CWE DEOLALI
HQ CWE DEOLALI, ONSLOW ROAD, DEOLALI (MH) 422401
AS PER TENDER DOCUMENTS
2026_MES_796954_1
87443/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE SOUTH AHILYANAGAR
AS PER NIT
7 documents required · 7 mandatory
₹1,000
Yes
GE SOUTH AHILYANAGAR
₹1.3 L
Yes
2 Nov 2026
2 Nov 2026
7 Dec 2026
2 Nov 2026
30 Nov 2026
23 Nov 2026
3 Nov 2026 - 16 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling of U/S 11 KV Air break gang operated triple pole switches vertical/horizontal including insulators and operating mechanisum complete all as specified and directed . | 4 | Each | 100 | ₹400 |
| 2 | Dismantling and taking down cross-arms of M.S. channel or angle sections with nuts, bolts, washers etc complete all as specified and directed . | 5 | Qtl | 100 | ₹500 |
| 3 | Dismantling steel poles/ PCC Pole of any size (HT/LT) complete all as specified and directed by Engineer in Charge. | 8 | Each | 100 | ₹800 |
| 4 | Dismantling old existing ACSR conductor of any type/size all as specified and directed. | 3 | Qtl | 100 | ₹300 |
| 5 | Supply, install, testing, commissioning complete 11 KV Ring Main Unit for 5 Nos (02 for incoming and 03 Nos outgoing) breaker of capacity 630 Amps each, outdoor type, copper bus bar of suitable capacity and breaking capacity 25 kA with enclosure for mounting. 02 No Load break switch for incoming and 03 Nos outgoing SF6 Circuit Breakers with interlocking arragement as specified in IE Rules & for clearance, safety and operation inside the enclosure, CPRI approved including cable termination chamber. SF circuit Breaker shall be front access. rating for single SF6 circuit breaker are as follows:-
(Note: Rates shall be inclusive with 02 No Load break switch for incoming and 03 Nos outgoing SF6 Circuit Breakers)
Circuit breaker, Rated Current: 630A, closing and Tripping coil: 24V DC, Spring Charging motor : 230V AC, STC:21KA for 03 sec
BIL: 12/28/75 KVP
CT Ratio- 200-100/1A, cl 1
Core 1 : Burden-10VA, class: 1.0
Core 2 : Burden-10VA, class: 5P10
STC :25KA for 1Sec
BIL: 12/28/75KVP
Potential Transformer with 3.15A HT Fuse ( Fixed type)
PT Ratio : 11KV/RT3/110/RT3/110/3
Core 1 : Burden-50VA, class: 1.0
Core 2 : Burden-50VA, class: 3P
BIL: 12/28/75 KVP
V.F 1.2 are continuous & 1.9 for 8 hours | 1 | Each | 100 | ₹100 |
| 5.01 | Protection Relay
(i) 3 over current +1 E/F Relay (RS-485 communicable)
(ii) Protection 50,51, 50N.51N, 86
(iii) CT Secondary- 5A
(iv) Mounting : Flush mounting
(v) Aux supply : 24V DC in built
Master Trip Relay ( Hand Reset Electromechanical type)
Protection- 86
Mounting- Flush Mounting
Aux supply : 24V DC
Metering Equipment (Incoming & Outgoing)
Digital Multifunction Meter (RS-485-Communicable), Class-1.0, Cut out size 92x92, Aux Supply : 230V AC
Digital Voltmeter, Class 1.0, Cut out size 92x92, Aux Supply : 230V AC & 12V DC
Accessories
TNT Switch, Contacts: 02 NO & 2NC
Local Remote Switch, Contacts: 02 NO & 2NC
Space heater 100W
Thermostat Temperature Range: 30-90, 15A 3 Pin socket for 230 V AC Supply Current 1-A
Toggle switch, Push button for Trip circuit Supervision check, Contacts: 02 NO | - | - | - | - |
| 5.02 | TB for CT & PT circuit, Disconnecting type
Type KUTSD6
TB for control circuit, Non-Disconnecting type
Fuse control circuit, 8 window Annuniciator
Aux Voltage : 230V AC
Hooter, Aux Voltage : 230V AC
Battery Charger 5A 230V AC I/P & 24 V DC O/P
Battery 12 V DC, 7AH
Indication Lamp
Red colour lamp, 24 V DC : For Breaker ON
Green colour lamp, 24V DC : For Breaker Off
Blue colour lamp, 24 V DC : For Breaker Spring Charge
Amber colour lamp, 24 V DC : For Auto Trip
White colour lamp, 24 V DC : For Trip Circiut Supervision
Red colour lamp, 63.5 V AC : For R Phase Healthy
Yellow colour lamp, 63.5 V AC : For Y Phase Healthy
Blue colour lamp, 63.5 V AC : For B Phase Healthy
Breaker Rack in and out handle
Testing
Factory Tests shall be carried out in presence of Rep of Accepting Officer as per IEC standard-62271-100 | - | - | - | - |
| 5.03 | Following test reports for 03 Nos SF6 breaker shall be submitted before applying payments:-
(i) Insulation resistance test
(ii) Operation time test
(iii) Contact resistance test
(iv) Pre-insertion resistance (PIR) test (If applicable)
(v) SF6 gas leak test
(vi) High Voltage withstand test
(vii) Secondary test to ensure the proper functioning of the live line indicators, fault passage indicators and relay
(viii) Mechanical Operation Test
Notes :-
(i) PCC foundation for RMU as per OEM drawing and specifications shall deemed be included in quoted rate.
(ii) Factory inspection of RMU shall be carried out by Engineer in Charge, Contractor has to inform the same in advance to the Dept.
(iii) Pre-commissioning Inspection shall be carried out by EI/SEI of HQ CESC, Contractor has to arrange T&P for testing the same. | - | - | - | - |
| 6 | Supply, install, testing, commissioning complete 11 KV Ring Main Unit for 4 Nos (01 for incoming and 03 Nos outgoing) breaker of capacity 630 Amps each, outdoor type, copper bus bar of 50x10mm with rupturing capacity of 350 MVA and breaking capacity 25 kA with enclosure for mounting. 01 No Load break switch for incoming and 03 Nos outgoing SF6 Circuit Breakers with interlocking arragement as specified in IE Rules & for clearance, safety and operation inside the enclosure, CPRI approved including cable termination chamber. SF circuit Breaker shall be front access. rating for single SF6 circuit breaker are as follows:-
(Note: Rates shall be inclusive with 01 No Load break switch for incoming and 03 Nos outgoing SF6 Circuit Breakers)
Circuit breaker, Rated Current: 630A, closing and Tripping coil: 240V DC, Spring Charging motor : 230V AC, STC:26.3KA for 03 sec
BIL: 12/28/75 KVP
CT Ratio- 200-100/5-5A
Core 1 : Burden-10VA, class: 1.0
Core 2 : Burden-10VA, class: 5P10
STC :25KA for 1 Sec
BIL: 12/28/75 KVP
Potential Transformer with 3.15A HT Fuse ( Fixed type)
PT Ratio : 11KV/RT3/110/RT3/110/3
Core 1 : Burden-50VA, class: 1.0
Core 2 : Burden-50VA, class: 3P
BIL: 12/28/75 KVP
V.F 1.2 are continuous & 1.9 for 8 hours | 3 | Each | 100 | ₹300 |
| 6.01 | Protection Relay
(i) 3 over current +1E/F Relay (RS-485 communicable)
(ii) Protection 50,51, 50N.51N, 86
(iii) CT Secondary-5A
(iv) Mounting : Flush mounting
(v) Aux supply : 24V DC in built
Master Trip Relay ( Hand Reset Electromechanical type)
Protection-86
Mounting-Flush Mounting
Aux supply : 24V DC
Metering Equipment (Incoming & Outgoing)
Digital Multifunction Meter (RS-485-Communicable), Class-1.0, Cut out size 92x92, Aux Supply : 230V AC
Digital Voltmeter, Class 1.0,Cut out size 92x92, Aux Supply : 230V AC & 12V DC
Accessories
TNT Switch, Contacts: 02 NO & 2NC
Local Remote Switch, Contacts: 02 NO & 2NC
Space heater 100W
Thermostat Temperature Range: 30-90, 15A 3 Pin socket for 230 V AC Supply Current 1-A
Toggle switch, Push button for Trip circuit Supervision check, Contacts:02 NO | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.25 MB
BOQ_893924.xls
BOQ • 0.24 MB
87443TENDERDOCSALL.pdf
Tender Documents • 2.19 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .