Loading…
Loading…
Tender Value
₹2.0 Cr
EMD Value
₹4.0 L
Closing Date
22 Oct 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
90 days
Expenditure
Revenue
ELECT WORK
14 conditions · 13 needing a document upload
The Bidder's average annual turnover over the last three Financial Years (2023-24, 2024-25 and 2025-26) preceding the Financial Year in which the tender has been published must be a minimum of Rs.5,13,61,123/-. The bidder shall submit Certificate from a Chartered Accountant for Turnover of the Bidder for the stipulated financial years, based on audited balance sheets, as per 'Annexure 2: Financial Turnover of Bidder' of Standard Bid Document Part-I. Note: - i. If the balance sheet for the immediately preceding financial year has not yet been audited, the same shall be certified by the CA in the above certificate, and in such a case the Financial Turnover for the fourth preceding year shall be mentioned in the CA certificate and the same shall be consider for the eligibility criteria. ii. Unless otherwise stipulated in Standard Bidding Document Part-II, if a bidder has been in existence for less than three years, the requirement of average annual turnover as per audited balance sheet shall be calculated by dividing the total turnover of the bidder during the eligible period by three. iii. For the purpose of Annual Turnover, only the revenue from operations shall be considered. Other incomes such as interest, dividend etc. are excluded from the annual turnover. iv. Credentials of affiliated companies like Parent / Holding Company, Strategic Business Unit, Group Company, Subsidiary / Associate Company, Sister Company etc. will not be taken into consideration.
QUALIFICATION CRITERIA
The bidder shall submit Self Information as per Annexure 1 of CRIS Standard Bid Document Part-1 (SBD-1).
The bidder shall submit the Power of Attorney / Board resolution issued by the bidding entity in the name of the person so authorized to submit the bid. The bid should be submitted online by such authorized person only.
The Bidder must be a Private or Public Company or a Proprietorship, Partnership firm, LLP, Society/ Trust, or HUF etc. Based on the nature of entity the bidder to submit the requisite documents, as listed below: For Companies: Certificate of Incorporation under the Companies Act; For Partnership Firms / Limited Liability Partnership (LLP): Partnership Deed or Certificate of registration under the Indian Partnership Act / LLP Act; For Societies / Trust: Certificate of Registration with Registrar of Societies; For Proprietorship Firms and HUFs: i. Attested certificate from Bank(s) clearly indicating the date on which the Bank account was opened in the name of the Proprietorship firm / HUF (as applicable) which establishes the existence of the firm for the required period. ii. For Proprietorship Firm: A copy of the notarized affidavit on Stamp Paper declaring that the concern is a proprietary concern, and he is the sole proprietor of the Concern Or For HUF: A copy of notarized affidavit on a Stamp Paper by the Karta of the HUF (Hindu Undivided Family) declaring that the bidder is a HUF and he is the Karta of the HUF.
Bidder must have a current / valid GST Certificate. Bidder shall upload the GST certificate. Bidder shall upload GST certificate along with the bid.
The Bidder should have successfully completed / executed Similar Project / Work in last five Financial Years preceding the Financial Year in which the tender has been published, and current financial year (up to and including the date of publishing of this tender), hereinafter referred to as the specified period, having value as under- At least one project costing not less than Rs.80,37,590/- Or at least two projects each costing not less than Rs.50,23,494/- Or at least three projects each costing not less than Rs.40,18,795/- • Similar nature of work: The bidder must have successfully completed Supply, Installation, Testing and Commissioning (SITC) of Precision Air-Conditioning (PAC) units of minimum 8 TR capacity in a Data Centre in a single location or in multiple locations under one contract. 1.The Bidder shall submit CA certificate as per 'Annexure 3: Past Performance Details of Bidder' of Standard Bid Document Part-I, detailing projects that meet the relevant Project Experience criteria. 2. Only those Contracts / Purchase orders / Work Orders etc. (hereinafter collectively referred to as Contract) shall be considered towards Project / Work Experience which have been issued by: - a. Any entity (Department / Organization / Autonomous body / PSU/ Local Body/ Authority etc.) wholly or partially owned by State / Central Government Or b. A Private sector organization which is listed in the National Stock Exchange (NSE) or Bombay Stock Exchange (BSE) in India < and> has an average annual Turnover of INR 500 Crore (revenue from operations) & above during last three (03) financial years preceding the year of publishing of tender. (Listing / Turnover of affiliated companies like Parent / Holding Company, Strategic Business Unit, Group Company, Subsidiary / Associate Company, Sister Company etc. will not be taken into consideration). 3. Only those Contract (s) shall be accepted as Project / Work experience wherein the contract (s) have been placed on the bidder directly by an entity belonging to one of the above categories. 4. In case the contract being presented is a composite contract (i.e. it contains items other than the ones defined in the qualification criteria as similar work), only such line items shall be considered which qualify as per the definition of similar work mentioned in the contract. In such cases the value of such line items shall be indicated by the bidder in the relevant Attachment to Annexure 3 of Standard Bid Document Part-I. If the value of contract / line items qualifying as per the definition of similar work is not mentioned separately in such composite contracts/ line items, such contracts / line items shall not be considered towards fulfilment of project / work experience. (The remaining part of the condition is continue 1.5.1)
5. In case the bid is submitted on behalf of a Joint Venture / Consortium, the project experience requirements are to be met by any one of the members of the Joint Venture / Consortium. For clarity, it is stated that the project experience requirement cannot be fulfilled by summation of project credentials of the individual members of the JV/ Consortium. 6. If the purchaser seeks any clarification related to relevant project / Work experience certificates submitted by the bidder, the bidder shall not be permitted to submit any new Contract / Purchase order/ Work order, whose details are not already provided in the original bid. Any such new Contract / Purchase order/ Work order shall not be considered. 7. In case the bidder submits credentials flowing out of a Rate / Running Contract/ 1.5.1 Master Service Agreement etc., each supply order / purchase order shall be treated as a distinct contract. For clarity, it is stated that no two or more supply / purchase orders against the same rate / running contract / Master Service Agreement shall be clubbed for the purpose of fulfilment of this eligibility criteria. 8. Completed / Ongoing Works Completed Works: a. In case work is completed / executed during the relevant period, whether it started prior to the relevant period or within the relevant period, the contract value (original / amended) shall be considered for fulfillment of credentials. b. Ongoing Works: Ongoing works, i.e. the works which have not been completed before the end date of the relevant period shall not be considered towards fulfilment of this qualification criteria.
The Bidder shall submit Copies of Purchase Order (s) / Contract (s) / Work Order (s) (including all associated documents / Annexures) for all the projects/ works mentioned in the CA certificate. Bidders may please note that in case of non-submission of the copy of Purchase Order (s) / Contract (s) / Work Order (s), such contract may not be considered towards evaluation of the bidder w.r.t Project Experience criteria.
The Bidder shall submit copies of Satisfactory Completion Certificate(s)/ Performance Certificate (s) issued by the Purchaser / Consignee for all the projects mentioned in the CA certificate submitted. Bidders may please note that in case of non-submission of the copy of Completion Certificate(s)/ Performance Certificate (s), such contract may not be considered towards evaluation of the bidder w.r.t Project Experience criteria.
The Bidder shall submit a self- declaration of non-blacklisting as per 'Annexure 5: Declaration of Non-Blacklisting by Bidder' of Standard Bid Document Part-I.
The Bidder shall submit a self- declaration of non-blacklisting of all the OEMs as per 'Annexure 10: Declaration of Non-Blacklisting for OEM' of Standard Bid Document Part-I.
The Bidder shall submit a self- declaration of compliance to Land Border clause of Standard Bid Document Part-I as per 'Annexure 7: Certificate from Bidder for Compliance to Govt. of India Order for Countries sharing Land Border with India' of Standard Bid Document Part-I.
The Bidder shall submit a self- certification of compliance to Make in India Policy as per 'Annexure 6: Self Certification by Bidder for Make in India' of Standard Bid Document Part-I.
13 conditions · 2 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Bidders are advised to thoroughly read and understand General Instructions for E-Tenders, the CRIS Standard Bid Document (SBD) Part-I and the Special Conditions of Contract (i.e. Bid Part- II), before quoting the tender and the same shall be applicable to the tender. Submission of the bid shall be deemed as acceptance of all terms and conditions contained therein.
The rates quoted in the Schedule shall be inclusive of all additional items or works required, other than those specifically mentioned above, for the successful execution of the subject work. CRIS will not make any separate payment for any additional items or works required for the completion of the said work. The prices shall be inclusive of Goods and Services Tax, and the rates shall remain firm during the contract period.
Bidders shall quote for the Buy-Back of old PAC units under Schedule 'A'. They may either offer a negative value (as rebate) if they agree to lift the old PAC units, or quote "0" (zero) if they do not intend to take back the old equipment.
Final selection shall be made on the basis of the overall lowest cost considering combined value of "Schedule A" and "Schedule B" from amongst technically suitable bidders meeting the eligibility criteria specified in Clause-4 of e-Tender and technical specifications including technical requirements in Bid Part-II. For the purpose of commercial evaluation and ranking, the total all- inclusive price for the entire scope, including the buy-back value (if any), shall be considered.
Details of existing Precision AC (PAC) units proposed for buy- back:- a). 4 Nos. Precision Air-Conditioning (PAC) units, Make: Stulz, Model: IEC 5105A, commissioned in January 2017.
Handing Over of Old Equipment: - The existing PAC units shall be handed over to the successful bidder only after successful supply, installation, testing and commissioning of new PAC units, at CRIS office premises, Chanakyapuri, New Delhi-110021. The successful bidder shall be responsible for lifting and transportation of the old units from the CRIS premises at their own cost.
Condition of Old Equipment:- The old PAC units are offered on "as-is-where-is" basis, and no claim regarding condition, performance, or completeness shall be entertained after submission of bid.
CRIS reserves the right to accept or reject the buy-back offer, either in full or in part, at its sole discretion at the time of award, without assigning any reason. In such an event, the procurement of new PAC units shall proceed independently of the buy-back arrangement.
The Make in India policy as incorporated in the clause 12.4 of Standard Bid Document Part-I.
Supply, installation, testing and commissioning of Precision Air-Conditioning Units on buy-back basis, including associated civil works, for Data Centre Area 'D' at CRIS Office, Chanakyapuri, New Delhi - 110021, along with post-warranty Comprehensive Annual Maintenance for a period of four years.
2026_CRIS_ELECT_20~CRIS
2026_CRIS_ELECT_20
Open
Works - General
6 Months
New Delhi, Delhi
₹0
₹4.0 L
1 Oct 2026
1 Oct 2026
8 Oct 2026
84 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 1,61,29,174.36 | ||
| — | 10.00 | — | — | ||
| Supply of microprocessor-based, floor-mounted, bottom discharge (downflow) air- cooled DX type Precision Air Conditioning (PAC) unit of gross cooling capacity 9-10 TR. To ensure space efficiency within the data center, the overall dimensions of unit not exceeding to maximum dimensions of 900 mm (W) x 900 mm (D) x 2000 mm (H) and feature a robust double-skin side panel construction for thermal and acoustic insulation. The unit shall be complete with energy- efficient Digital Scroll Compressor or Inverter Scroll Compressor operating on refrigerant R-410A, including crankcase heater, vibration isolators and necessary safety controls, high-efficiency evaporator coil with hydrophilic coating, direct-driven EC motor with variable speed control. The matching air-cooled outdoor condensing unit must be "tropicalized" for North Indian weather conditions, featuring axial or an EC fan motor with an integrated speed controller. For environmental stability, the unit shall include an electrode or infrared-type humidifier, integrated electric heaters for dehumidification, a stainless-steel or corrosion-resistant condensate drain pan and a dedicated water leak detection sensor. The integrated microprocessor controller must feature a high-visibility display for real-time monitoring of date, time and set versus actual values for temperature and relative humidity, supported by an internal memory capable of logging at least 100 recent events with time and date stamps. The PAC unit shall be suitable for operation on 415 V ±10%, 50 Hz, 3 Phase, 4 Wire AC supply and designed for return air conditions of 22°C ±2°C and 45-55% RH, the outdoor condenser must be engineered to operate reliably at a peak ambient temperature of 45°C (with a recommended safety margin up to 48-50 Deg. Celsius), ensuring the condensing temperature does not exceed 57 Deg. Celsius. For seamless facility management, the system must support advanced sequencing logic (Lead-Lag) and provide native communication protocols for BMS compatibility, including Modbus, SNMP, or BACnet. | — | — | — | 1,13,28,000 | |
| — | 10.00 | — | — | ||
| Lifting, shifting, positioning along with installation, testing and commissioning of Precision Air-Condition unit (i.e. Indoor & Outdoor). This includes tile cutting for placement of MS stand for installation of indoor unit & installation of outdoor unit along with charging of refrigerant gas & oil duly vacuuming the AC system and leak testing. | — | — | — | 5,66,400 | |
| — | 250.00 | — | — | ||
| Supply of refrigerant R-410 for charging in Precision Air-Condition unit of Area 'D'. | — | — | — | 4,42,500 | |
| — | 250.00 | — | — | ||
| Supply laying, connecting and commissioning of interconnection of copper pipe pair of 18 Gauge (5/8" & 7/8" or as per manufacture guidelines for offered PAC) between the indoor & outdoor units, @ 25 Rmt per PAC unit of Area 'D'. | — | — | — | 11,50,500 | |
| — | 280.00 | — | — | ||
| Supply, laying, connecting and commissioning of interconnection armoured copper cable of size 2.5 sqmm 3 core (or as per manufacture guidelines for offered PAC) between indoor & outdoor units of Area 'D'. This includes all required accessories for laying of copper cable. | — | — | — | 1,13,988 | |
| — | 100.00 | — | — | ||
| Supply, laying, connecting and commissioning of 15 mm dia CPVC pipe for water inlet, of make Astral / Ashirvad / Supreme Industries, complete with all necessary fittings such as bends, tees, couplers, reducers, unions, valves, clamps, supports, solvent cement, etc., as required for proper installation. The pipe shall be insulated with 9 mm thick nitrile rubber insulation (Class "O"), including necessary adhesives, vapour barrier tape and finishing as required. The work shall include cutting, jointing, testing, commissioning and making good of walls/floors as required, complete in all respects as per site conditions and direction of Engineer-in-Charge. | — | — | — | 88,500 | |
| — | 100.00 | — | — | ||
| Supply, laying, connecting and commissioning of 40 mm dia CPVC pipe for drain outlet, of make Astral / Ashirvad / Supreme Industries, complete with all necessary fittings such as bends, tees, couplers, reducers, unions, valves, clamps, supports, solvent cement, etc., as required for proper installation. The pipe shall be insulated with 9 mm thick nitrile rubber insulation (Class "O"), including necessary adhesives, vapour barrier tape and finishing as required. The work shall include cutting, jointing, testing, commissioning and making good of walls/floors as required, complete in all respects as per site conditions and direction of Engineer-in-Charge. | — | — | — | 88,500 | |
| — | 10.00 | — | — | ||
| Design, fabrication and supply of adjustable MS stand (angle size 40x40x6 mm) suitable for indoor units of Precision Air Conditioning (PAC) systems, duly treated and painted with anti-corrosive paint, complete with vibration isolation pads and all necessary accessories for proper installation. | — | — | — | 84,960 | |
| — | 500.00 | — | — | ||
| Design, fabrication, supply and installation of MS structure with safety railing for mounting of outdoor units of new Precision PAC Unit-9 & Unit-10 and modification/strengthening of the existing MS structure to accommodate the new outdoor units, duly treated and painted with anti- corrosive paint, complete with vibration isolation pads and all necessary accessories. The MS structure shall be fabricated using C-Channels (75 x 40 x 5 mm), Angles (40 x 40 x 6 mm) and Flats/Strips (40 x 5 mm), as per site requirements and approved drawings. The scope shall also include all necessary civil works such as foundation, grouting, anchoring, and fastening for proper installation and stability of the structure, complete in all respects. | — | — | — | 1,15,050 | |
| — | 125.00 | — | — | ||
| Design, supply, fixing of Perforated type GI cable tray made out of 2mm thick GI sheet, bent in 'C' shape, size of 300mm (W) x 50mm (H), duly powder coated with adequate load bearing capacity. Complete with necessary supports, tees, elbows, bends, bolts and nuts, and any other associated accessories to complete the job on wall with angle iron bracket / hanging provision on roof with necessary anchor fasteners and fixing accessories for supporting the cable tray. | — | — | — | 1,99,125 | |
| — | 300.00 | — | — | ||
| Design, supply, fixing of Perforated type GI cable tray made out of 2mm thick GI sheet, bent in 'C' shape, size of 200mm (W) x 50mm (H), duly powder coated with adequate load bearing capacity. Complete with necessary supports, tees, elbows, bends, bolts and nuts, and any other associated accessories to complete the job on wall with angle iron bracket / hanging provision on roof with necessary anchor fasteners and fixing accessories for supporting the cable tray. | — | — | — | 3,71,700 | |
| — | 4.00 | — | — | ||
| Dismantling of the existing Precision Air-Conditioning unit along with all low-side materials and accessories. The scope includes careful removal, lifting, shifting and safe transportation of the existing Precision Air-Conditioning unit and all associated materials from the installed location to a designated place as directed by the Engineer-in-Charge. | — | — | — | 1,27,440 | |
| — | 10.00 | — | — | ||
| Supply, installation, testing and commissioning of factory-manufactured Heavy-Duty Raised Access Floor System complete in all respects, suitable for Data Centre environment. The system shall meet the following minimum performance criteria: Uniformly Distributed Load (UDL): Minimum 2100 kg per sq. mtr.; Concentrated/Point Load: Minimum 400 kg.; Pedestal Axial Load Capacity: Minimum 3000 kg. The raised floor system shall comprise the following: 1. Panels: 600mm x 600mm modular panels with high-density cementitious / calcium sulphate core or steel encapsulated construction. Panels shall be factory finished with anti-static High-Pressure Laminate (HPL) suitable for Data Centre applications and provided with PVC/ABS edge protection. Bottom side shall be reinforced with galvanized steel sheet. 2. Understructure: Adjustable heavy-duty galvanized steel pedestals with threaded head assembly and locking arrangement. Each pedestal shall have adequate base plate for epoxy fixing to the sub-floor. Pedestals shall be capable of withstanding axial load of minimum 3000 kg. 3. Stringers: Galvanized steel bolt-on stringers to provide lateral stability and enhance load distribution. 4. Installation: Installation over properly cleaned and prepared sub-floor. Pedestals shall be fixed with approved epoxy adhesive. The finished floor shall be level and aligned within permissible tolerances. Necessary cut-outs with grommets, edge trims, ramps, and accessories shall be included wherever required. 5. Accessories & Completeness: Including earthing/grounding provisions, cable cut-outs, perforated panels (if required), and all incidental materials, labour, tools, tackles and consumables required for complete installation. The work shall be carried out as per approved drawings, manufacturer's recommendations and as directed by Engineer-in-Charge. | — | — | — | 69,030 | |
| — | 10.00 | — | — | ||
| Design, supply, installation, testing and commissioning of return air dampers along with suitably sized motorized actuators, including linkage mechanisms, control wiring, integration with PAC unit control system and all necessary accessories for proper operation with the offered Precision Air Conditioning units. | — | — | — | 2,65,500 | |
| — | 35.00 | — | — | ||
| Supply, installation, testing and commissioning of powder-coated extruded aluminium floor grille of size 600 mm x 600 mm, suitable for installation in raised floor of data centre, having minimum 65%-75% free area, complete with G.I. opposed blade damper with smooth manual operating arrangement for air balancing. The grille shall be provided with an aluminium frame compatible with standard 600 x 600 mm raised floor system and designed to withstand a minimum load of 150 kg. Powder coating shall be of minimum 50 microns thickness. The item shall include all necessary fixing arrangements, fasteners and accessories for proper installation. | — | — | — | 1,98,240 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing and commissioning of active floor grille tile of size 600 mm x 600 mm, suitable for raised floor application in Data Centre, complete with integrated EC fan for airflow control with local display for monitoring of temperature and relative humidity (RH) and inbuilt temperature & RH sensors. The unit shall be capable of modulating airflow based on sensed conditions. The item shall include all necessary accessories, cabling and fixing arrangements for proper installation and operation. | — | — | — | 4,56,660 | |
| — | 1.00 | — | — | ||
| Code. No. 15.12 of CPWD DSR-2023 :- Dismantling doors, windows and clerestory windows (steel or wood) shutter ncluding chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead : Code No. 15.12.1 - Of area 3 sq. metres and below | — | — | — | 367.2 | |
| — | 15.00 | — | — | ||
| Code No. 14.4 of CPWD DSR-2023 : Making the opening in brick masonry including dismantling in floor or walls by cutting masonry and making good the damages to walls, flooring and jambs complete, to match existing surface including disposal of mulba/ rubbish to the nearest municipal dumping ground, all complete as per direction of Engineer-in-Charge. Code No. 14.4.1 - For door/ window/ clerestory window | — | — | — | 18,965.25 | |
| — | 1.00 | — | — | ||
| Code No. 4.2 of CPWD DSR-2023 : Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing: Code No. 4.2.3 -: 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources) | — | — | — | 9,895.2 | |
| — | 4.00 | — | — | ||
| Code No. 9.20 of CPWD DSR-2023 : Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. Code No. 9.20.2 -: 30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws | — | — | — | 12,671.8 | |
| — | 0.10 | — | — | ||
| Code No. 9.1 of CPWD DSR-2023 : Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately). Code No. 9.1.1 -: Second class teak wood | — | — | — | 14,294.97 | |
| — | 15.00 | — | — | ||
| Code No. 6.13 of CPWD DSR-2023 : Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Code No. 6.13.2 -: Cement mortar 1:4 (1 cement :4 coarse sand)Code No. 6.13 of CPWD DSR-2023 : Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Code No. 6.13.2 -: Cement mortar 1:4 (1 cement :4 coarse sand) | — | — | — | 16,857 | |
| — | 70.00 | — | — | ||
| Code No. 5.22 of CPWD DSR-2023 : Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Code No. 5.22.4 -: Hot rolled deformed bars | — | — | — | 7,549.5 | |
| — | 10.00 | — | — | ||
| Code No. 1.1.18 of CPWD DSR-2023 : Disposal of moorum/building rubbish/ malba/ similar unserviceable, dismantled or waste material by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 10 km for all lifts, complete as per directions of Engineer-in-charge. Note - item to be applicable in urban areas having directions for restricted hours for movement/ plying of load carrying motor vehicle of 3.5 cum or more. | — | — | — | 4,941 | |
| — | 120.00 | — | — | ||
| Code No. 21.1 of CPWD DSR-2023 : Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately): Code No. 21.1.1.2 -: Powder coated aluminium (minimum thickness of powder coating 50 micron) | — | — | — | 63,708 | |
| — | 20.00 | — | — | ||
| Code No. 26.45 of CPWD DSR-2023 : Supplying and installation of moisture resistant/fire resistant cement board as per standard sizes fixed with self-drilling / taping screws. Screws shall be of counter sunk rib head of 1.60 mm to 4 mm thick or 8 to 10 gauge of length varying from 25 to 45 mm. Code No. 26.45.2 -: Cement Bonded particle board 8 mm thick (Termite, Fire & Moisture Resistance), as per IS:14276 : 1995 | — | — | — | 19,839 | |
| — | 2.00 | — | — | ||
| Code No. 6.4 of CPWD DSR-2023 : Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Code No. 6.4.2 -: Cement mortar 1:6 (1 cement : 6 coarse sand. | — | — | — | 18,211.9 | |
| — | 60.00 | — | — | ||
| Code No.13.1 of CPWD DSR-2023 : CEMENT PLASTER (IN FINE SAND) : Code No. 13.1.1 -: 12 mm cement plaster of mix: 1:4 (1 cement: 4 fine sand). | — | — | — | 20,823 | |
| — | 60.00 | — | — | ||
| Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved brand and manufacturer and of required shade and colour (Code No. 13.41 of CPWD DSR-2023) : Code No. 13.41.1 -: New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre | — | — | — | 11,139 | |
| — | 30.00 | — | — | ||
| Code No. 14.1 of CPWD DSR-2023 : Repairs to plaster of thickness 12 mm to 20 mm in patches of area 2.5 sq.meters and under, including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete, including disposal of rubbish to the dumping ground, all complete as per direction of Engineer-in-Charge. Code No. 14.1.2 -: With cement mortar 1:4 (1cement: 4 coarse sand) | — | — | — | 16,815 | |
| — | 60.00 | — | — | ||
| Code No. 13.80 of CPWD DSR-2023 : Providing and applying white cement based putty of average thickness 1mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. | — | — | — | 9,363 | |
| — | 120.00 | — | — | ||
| Code No. 10.2 of CPWD DSR-2023 : Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. | — | — | — | 16,044 | |
| — | 1.00 | — | — | ||
| Code No. 4.2 of CPWD DSR-2023 : Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing: Code No. 4.2.5 -: 1:3:6 (1 Cement : 2 coarse sand (zone-III) : derved from natural source :4 graded stone aggregate 20mm nominal size derived from natural sources) | — | — | — | 9,311.4 | |
| — | 8.50 | — | — | ||
| Supplying, providing & fixing steel-based fire resistant/proof door with 02 hrs. rating, fire rating confirming to IS: 3614 (Part-2) 1992, BS: 476 and ISO:834 with all necessary fitting & fixtures including self-closing hinges & locking arrangement. Frames to be made of 1.6mm thick galvanized steel sheet & shutters of overall thickness 43mm - 46mm thick framed out of two outer skin panels of 1.25mm galvanized steel sheets having lock seam joints. Reinforcement shall also be provided at the top, bottom & locking areas. The infill material shall be mineral wood blanket confirming to IS:8183 to give required rigidity and effective acoustic and thermal insulation. The sheet metal used for both the frames & shutters are to be galvanized and to confirm to IS 277-1992 including one coat of Zink rich primer and two coats of fire-resistant synthetic enamel paint. The door frame cavity/box facing wall of all four sides shall be filled with cement concrete 1:2:4 (which shall be paid separately). The door frame has to be fixed with minimum 150mm x 12mm thick dash fastener 08 Nos. (i.e. 4 No.) on each sides. The contractor shall obtain and furnish necessary approval from TAC for the supplied material etc. (Hardwares for double leaf fire resistant doors with: Two pair of D-Handles 300mm, Two Door closer, One Tower bolt 300mmx10mm, one (Godrej/ Door King /Harrison) Dead Lock, S. S. Ball Bearing Hinges 08 Nos. Two clear fire-resistant wire glass Vision Panel of size 200mm x 300mm each with GI treated beading etc. All the gaps shall be filled with epoxy sealant of both the sides (inside & outside). Approximate Size of double leaf doors (1200/1120 x 2000/2100) m & that of door frame (0.125 x 0.075m). Complete with all labour, material, tools, transportation, etc. | — | — | — | 1,63,050.14 | |
| — | 250.00 | — | — | ||
| Supply, laying, connecting and commissioning of 1.1 KV grade 4 core 25 sqmm (or as per manufacture guidelines for offered PAC) of copper conductor PVC insulated L.T. armoured cable in raised way with clamping / saddling including proper termination, thimbling at both ends as per site requirement. | — | — | — | 3,13,375 | |
| — | 10.00 | — | — | ||
| Supply, installation, testing and commissioning of four polls (TPN) MCB-63 Amp. including enclosure. | — | — | — | 34,460 | |
| — | 4.00 | — | — | ||
| Buy-back of existing microprocessor-based, air-cooled Precision Air-Conditioning units of Stulz make, 24 TR capacity each, Model IEC 5105A, along with all associated low-side materials and accessories, excluding MS structure of outdoor units. | — | — | — | -3,18,600 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Bid Part II
ATTACHMENT
SBD Part I
ATTACHMENT
Layout_Plan_of_Area_D.pdf
ATTACHMENT
CRIS_SBD-I_19_05_2025_Version_1.1.pdf
ATTACHMENT
Bid_Part-II_Area_D_PAC_Replacement.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .