Garrison Engineer (East) Mathura
Garrison Engineer (East) Mathura
REPAIR/MAINTENANCE AND IMPROVEMENT TO MAIN RECEIVING STATION AND CONNECTED FEEDER AND LT ELECTRICAL DISTRIBUTION SYSTEM IN THE AOR OF GE EAST MATHURA
2026_MES_768075_2
1584/E8
Open Tender
Electrical and Maintenance Works
180 days
GE (E) Mathura
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (E) Mathura
₹90,000
Yes
3 Jul 2026
3 Jul 2026
17 Jul 2026
3 Jul 2026
15 Jul 2026
9 Jul 2026
3 Jul 2026 - 9 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Excavating in trenches, n exc 1.5 m wide and more than 1.5 m n exc 3.0 m in depth; for foundation, laying of cables etc. Or for shafts, wells, cesspits, manholes, pier holes, etc. N exc 10 sq m on plan and n exc 3.0 m in depth and getting out complete all as specified and directed | - | Cum | - | - |
| 2 | M&L for PCC 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed by Engr in Charge. | - | Cum | - | - |
| 3 | M&L for PCC 1:3:6 type C-2 using 40mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed by Engr in Charge. | - | Cum | - | - |
| 4 | M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate as in coping complete all as specified and directed by Engr in Charge. | - | Cum | - | - |
| 5 | Excavating in trenches not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide for foundation, laying of cables and getting out in soft/loose soil all as specified and as directed by Engr-In-Charge. | 533 | Cum | - | - |
| 6 | M&L for sand cushioning to under ground cable in trenches in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified and directed by Engr in charge.
Note:- Measurement shall be taken after gentling puning of sand. | 111 | Cum | - | - |
| 7 | Supply and laying PCC cable cover class HV type 1 flat size 300 mmx180mmx40mm complete all as specified and directed by Engineer-in-charge. | 3,164 | Each | - | - |
| 8 | Supply and laying PCC cable cover class LV type 1 flat size 250mmx150mmx40mm complete all as specified and directed by Engineer-in-charge. | 7,933 | Each | - | - |
| 9 | Returning, filling in including spreading, levelling, watering and well ramming excavated soil in layers not exceeding 25 cm thick each , filling back in trenches after cables have been laid and tested complete all as specified. | 363 | Cum | - | - |
| 10 | Removal of excavated surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified. | - | Cum | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.27 MB
BOQ_869406.xls
BOQ • 0.34 MB
Makelist.pdf
Additional Documents • 1.17 MB
Tender1584.pdf
Tender Documents • 3.10 MB
Download all tender documents and submit your bid