). Trolley should have 4 wheels complete and the front two wheel will be rotated upto 160 degree with up/down movable tow hook. Tyre should be of suitable size and load capacity minimum 10 ton. Trolley to have parking and over run break, pulley, tow hook and leaf spring four sets & 2 nos axles. Super Structure of the trolley should be made of suitable size and top platform made of minimum 3 mm thick MS plate. Necessary arrangements for fixing of the DG set on top platform will be made suitably for 500 KVA DG set. Side support of MS angle minimum size100 mm x 100 mm x 10 mm will be provided based on the suitable size for fixing the DG set to avoid sliding. Reflective sticker both side of rear will also be provided for night movement. Minimum ground clearance should be 80 cm. Toolbox of size 100 cm x 50 cm and height 30 cm to be fitted at trolley floor and one set of spare wheel with tyre fitted with trailer complete all as directed by Engineer-In-charge. | 1 | EACH | 3,54,375 ₹3.5 L | 5,03,517.4 ₹5.0 L | 4,95,000 ₹5.0 L | 5,51,700 ₹5.5 L |
Updated dates
Tender Value
₹43.2 L
EMD Value
₹86,500
Closing Date
25 Oct 2025, 6:00 pmClosed
GE I R AND D GIRINAGAR PUNE 25
GE I R AND D GIRINAGAR PUNE 25
PROVISION OF TROLLEY MOUNTED DG SET 500 KVA AT MILIT GIRINAGAR PUNE 25
2025_MES_719323_2
GE I R AND D GNR TOKEN 34 OF 2025-2026
Open Tender
Electrical and Maintenance Works
270 days
GE I R AND D GIRINAGAR PUNE 25
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE I R AND D GIRINAGAR PUNE 25
₹86,500
Yes
8 Jan 2026
20 Sept 2025
27 Oct 2025
20 Sept 2025
25 Oct 2025
11 Oct 2025
20 Sept 2025 - 22 Sept 2025
Amount
Supplying Installing testing & commissioning diesel engine driven generating set 415 V, 3 Phase, 4 Wire as per BS 5514/IS-10002 of capacity continuous rating 500 KVA conforming to CPCB IV+/latest norms at NTP conditions with acoustic enclosure considering all derating factors and comprising of the following :- (a) ALTERNATOR : Closed type regulated with brushless self excitation 415 V, 3 Phase, 4 Wire, 50 HZ, 0.8 PF 1500 RPM with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load Anti vibration mounted drip proof type with class 'F' insulation, steel ball/roller bearings at both ends of the alternator shaft, with necessary controls as recommended by the manufacturer confirming to BS-5000/IS-4772 capable of supplying unbalanced load, alternator make: as specified in tender documents. (b) Engine : Multi/cylinder compression ignited, heavy duty, turbocharged, compact diesel engine water cooled through radiator with water pump hydraulic governing mechanism, all as per BS-5514/IS-3046, 1500 RPM class A1 governing/ control gauges. RPM/Hours meters etc suitable for generating application and capable of giving an output of 500 KVA for coupled alternator under NTP conditions, complete with following :- (i) Flywheel with housing ad mesh protection. (ii) Flexible coupling set directly mounted to engine and alternator with coupling guard. (iii) Air-cleaner dry type with vacuum indicator. (iv) Fuel pump FIP/CRDI and fuel piping 15mm MS Pipe with bends, flanges etc. (v) Fuel filter with water separator and filter element. (vi) Lub-oil filter with filter element. (vii) DC heavy duty starter 24 Volts. (viii) Maintenace free DC batteries 180 AH 24 Volts. (ix) Engine overspeed stop/trip switch. (x) Radiator with fan, thermostat.
(xi) Dynamo/Alternator for battery charging. (xii) Corrosion inhibitor coolant. (xiii) Engine control panel electronic digital display type consisting of battery voltage indicator lub oil temp and pressure gauges, coolant water temp gauge RPM indicator cum hour meter with indications of battery charging failure, over speed, under speed, over current, under voltage, over voltage, over KW & control for phase sequence, monitoring, phase mising, common alarm, hooter out put etc complete. (xiv) Safety controls for alram due to high water temp (HWT) and low luib oil pressure (LLOP). (xv) Any other devices/ accessories recommended /supplied by the manufacturers as standard eqpt. Engine make: as specified in tender documents. (c) The engine and alternator will be coupled, aligned and mounted on a specially designed common base frame fabricated from MS channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads, Make Dunlop/ Polybond of reqd size and numbers as recommended by the OEM for mounting of 500 KVA DG Set. (d) Diesel tank of adequate capacity for 24 hrs continous run on full load, with caliberated scale (fuel level indicator) dip stick, fuel inlet/outlet, Air vent drain plug and intlet arragement for direct filling, incl suitabsle size gate valve in outlet, tank to be fitted at suitable height. (e) Acoustic encloser with canopy cover to be provided as per CPCB IV+ norms.
Supply, testing of four wheel trolley suitable for mounting of 500 KVA DG Set made of high tensile MS section. The Size of trolley 6.0 mtr x 3.0 mtr (+/- 10%). Trolley should have 4 wheels complete and the front two wheel will be rotated upto 160 degree with up/down movable tow hook. Tyre should be of suitable size and load capacity minimum 10 ton. Trolley to have parking and over run break, pulley, tow hook and leaf spring four sets & 2 nos axles. Super Structure of the trolley should be made of suitable size and top platform made of minimum 3 mm thick MS plate. Necessary arrangements for fixing of the DG set on top platform will be made suitably for 500 KVA DG set. Side support of MS angle minimum size100 mm x 100 mm x 10 mm will be provided based on the suitable size for fixing the DG set to avoid sliding. Reflective sticker both side of rear will also be provided for night movement. Minimum ground clearance should be 80 cm. Toolbox of size 100 cm x 50 cm and height 30 cm to be fitted at trolley floor and one set of spare wheel with tyre fitted with trailer complete all as directed by Engineer-In-charge.
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3454064)
Vijaypower Generators Limited (BID ID -3454184)
M/S JVS ENGINEERING (BID ID -3451933)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
TENDER.pdf
Tender Documents • 0.60 MB
BOQ_819439.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid