Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.2 LAccepted-AOC B 17 SHRIRAM INDUSTRIAL ESTATE G D AMBEKAR ROAD WADALA MUMBAI CITY MAHARASHTRA 400031 | MUMBAI | MAHARASHTRA | 400031 | L1 | Accepted-AOC Being 1st Lowest | |
| 2 | L2₹20.3 L+₹4.3 L (27.0%)Rejected-Finance 702 A1 SHREE PRASAD TAWADEWADI SHREE DATTAGURU PARK KUMBHARWADA URAN DIST RAIGAD MAHARASHTRA 400 702 | URAN | RAIGAD | MAHARASHTRA | 400702 | L2 | Rejected-Finance Being 2nd Lowest | |
| 3 | L3₹21.2 L+₹5.2 L (32.7%)Rejected-Finance | L3 | Rejected-Finance Being 3rd Lowest | |
| 4 | L4₹22.2 L+₹6.2 L (38.7%)Rejected-Finance | L4 | Rejected-Finance Being 4th Lowest | |
| 5 | L5₹22.4 L+₹6.5 L (40.4%)Rejected-Finance 1501 BHAGWATI EMINENCE SAVITRIBAI PHULE MARG BESIDES R R PATIL GARDEN SECTION 13 NERUL E NAVI MUMBAI | RAIGAD | MAHARASHTRA | 400702 | L5 | Rejected-Finance Being 5th Lowest |
Tender Value
₹22.9 L
EMD Value
₹45,900
Closing Date
2 Aug 2022, 6:00 pmClosed
CWE KARANJA
CWE KARANJA NAVAL STATION KARANJA URAN RAIGAD - 400704
SPECIAL REPAIRS TO HT/ LT UG CABLE, REPLACEMENT OF HT FEEDER PILLAR BOX AND CONNECTED WORK SERVICES IN TUNIR AREA AT NAVAL STATION KARANJA
2022_MES_538169_1
84164-K/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
NAVAL STATION KARANJA
Please refer tender documents
8 documents required · 8 mandatory
₹500
GARRISON ENGINEER (NW) KARANJA
₹45,900
25 Aug 2022
14 Jul 2022
4 Aug 2022
14 Jul 2022
2 Aug 2022
28 Jul 2022
Amount
Supply, installation, testing and commissioning of 22kV, 630A, 16kA/3sec, 3Way Outdoor, Extensible motorised SCADA compatible RMU as per MSEDCL R-APDRP specification consisting of 2Nos. feeder with Load Break Switch and 1No. feeder with VCB. | <2LBS +1VCB+M> - Qty. – 1No. complete all as specified and as directed by Engr-in-charge. Each Incomer feeder with Switch consists of: (a) . Motorised 630A load breaker switch with built-in earth switch with full making capacity - 01 No (b) Mechanical position indicator. Switch ON/OFF/EARTHED- 1 No. (c) Live Cable Indication - 1 No. (d) Cable compartment cover interlocked with earth switch - 1 No. (e) Cable termination bushings suitable for 3 no. 1CX300mm2 XLPE cable - 03 Nos (f) 22kV Screened touch proof Cable termination kit with boots - 01 Set
(g) CTs of ratio 30/1A, 2.5VA, CL-1.0 (Metering core) - 01 Set (h) Multifunction meter - 01 No (j) NO/NC contact for: - 01 Set (i) Isolator ON/OFF (ii)Earth Switch ON/OFF (iii) Fault Indicator Operated (k) Command Output for: - 01 Set (i) Isolator Close (ii) Isolator Open (iii) FPI reset
Each Outgoing VCB feeder consists of: (a) Motorised 630A Vacuum Circuit Breaker with manual spring charging arrangement and manual close & open push buttons, ON /OFF indication and series trip coil for self powered relay & shunt trip coil for external tripping -01 No (b) Self powered Numerical O/C & E/F relay with CTs of ratio 30/1A, 2.5VA, 5P10 (Protection core) - 01 No (c) Manually operated 630A load breaker switch with built-in earth switch with full making capacity - 01 No (d) Mechanical position indicator. Switch ON/OFF/EARTHED - 01 No (e) Live Cable Indication - 01 No (f) Cable compartment cover interlocked with earth switch - 01 No
(g) Cable termination bushings suitable for 1no. 3CX300mm2 XLPE cable -03 Nos (h) 22kV Screened touch proof Cable termination kit with boots. - 01 Set (j) NO/NC contact for: - 01 Set (i) Breaker ON/OFF (ii)Relay operated. 1No. Metering Module as Bus PT (a) 03nos. Single Phase Potential Transformers having ratio 22kV/rt3:110V/rt3, 50VA, Class 1.0 Common Items per RMU (a) SF6 Gas Pressure indicator with auxiliary contacts. (b) 1 No. Handles for RMU (c) 1 No. Fault Passage Indicator with associated CT’s. (d) 1No. 500VA Auxiliary Transformer. (e) Battery & Battery Charger.
Supply, laying in repairs, in trenches /ducts, electric power cable (heavy duty) of size 3 x 120 sqmm with aluminium conductor suitable for 22 KV grade as per relevent IS including latest amendment for IS (ISI marked cable) testing, commissioning along with HT cable route indicator with GI strip 32x6mm, XLPE HT insulated, screened, earthed, PVC bedded, galvanised steel strip or wire armoured complete all as specified and as directed by Engr-in-charge. Notes: (a) Earth work, EHV cable cover, sand coushioning & GI pipe will be measured and paid seperately. (b) High voltage test to be conducted at site with suitable voltage before and after laying of HT cable and reading shall be recorded jointly and test report to be submitted in triplicate to the Engr-in-charge. The cost of the same shall be deemed to be included in the unit rate quoted above.
Excavation in trenches for not exc 1.5m wide and not exc 1.5m depth and getting out in soft /loose soil including taking out faulty cable /cable, cable covers and GI pipe complete all as specified and as directed by Engr-in-charge.
Removing excavated materials not exc 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and as directed by Engr-in-charge.
Returning filling in including spreading levelling watering and well ramming in layers not exc 25cm complete all as specified and as directed by Engr-in-charge.
Supply and lay sand cushioning to under ground HT cable complete all as specified and as directed by Engr-in-charge. Note: Only punned thickness shall be measured and paid separately.
Supply and laying reinforced precast concrete cable cover laid width wise factory made, class EHV type 1 with peak size 450x230x50mm complete all as specified and as directed by Engr-in-charge.
Laying only precast concrete cover of size 450x230x50mm complete all as specified and as directed by Engr-in-charge.
Material and labour for GI pipe light grade with all fittings complete laid in trenches for 100mm bore of pipe complete all as specified and as directed by Engr-in-charge.
Material and labour for heat shrinkable cable end termination joint including jointing kit outdoor type suitable for earthed 3 core 95/120 sqmm HT 22KV XLPE aluminium conductor cable and HV test after jointing and connecting up complete all as specified and as directed by Engr-in-charge.
Material and labour for PCC type C2, 1:3:6 (Using 40mm graded stone aggregate) in foundations, filling and mass concrete includings necessary form work complete all as specified and as directed by Engr-in-charge.
Material and labour for precast cable route indicator made out of cement concrete 1:2:4 type B-1, (Using 22mm graded stone aggregate) having 15 cm square shape at top and 30 cm square shape at bottom and total height of 100 cm casted as per direction of Engineer-in-Charge and grouted into PCC 1:2:4 type B-1, 50 cm below the ground level as per the site requirement including embosed with HT 22 KV cable and also painted with synthetic enamel paint and neccessary excavation and earth work in any type of soil complete all as specified and as directed by Engr-in-charge.
Sagar Electricals
Radha Engineering Services
Expert Electric Service And Stores
SREE HARITHA ASSOCIATES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .