REPAIR REPLACEMENT AND IMPROVEMENT OF LT DISTRIBUTION SYSTEM BY REPLACEMENT OF UNSERVICEABLE LT CABLES AND SWITCH GEARS AT MILITARY HOSPITAL KHADKI AND 41 ARTY DIV UNDER GE (MH AND RH) KHADKI
2026_MES_784093_1
8815/E8
Open Tender
Civil Works
Item Rate
180 days
GE MH AND RH KHADKI
As per tender documents
8 documents required · 8 mandatory
₹500
GE MH AND RH KHADKI
Exempted
12 Aug 2026
12 Aug 2026
5 Sept 2026
12 Aug 2026
2 Sept 2026
26 Aug 2026
12 Aug 2026 - 2 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Disconnecting incoming and outgoing cable/busbar connections, taking out from the cradle and overhauling of manually/electrically operated, draw out type air circuit breaker of any make, 03 or 04 pole, 415 volts, AC, current rating 800 A, Make C &S complete all as specified and directed.
(a) Cleaning of dust, spider web, foreign particles etc.
(b) Removal of old grease from various parts.
(c) Cleaning of various parts with CRC-2-26.
(d) Check the tightness of all hardware.
(e) Replacement of damaged parts.
(f) Re-greasing and lubricating of all rotating, moving parts.
(g) Checking, setting and fault attending of spring charging mechanism operation.
(h) Checking, setting and fault attending of closing and tripping mechanism operation.
(j) Checking, setting and fault attending of breaker auxiliary switch contact healthiness.
(k) Checking of breaker operation in isolating / test and service position.
(l) Confirming of Insulation resistance value of each live part w.r.t earth.
Make:- C & S ACB Spares will be measured in relevant following items:- | 3 | Each | - | - |
| 1.01 | Supply in repair / replacement of Motor Auxiliary isolating contact assembly CS-AIH-2-116(4P), complete all as specified and directed. | 3 | Each | - | - |
| 1.02 | Supply in repair / replacement of Motor Compact UVT Coil6D- 16D/06N-2OS, CS-AUH-V-A-NA, complete all as specified and directed. | 2 | Each | - | - |
| 1.03 | Supply in repair / replacement of Motor Shunt Trip 6D-16D/06N-2OS,CS-AVH-S-116-MA, complete all as specified and directed. | 2 | Each | - | - |
| 1.04 | Supply in repair / replacement of Motor Closing Coil 6D-16D/06N-2OS,CS-AVH-S-116-MA, complete all as specified and directed. | 2 | Each | - | - |
| 1.05 | Supply in repair / replacement of Motor Arcing Contact, CS-ARCCONT-O8D, complete all as specified and directed. | 4 | Each | - | - |
| 1.06 | Supply in repair / replacement of Motor Main isolating Contact(Jaw Contacts) CS-MIC-O8D(50k), complete all as specified and directed. | 3 | Each | - | - |
| 1.07 | Supply in repair / replacement of Motor Cradle terminal for drawout AH ACB, complete all as specified and directed. | 2 | Each | - | - |
| 1.08 | Supply in repair / replacement of Motor Arc Chutes, complete all as specified and directed. | 2 | Each | - | - |
| 1.09 | Supply in repair / replacement of Spring Charging Motors (220 Volts AC / DC), complete all as specified and directed. | 3 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.41 MB
BOQ_878532.xls
BOQ • 0.37 MB
T8815.pdf
Tender Documents • 0.69 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].