| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.9 LAccepted-AOC 227 2 5TH B MAIN ROAD 2ND BLOCK HRBR LAYOUT KALYAN NAGAR BANASAWADI BANGALORE 560 043 | BENGALURU URBAN | KARNATAKA | 560043 | ₹37.9 L Quoted ₹38.0 L | L1 | Accepted-AOC Accepted |
| 2 | L2₹42.9 L+₹4.9 L (13.0%)Rejected-AOC 66 C O J R NAICKER ASWATHNAGAR SANJAYNAGAR P O BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | ₹42.9 L+₹4.9 L (13.0%) | L2 | Rejected-AOC Rejected |
Tender Value
Refer Docs
EMD Value
₹86,600
Closing Date
18 Sept 2024, 6:00 pmClosed
GE (AF) BANGALORE
GE (AF) BANGALORE, HQ TC AIR FORCE , BANGALORE - 560006
PROVISION OF FIRE RETARDANT DOORS AT AFNET AND FIRE RETARDANT FALSE CEILING IN STAND BY ICSC AND UPS ROOM AND CERTAIN MAJOR REVENUE AND MINOR WORKS AT HQTC BANGALORE
2024_MES_666586_1
8266/GE
Open Tender
Civil Works
Item Rate
180 days
GE (AF) BANGALORE
AS PER NIT
5 documents required · 5 mandatory
₹500
Yes
GE (AF) BANGALORE
₹86,600
25 Oct 2024
18 Jul 2024
25 Sept 2024
18 Jul 2024
18 Sept 2024
1 Aug 2024
19 Jul 2024 - 25 Jul 2024
Amount
Dismantling wall and ceiling boards (fibre, pulp, insulation, etc.,) or insulation boards/ slabs /blankets, any thickness, including cover fillets complete all as specified and as directed by Engr-in-charge.
Supply and fix for 5.5mm thick ceiling board with powder coated GI suspended ceiling with 9mm wide T section. The frame work comprises of main runner at 1200mm c/c. The last hanger at end of each main runner should not be greater than 450mm from wall. T channel 1200mm long cross way to be inter locked between main work at 600mm long cross to centrally between the 1200mm cross tees main T channel suspended with 6mm dia GI (upto 1200mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of GI flat 40x3mm size 60mm long and expansion hold fasteners 12.5mm dia 40mm long with following specifications complete all as specified and as directed by Engr-in-charge. (a) Ceiling board dimension 595x595mm (b) Weight - 5.94Kg/Sqm (c) Density - 1200Kg/Cum (d) Accoustics - 34 DB (e) Moisture resistance - Yes (f) Fire resistance - Yes (g) Thermal insulation - Yes
Taking down cement plaster on brick or stone walls, etc., including raking out joints, hacking for key, scrubbing down with water, etc., complete all as specified and as directed by Engr-in-charge.
Material and labour for rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:6, finished even and smooth with out using extra cement complete all as specified and as directed by Engr-in-charge.
Material and labour for 2 coats of distempering wall with distemper oil emulsion white or tinted over a coat of 1mm thick wall care putty including preparation of new surface complete all as specified and as directed by Engr-in-charge.
Material and labour for 2 coats of distempering wall with distemper oil emulsion white or tinted through mechnical means, over a coat of 1mm thick wall care putty, including preparation of old surface after complete removal of existing treatment complete all as specified and as directed by Engr-in-charge.
Taking down chowkhats or frames with shutters (without taking off shutter from the frame) wooden exc 1.5 sqm not exc 4 sqm each complete all as specified and as directed by Engr-in-charge.
S & F Fire Door of Size 1220 X 2135mm single door profile with 100 X 57 X 1.2mm frame shutter, 0.8 Hardware Doorset, SS single ball bearing butt hinges 101 X 76 X 3mm, clear glass of size 200 X 300mm Normal single door closure, FR 80 pull handle, TGDI D type 250mm Dead lock, ML 103 ET bolt in fill by material, honey comb finish, complete all as specified and directed.
S & F Fire door of Size 915 X 2135mm single door profile, 100 X 57 X 1.2mm frame shuttter, 0.8 Hardware Doorset, SS single ball bearing butt hinges 101 X 76 X 3mm clear glass of size 200 X 300mm Normal single door closure, FR 80 pull handle, TGDI D type 250mm Dead lock, ML 103 ET bolt in fill material honey comb finish, complete all as specified and directed.
Removing old door and finishing the wall with plastering in CM 1:4 and filling the gaps complete all as specified and as directed by Engr-in-charge.
Material and labour for packing server room with plastic sheet and bubble sheet complete all as specified and as directed by Engr-in-charge.
Supply and fix access floor panel of size 600x600x32mm of all mild steel casted construction with an enclosed bottom pan of 60 hemispherical cones and top plain sheet fuse welded at 124 locations and folded on all the four perimeters to achieve the greater strength of the edges. The overall thickness of the panel shall be 32mm. The panel after cleaning, degreasing, phosphating by 11 tank process is coated with 40–60 microns epoxy coat and is heated to achieve maximum adhesion to the panel surface and corrosion resistance. The inner empty core of the panel is injected with a light weight, fire retardant, non-combustible cementitious compound at high pressure to fill in all the crevices of the panel and ensures support of not less than 90% of the top surface area of the panel. The top finish of the panels shall be of vitrified tiles finish complete all as specified and as directed by Engr-in-charge. The panel shall have 4 locating corner holes with a self-capturing fastener which will remain within the panel and will not get lost. These fasteners are used for bolting the panel to the substructure to form a rigid monolithic smooth levelled floor.
Demolition of brickwork or stone/ boulder masonry, built in cement mortar or cement lime mortar including all quoins, arches, pillars, etc., but excluding ashlar facings, dresses stonework and precast concrete articles complete all as specified and as directed by Engr-in-charge.
Material and labour for precast cement concrete block type C-1 1:3:6 (Using 20mm graded stone aggregate) masonry with solid blocks, exc 10cm in width and setting in mortar 1:6 complete all as specified and as directed by Engr-in-charge.
Material and labour for two coats of cement paint over a coat of priming plastered and other surfaces with alkali resistant priming paint including preparation of new surfaces complete all as specified and as directed by Engr-in-charge.
Material and labour for 75mm thick cement concrete type C-2, 1:3:6 (Using 40mm graded stone aggregate) as in flooring, foot path, hard standing, plinth protection, bases of water tanks etc., complete all as specified and as directed by Engr-in-charge.
Material and labour for 25mm thick cement concrete type B-0, 1:2:4 (Using 12.5mm graded stone aggregate) as in flooring complete all as specified and as directed by Engr-in-charge.
Material and labour for non-skid ceramic coloured tiles 7 to 8mm thick (square/rectangular) area of each tiles exc 0.06 sqm but not exc 0.11 sqm floors etc., set and jointed in neat cement slurry over and including 15mm thick screed bed of CM 1:6 and pointed in white/ coloured cement to match complete all as specified and as directed by Engr-in-charge.
Supply and fix for powder coated anodised aluminium frame (minimum thickness of powder coating 50 micron) for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc., complete all as specified and as directed by Engr-in-charge.
Supply and fix for powder coated anodised aluminium door, window and ventilator shutters (minimum thickness of powder coating 50 microns), aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc., complete all as specified and as directed by Engr-in-charge.
Taking down carefully copper/ aluminium point wiring (light, fan, socket or power) complete including fittings and fixtures such as switches, ceiling rose, pendants, regulators, sockets, light fittings etc., removing materials to store for keeping in safe custody for taking credit and making good disturbed surfaces of walls, floors, etc., complete all as specified and as directed by Engr-in-charge.
Material and labour for point wiring with cable of PVC insulated FRLS copper multistranded conductor 1.5 sqmm 1100 volts grade in and including heavy grade PVC casing caping pipe ISI marked with all accessories and fixing arrangements on wall/ ceiling/ floor etc., including fixing top cover/ PVC junction boxes fixing on wall surface for housing switches /sockets /regulators etc., with and including 1.5 sqmm PVC insulated multistranded copper earth continuity conductor connecting to the common earth dolly etc., for the following complete all as specified and as directed by Engr-in-charge.
One light/ bell point controlled by one single pole 5 Amps switch.
One Ceiling fan point controlled by one single pole 5 Amps switch.
One 3 pin socket point 5 Amps on independent board.
One 3 pin socket point 5 Amps on same board.
All as per item No.22 here-in-before but using copper conductor 2.5 sqmm PVC insulated unsheathed FRLS cable with copper conductor size 2.5 sqmm PVC insulated unsheathed continuous earth continuity for 3 pin 15 amps switch socket outlet independently.
Supply and fix for modular type fan regulator upto 300 watts with 5 step speed control for fans any sweep 1200mm/ 1400mm complete all as specified and as directed by Engr-in-charge.
Supply and fix for PVC ceiling rose 65x50mm surface type with 3 terminals complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular switch one way 6 Amps, 230 volts complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular socket, 6 Amps 2/3 pin combined two module, 230 volts complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular socket, 6 A/16 Amps 2/3 pin combined two module, 230 volts complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular switch one way 16 Amps one module, 230 volts complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular white cover suitable with frame 1/2 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular white cover suitable with frame 3 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular white cover suitable with frame 4 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular white cover suitable with frame 6 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular metal flush board 1/2 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular metal flush board 3 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular metal flush board 4 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular metal flush board 6 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for LED lights fitting 4 feet, 1X20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by Engr-in-charge.
Supply and fix for flame proof LED luminaire 600x600mm, 35/36 watt, 220V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders and LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed by Engr-in-charge.
Taking down ceiling/ exhaust fan circulators, sealing cable end, dismantaling blades, and removing fan including painting and refix the same including connecting up and provision of cable from ceiling rose or connector to fan complete all as specified and as directed by Engr-in-charge.
Supply and fix for single pole and neutral enclosure with a two pin and earth plug and socket with one double pole MCB for geyser complete all as specified and as directed by Engr-in-charge.
Supply and fix for sub main wiring with two single core PVC insulated cable with copper conductor multistranded 1100 volts grade 4 sqmm in and including PVC casing and caping and accessories and fixing arrangements fixed to surface on wall, floor or ceiling etc., including 4 sqmm PVC insulated multistranded copper earth continuity conductor and connecting to main earth dolly complete all as specified and as directed by Engr-in-charge. Note: One run of earth continuity conductor, one run of PVC conduit and two run of copper conductor together taken as one length for measuring unit length.
Supply and fix for sub main wiring with two single core PVC insulated cable with copper conductor multistranded 1100 volts grade 6 sqmm in and including PVC casing and caping and accessories and fixing arrangements fixed to surface on wall, floor or ceiling etc., including 6 sqmm PVC insulated multistranded copper earth continuity conductor and connecting to main earth dolly complete all as specified and as directed by Engr-in-charge. Note: One run of earth continuity conductor, one run of PVC conduit and two run of copper conductor together taken as one length for measuring unit length.
Supply and fix for MCB DB TPN 6 ways, single door type complete all as specified and as directed by Engr-in-charge.
Fixing only MCB SP 6 to 32 Amps 240 volts 10 KA rupturing capacity complete all as specified and as directed by Engr-in-charge.
Supply and fix for MCB SP 6 to 32 Amps 240 volts 10 KA rupturing capacity complete all as specified and as directed by Engr-in-charge.
Fixing only MCB TP 63 Amps 415 V 10 KA rupturing capacity complete all as specified and as directed by Engr-in-charge.
Supply and fix for MCB SPN 32 Amps 240 volts 10 KA rupturing capacity complete all as specified and as directed by Engr-in-charge.
Supply and fix for modular bell push 6A 1 module complete all as specified and as directed by Engr-in-charge.
Supply and fix for buzzer, ding dong AC, 230 volts, single pole complete all as specified and as directed by Engr-in-charge.
Supply and fix for sirens electronic type horizontal single stage continuous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5m with sound output variation of + 5 DB 500m range complete all as specified and as directed by Engr-in-charge.
Supply and fix for cable with copper conductor PVC round sheathed (flexible) industrial cable 3 core 2.5 sqmm complete all as specified and as directed by Engr-in-charge.
Excavation in trenches not exc 1.5m wide and exc 1.5m in depth or part there of in soft/loose soil and getting out for laying of underground cables/ pipes and foundation for poles etc., complete all as specified and as directed by Engr-in-charge.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cms complete all as specified and as directed by Engr-in-charge.
Removing excavated materials not exc 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and as directed by Engr-in-charge.
Suplly, laying and testing in trenches/ on ground/ on wall, jointing and testing galvanised steel water tubing IS-1239 marked, medium grade, including all necessary pipe fittings/ accessories like sockets, unions, tees, elbows etc., of the under mentioned sizes complete all as specified and as directed by Engr-in-charge.
80mm dia
50mm dia
40mm dia
32mm dia
25mm dia
20mm dia
Supply and fix for gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed 50mm dia bore complete all as specified and as directed by Engr-in-charge.
Supply and fix for gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed 40mm dia bore complete all as specified and as directed by Engr-in-charge.
Supply and fix for gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed 32mm dia bore complete all as specified and as directed by Engr-in-charge.
Supply and fix for gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed 25mm dia bore complete all as specified and as directed by Engr-in-charge.
Supply and fix for gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed 20mm dia bore complete all as specified and as directed by Engr-in-charge.
Supply and fix fo gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed 15mm dia bore complete all as specified and as directed by Engr-in-charge.
Supply, install, testing and commissioning of submersible open well pump set 65X50mm dia outlet electric driven of capacity 3 HP, 3 phase, 415 volt, 50 Hz, AC supply complete all as specified and as directed by Engr-in-charge.
Supply, install, testing and commissioning of DOL delta starter in sheet steel enclosure type for motor rating, 3/2 HP, 3 phase, 415 Volt, 50 Hz, AC supply complete all as specified and as directed by Engr-in-charge.
Supply and fix for GI ring 32mm, 6 ft, dia with 54 socket complete all as specified and as directed by Engr-in-charge.
Supply and fix for GI ring 25mm, 3 ft, dia with 27 socket complete all as specified and as directed by Engr-in-charge.
Supply and fix for centre jet nozzle 25mm dia complete all as specified and as directed by Engr-in-charge.
Supply and fix for SS 304 under water LED light RGB complete all as specified and as directed by Engr-in-charge.
Supply and fix for LED driver and LED controller for under water light fittings in suitable enclosure complete all as specified and as directed by Engr-in-charge.
Material and labour for flat 3 core PVC insulated, submersible multistranded copper conductor cable of size 2.5 sqmm including in PVC conduit and neccessary connections complete all as specified and as directed by Engr-in-charge.
Material and labour for round cable 4 core PVC insulated, submersible multistranded copper conductor cable of size 2.5 sqmm including in PVC conduit and necessary connections complete all as specified and as directed by Engr-in-charge.
Supply, install, testing and commissioning of suction pumps set 40x40 dia outlet electric driven of capacity 1.5 HP 1 phase, 233 volt, 50HZ, AC supply complete all as specified and as directed by Engr-in-charge.
Material and labour for plate earthing for substation equipments (Transformer, lighting arrestor and feeder pillar box) complete with galvanised mild steel plate electrode 600x600x6mm thick buried directly in ground vertically (in earth pit not less than 2.25m below normal ground level) with the top edge of the earth plate at a depth not less than 1.5m below normal ground level, the earth electrode surrounded by adequate quantity of charcaol dust and salt to a packed thickness of 15 cm on all sides and including GI earth strip 32x6mm bolted (with GI nuts, bolts and check nuts) and riveted to earth plate at one end and connected to metallic body of HT/LT equipments etc., at the outer, earth strip encased in and including 50mm bore of GI grade pipe with all fitting from top of electrode to body of equipments fixed with and including 25x6mm flat iron clamps, bolts, nuts and washer and also providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-O (Using 12mm graded crushed stone aggregate) and RCC cover shown in electrical plate No 5 of SSR Pt-I complete all as specified and as directed by Engr-in-charge. Note: Quoted rate includes include necessary excavation and earthwork.
Material and labour for sand cushioning to under ground cable dry river sand for protection of cable 8cm thick before laying of cable and 15 cm thick after laying and stretching the cable below the bricks/ PCC covers, punning of sand using suitable T&P complete all as specified and as directed by Engr-in-charge. Note: Punned thickness of sand i.e 18 cm to be consider for measurement purpose.
Supply and laying for precast cable cover protection of UG cables of size 250x150x40mm laid in trenches complete all as specified and as directed by Engr-in-charge.
Supply and laying cable XLPE insulated screened PVC bedded, galavanised steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sqmm 4 core complete all as specified and as directed by Engr-in-charge.
Supply and fix for sluice valve, with iron wheel head, screwed both ends for iron pipe and fixed 65mm dia bore complete all as specified and as directed by Engr-in-charge.
Supply and fix for Non return valve 50mm dia bore complete all as specified and as directed by Engr-in-charge.
Supply and fix for foot valve of 65mm dia bore complete all as specified and as directed by Engr-in-charge.
Material and labour for wiring for circuit/ submain wiring alongwith earth wire with 2x4 sqmm + 1x4 sqmm of FRLS PVC insulated copper conductor, single core cable in concealed non metallic rigid PVC conduit medium grade ISI marked of appropriate size complete all as specified and as directed by Engr-in-charge.
Material and labour for plain cement concrete 1:2:4 type B-1 (Using 20mm graded crushed stone aggregate) as in foundation, filling and mass concrete in foundation of poles with necessary plastering work complete all as specified and as directed by Engr-in-charge.
Supply and laying in trenches /laid in floor /duct /drawn through conduit XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 50 sqmm 3.5 core complete all as specified and as directed by Engr-in-charge.
Supply and laying in trenches /laid in floor /duct /drawn through conduit XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100V grade with aluminum conductor of cross sectional area 70 sqmm 3.5 core complete all as specified and as directed by Engr-in-charge.
Material and labour for 50mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath, etc., including flat iron clamps-02 Nos of size 50x6mm, with nuts, bolts and washers complete all as specified and as directed by Engr-in-charge.
Material and labour for boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4mpa working pressure complete all as specified and as directed by Engr-in-charge.
Supply and install on load changeover switch 415 Volt in sheet metal enclosure 4 pole of capacity 125 Amps including connecting up incoming/ outgoing cables connection with suitable lugs and testing complete all as specified and as directed by Engr-in-charge.
Supply and fix for sheet metal enclosure for DB's double door TPN 6 ways when MCBs to be used single pole and neutral, deep drawn with 200 Amps rated copper bus bar 415 V complete all as specified and as directed by Engr-in-charge.
Supply and fix for MCB TPN, 100 Amps, 415 V, C- series with breaking capacity of 16 KA complete all as specified and as directed by Engr-in-charge.
Supply and fix for sub main wiring with two single core FRLS PVC insulated cable with copper conductor multistranded 1100 volts grade 6 sqmm in and including non-metallic rigid PVC conduit and accessories and fixing arrangements fixed to surface on wall, floor or ceiling etc including 6 sqmm PVC insulated multistranded copper earth continuity conductor and connecting to main earth dolly complete all as specified and as directed by Engr-in-charge. Note: One run of earth continuity conductor, one run of PVC conduit and two run of copper conductor together taken as one length for measuring unit length.
Supply and fix for PVC cable loop box, size not less than 200x140x95mm, out door type, IP 65 including 4 Nos aluminium bus bar of size 25x5mm mounted on porcelain insulators with one MCB SP 6 Amps 230 volts connected to street light fitting submain wire and using FI clamps of size 20x3mm for fixing of PVC cable loop box with pole, including nuts, bolts and washers and connecting the cables to bus bars with using suitable size GI nuts, bolts and washers and aluminum lugs etc., complete all as specified and as directed by Engr-in-charge.
Material and labour for earthing complete with galvanized steel earth plate electrode 600x600x6mm buried directly in ground vertically to a depth not less than 2.25m below normal ground level (with top edge of earth plate not less than 1.5m below ground level) connected to GI strip 32x6mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES schedule Part-I (2009) with connected to earth test point and to main switch board, LT panel etc., with and including adequate quantity of charcoal dust and common salt around earth plate, PCC 1:3:6 type C-1 (Using 20mm graded stone aggregate) for earth pit with precast RCC (1:2:4) type B-1 (Using 20mm graded stone aggregate) 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle, GI light grade watering pipe 20mm dia with funnel and wire mesh and 40mm dia GI light grade earth lead protection pipe complete all as specified and as directed by Engr-in-charge. Note: The unit rate includes main earthing lead GI earth strip of size 32x6mm with 40mm dia GI light grade earth lead protection pipe from earth electrode to test point upto 7.5m.
Supply, installation, commisioning and testing weather proof bus bar chamber 600x450x300mm made out of 2mm thick CRCA steel sheet and 40x5mm angle iron frame suitable for mounting 0.5m above ground level with locking arrangements including provision of 4 Nos aluminium busbar of 400 Amps rating mounted on insulated frames 2 Nos including connecting up incoming and outgoing cables complete with glands, lugs including painted with two coats of powder coated paint over a coat of red oxide primer, including necessary PCC 1:3:6 type C1 in foundation for mounting complete all as specified and as directed by Engr-in-charge.
Supply, installation, commisioning and testing outdoor type LT panel made out of mild steel CRCA sheet of 3.15mm thick with angle iron frame of size 40x40x6mm for mounting and 0.5m above ground level with canopy top, two side ventilators, front and back openable door hinged, double door shutters with locking arrangement (including lock and key), weather and vermin proof IP 65 suitable for operation on 440 volts, 50Hz, 3 Phase 4 wire AC supply including separate bus bar chamber for incoming side MCCB connection and aluminium bus bar of suitable size 4 Nos mounted on hygroscopic insulators all prewired with suitable size of copper conductor cable including painted with two coats of powder coated paint over a coat of red oxide zinc chrome primer on outside surface and two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer on internal surfaces and providing necessary foundation /platform of the LT panel with PCC 1:2:4 type B2 including provision of lugs and cable gland for housing with the following fitment accessories complete all as specified and as directed by Engr-in-charge. Incoming (a) MCCB 4 Pole, 100 Amps, 415 volt of breaking capacity not less than 35 KA -1 No. (b) Digital type ammeter composite type with suitable CT, 0-200 Amps - 1 No. (c) Indicator lamp LED type set of three (R, Y, B) - 1 No. (d) Digital type voltmeter composite type with, 0-500 Volts - 1 No. Outgoing (a) MCB SPN 40 A 'C' curve, 415 V, 10 KA, 50 Hz, AC - 06 Nos. (b) MCB TPN 63A 'C' curve, 415 V, 10 KA, 50 Hz, AC - 01 No.
Supply and laying in trenches /laid in floor /duct /drawn through conduit XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100 V grade with aluminum conductor of cross sectional area 95 sqmm 3.5 core with lugs complete all as specified and as directed by Engr-in-charge.
Supply and laying in trenches /laid in floor /duct /drawn through conduit XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured heavy duty electric cable 1100 V grade with aluminum conductor of cross sectional area 120 sqmm 3.5 core with lugs complete all as specified and as directed by Engr-in-charge.
Material and labour for 80mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc., including flat iron clamps-02 Nos of size 50x6mm, with nuts, bolts and washers complete all as specified and as directed by Engr-in-charge.
Supply and fix for on load changeover switch 415 Volt in sheet metal enclosure 4 pole of capacity 200 Amps including connecting up incoming/ outgoing cables connection with suitable lugs and testing complete all as specified and as directed by Engr-in-charge.
Supply and fix for sheet metal enclosure for DB's double door TPN 8 ways when MCBs to be used single pole and neutral, deep drawn with 200 Amps rated copper bus bar 415 V complete all as specified and as directed by Engr-in-charge.
Cutting existing steel tubing for alterations or additions (each cut measured) of the following sizes complete all as specified and as directed by Engr-in-charge.
Screwing existing steel tubing for alterations or additions (or lengthening screw on pipe to form connector) of the following sizes complete all as specified and as directed by Engr-in-charge.
Taking up or down steel tubing and connections, including cleaning for refixing or removal to store complete all as specified and as directed by Engr-in-charge.
OM ENTERPRISES (BID ID -3087775)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .