diesel generators- DG Sets Experience with Gov. Required 3 Year (s) Diesel Generators- DG Sets ( 1 ) Technical Specifications Specification Specification Name Values Allowed Values OUTPUT CAPACITY RATING/PHASE Nominal Rated Capacity (KVA) 600 3.5
5
7.5
10
15
20
25
3 0
40
62.5
82.5
100
125
160
180
200
250
320
380
400
500
600
750
5 0
140 No of Phase Three Phase Single phase
Three Phase ENGINE Make of Engine KOEL GREEN KIRLOSKAR N/A Model Number of Engine DV12TA G1 N/A Capacity of Engine (cc) 23880 N/A Engine Power (kWm) 532 N/A ISI Marking to IS :10001 for engine false N/A BIS license No
if applicable 0 N/A Type of Engine cooling Liquid Cooled Air Cooled
Liquid Cooled Type of governer Electronic Array
Array Class of governer A1 Array
Array
Array 1/4 Number of cylinders (nos) 12 N/A No of Strokes (nos) 4 N/A Rated RPM of Engine (RPM) 1500 1500
3000 Overload capacity for one hour for every 11 hours continuous running at full load (%) 10 N/A Specific Fuel Consumption (gm/kWh) 221 N/A Starting voltage (volt) 24 N/A ALTERNATOR AC GENERATOR(ALTER NATOR) Make KOEL GREEN N/A AC GENERATOR(ALTER NATOR) model Number KG354L1 N/A Rating of AC Generator (KVA) 600 N/A Power Factor of AC generator 0.8 N/A Efficiency at rated Power factor at 75% of full Load 95.2 N/A Compliance of Alternator to IS:13364(part-1) Yes N/A Type of alternator Brushless N/A Voltage Regulation Grade VG 3 N/A Alternator IP Rating IP 23 N/A Class of Insulation H N/A CONTROL PANEL Control Panel AMF Manual
AMF IP Rating of Control Panel IP 53 N/A ACOUSTIC ENCLOSURE Sheet Thickness 1.6 1.6
1.8
2
1.2 Thickness of Foam 50 N/A Density of Foam for sound insulation 28 N/A Noise level at 1 meter (dB) 75 N/A BATTERY Battery Type & Specification Low Maintenance free to IS: 14257 for high cranking performance N/A Battery capacity (Ah) 180 N/A 2/4 No of batteries 2 N/A TEST REPORTS Availability of Type test report for Engine from Central govt/NABL/ILAC accredited laboratory No N/A Test Report number and date(Engine) 00 N/A Name and address of laboratory(Engine) 00 N/A Availability of Type test report for Alternator from Central government/NABL/ILAC accredited laboratory Yes N/A Test Report number and date(Alternator) 142091 N/A Name and address of laboratory(Alternator) 29/12/2011 N/A DG set meet requirements of Enviro nmental(Protection) Rules 1986
in respect of noise and emission norms
as described in STC Yes N/A WARRANTY INSTALLATION & COMMISSIONING Warranty 1 Installation & Commissioning With Installation With Installation
Without Installation Agreed to STC of the Product Yes N/A * Bold specifications are the golden parameters. Consignees and Quantity S.No. Consignee Address Quantity Delivery Days 1 Shyamal Mukherjee 826015
Barwa Road Campus 1 15 EMD Advisory Bank HDFC Bank EMD Percentage(%) 2.00 EMD Amount 89180 ePBG 3/4 Advisory Bank State Bank of India ePBG Percentage(%) 5.00 Duration of ePBG required (Months). 12