| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.5 LAccepted-AOC FLAT NO 203 SEC 14 PLOT NO 142 SHIVSRUTI PARK APARTMENT E WING 1ST FLOOR MOSHI PRADHIKARAN TAL HAVELI DIST PUNE 412 105 | PUNE | MAHARASHTRA | 412105 | L1 | Accepted-AOC THE LOWEST TENDERER | |
| 2 | L2₹28.2 L+₹66,776.51 (2.42%)Rejected-Finance SADASHIV PHUGE NAGAR OPP SANDVIK FACTORY RADHIKA RESIDENCY F WING FLAT NO 7 PHUGEWADI PUNE 411 012 | PUNE | MAHARASHTRA | 411012 | L2 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 3 | L3₹34.1 L+₹6.6 L (23.8%)Rejected-Finance | L3 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 4 | L4₹35.6 L+₹8.0 L (29.1%)Rejected-Finance | L4 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 5 | L5₹40.0 L+₹12.4 L (45.2%)Rejected-Finance 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L5 | Rejected-Finance NOT THE LOWEST TENDERER |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
19 Apr 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE MH AND RH KHADKI
Military Engineer Services Garrison Engineer MH and Range Hills Range Hills Road Khadki, Pune 411003
MAINTENANCE OF LT FEEDER PANEL IN REPAIR/REPLACEMENT OF MARRIED ACCOMMODATION AND OTM ACCOMMODATION INCLUDING ALLIED WORKS AT AUNDH MILITARY STATION UNDER GE MH AND RH KHADKI
2025_MES_702947_1
8683/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE MH AND RH KHADKI
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MH AND RH KHADKI
₹80,000
Yes
5 Jun 2025
28 Mar 2025
21 Apr 2025
28 Mar 2025
19 Apr 2025
12 Apr 2025
28 Mar 2025 - 19 Apr 2025
Amount
Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 65x65x6mm with bottam of panel having minimum 60cm height from existing ground/floor level. (vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost.
Aluminium bus bar strips with proper colour code -04 No, 1000 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer ACB 4P 630 Amp, 415V, 50 KA Microprocessor release EDO type cat no- WX06N4PA(S) make C&S - 01 No Make :- C&S/L&T/Schineder/Legrand
Outgoing, MCCB 4P 320/315 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 01 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 200 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 04 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 63 amp, 415V, 16 KA Ics = 100 Icu Adjustable type - 02 No Make :- C&S/L&T/Legrand
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 65x65x6mm with bottam of panel having minimum 60cm height from existing ground/floor level. (vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost.
Aluminium bus bar strips with proper colour code -04 No, 1000 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer ACB 4P 630 Amp, 415V, 50 KA Microprocessor release EDO type cat no- WX06N4PA(S) make C&S - 01 No Make :- C&S/L&T/Schineder/Legrand
Outgoing, MCCB 4P 250 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 01 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 200 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 02 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 100 amp, 415V, 16 KA Ics = 100 Icu Adjustable type - 05 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 63 amp, 415V, 16 KA Ics = 100 Icu Adjustable type - 02 No Make :- C&S/L&T/Legrand
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 65x65x6mm with bottam of panel having minimum 60cm height from existing ground/floor level. (vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost.
Aluminium bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 400 Amp, 415V, 36 KA - 01 No Ics = 100 Icu Adjustable type - 01 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 200 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 03 Nos Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 160 amp, 415V, 25 KA, Ics = 100 Icu Adjustable type - 01 Nos Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 63 amp, 415V, 16 KA , Ics = 100 Icu Adjustable type - 02 Nos Make :- C&S/L&T/Legrand
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 65x65x6mm with bottam of panel having minimum 60cm height from existing ground/floor level. (vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost.
Aluminium bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 400 Amp, 415V, 36 KA - 01 No Ics = 100 Icu Adjustable type - 01 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 125 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 01 Nos Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 100 amp, 415V, 16 KA, Ics = 100 Icu Adjustable type - 05 Nos Make : C&S/L&T/Legrand
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 65x65x6mm with bottam of panel having minimum 60cm height from existing ground/floor level. (vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost.
Aluminium bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 400 Amp, 415V, 36 KA - 01 No Ics = 100 Icu Adjustable type - 01 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 160 amp, 415V, 25 KA, Ics = 100 Icu Adjustable type - 01 Nos Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 125 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 01 Nos Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 100 amp, 415V, 16 KA, Ics = 100 Icu Adjustable type - 02 Nos Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 63 amp, 415V, 16 KA , Ics = 100 Icu Adjustable type - 01 Nos Make :- C&S/L&T/Legrand
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
Note : (i) Electrical connection from switchgear to bus bar would be through copper strips of suitable size. (ii) The internal electrical connection for measuring instruments would be through multi-stranded PVC insulated copper conductor cables of suitable size. (iii) The termination of incoming and outgoing cable into and from switchgear would be through properly crimped aluminum lugs of suitable rating incommensurate with that of switchgear. (iv) Cable glands would be provided for incoming & out going cables in panels. (v) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (vi) The panel is to be fixed with Angle Iron Frame of size 65x65x6mm with bottam of panel having minimum 60cm height from existing ground/floor level. (vii) The operation of all MCCBs should be of Rotary handle type, the cost of rotory handles is deemed to be included in the quoted cost.
Aluminium bus bar strips with proper colour code -04 No, 500 A cap, insulator, nuts bolts etc complete.
Indicator Lamp-01 Set (Set of three)
Incommer MCCB 4P 400 Amp, 415V, 36 KA - 01 No Ics = 100 Icu Adjustable type - 01 No Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 125 amp, 415V, 25 KA Ics = 100 Icu Adjustable type - 01 Nos Make :- C&S/L&T/Legrand
Outgoing, MCCB 4P 100 amp, 415V, 16 KA, Ics = 100 Icu Adjustable type - 09 Nos Make :- C&S/L&T/Legrand
Connection with Aluminium bus bar strip duly insulated with coloured sleeves /stranded copper cable of suitable size with thimbles.
M & L in replacement Earthing complete with galvanized steel earth plate electrode 60 cm x 60cmx6 mm thick, buried directly in ground vertically (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5m below ground level , connected to 32x6 mm GI strip as earthling lead by means blots and nuts check nuts and washers of galvanized iron and connected to main switch board including watering arrangement with PCC chamber , MS funnel, wire gauge. CI cover with frame , 50 MM dia GI pipe light grade for protection of wire/strip etc including necessary excavation in any type of strata , returning, filling removal of soil outside MD land ,filling of charcoal and salt complete all as shown in electrical plate No. 3 of MES Sch Part I , connected to Earthing test point all as specified and directed on testing on completion.
Supply, installation and commissioning of advance maintenance free system based earthing comprising of following accessories (a) Set of 04 Nos 3000 mm long, 17.0 mm dia earth electrode made of 99.99% copper circular rods with connect copper strip and electrode with the help of copper brazzing of incoming copper strips of size 25 x 3 mm of length as per site requirement upto Bus bar as decided by Engr - in-Charge and distance between each copper earth electrode is minimum 3 Meter . (b) Copper bus bar of size (300 x 25 x 6)mm act as test point connect with copper nuts and bolts with post insulator.(Nuts/bolts as required is included in the cost). (c) Poly propylene earth pit cover of size 300 x 300 mm (with safe working load 2000 Kg) - 04 Nos (d) Copper bus bar of size (250 x 50 x 6)mm exothermically welded with main earth electrode (e) Each pit filled with earth enhancement compound /chemical (Magnesium sulphate) only (min 75 Kgs/pit) all as specified. (f) Required result of earthing less than 01 Ohm . If desired Ohmic value is not achieved then additional set of 1 No of 3000 mm long, 17.0 mm dia earth electrode made out of 99.9% copper rod with allied items, 01 x Pit cover, 01 x Sub bar as (d) above 75 Kg of chemical shall be provided by contractor without any extra cost to Govt. No price adjustment shall be made, if additional set is not required complete all as directed of Engr- in-charge (g) Necessary excavation work in any type of soil/strata, returning filling and removal of soil is included in the aquoted rates. (h) Site inspection for complete Earthing work is mandotry for the Contractor befour quoting the tender. No explanation/doubts will be entertained later. (j) Any damage done to govt property during the execution of work will be make good by the contractor at his own cost.
Supplying, laying, jointing, commissioning and testing XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable in replacement with stranded aluminium conductor 1100 volts grade confirming to IS-7098 (Part-I-1988) laid in trenches/ducts/wall / floor / pipes/ poles including cable glands and aluminium lugs of appropriate size, pvc sleeve etc complete all as directed by Enginner in -Charge for following sizes . Make :- Havells / Gloster / Finolex / Polycab
300 sq mm 3.5 core .
240 sq mm 3.5 core
185 Sqmm 3.5 core
150 sq mm 3.5 core
95 sq mm 3.5 core
70 sq mm 3.5 core
50 sq mm 3.5 core .
35 sq mm 3.5 core
25 sq mm 3.5 core
16 sq mm 4 core
NOTE :- Earth work , bricks , riddled earth , GI pipe for protection of cable will be measured & paid under under relevant items of schdule .
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation of poles stays laying of electric cables, pipes etc and getting out in soft/loose soil complete all as specified and directed.
All as per item no 10 but in hard/dense soil.
Removing excavated material soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed
Returning, filling in, including spreading, levelling watering and well ramming in layers not exceeding 25cm in soft/loose soil complete all as specified and directed.
M & L for riddled earth for cushioning to under ground electric cable including spreading , levelling and hand punning complete all as directed. Note - Punned thickness shall only be measured & paid
M& L for road cutting / foot path and making good with PCC 1:3:6 TYPE C-2 ( using 40 mm graded stone aggregate ) of 150 mm
Supply and laying un-reinforced precast concrete cable cover LV, Type I, flat, size 250mm x 150mm x 40mm for Under ground cable all as specified and directed.
Supply and laying GI tubes light grade, galvanized, 40 mm bore in repair ,laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as directed
All as per item no -17 but 80 mmm bore.
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size 25 to 50Sqmm 3.5/4 core cable complete all as directed .
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 70 up to 120 sq mm3.5/4 core cable complete all as directed .
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 150 to 185 sq mm 3.5/4 core cable complete all as directed .
Supply only straight through joint kit , heat shrinkable type suitable for LT UG electric cable 1100 volts grade of size from 240 to 300 sq mm 3.5/4 core cable complete all as directed .
M&L for cleaning of MES electric supply installations/campus by surface dressing or trimming of natural ground to remove small unequalities not exc 15 cm deep (including removing vegetation/ shrubs/brush wood/under growth) and carrying away the rubbish to a distance of not exc 50 mtr away complete at an interval of every 30 days for the various sub stations. Note: Spray of herbsite deemed included in quoted rate.
M/S kirpan Enterprises (BID ID -3284892)
M/s Harshal Traders (BID ID -3284810)
Priyanka Power line (BID ID -3284820)
Adinath Technical Services (BID ID -3284669)
Rama Electricals (BID ID -3284910)
Mahindra Electric Stores (BID ID -3283983)
SBS Enterprises (BID ID -3284678)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .