| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.6 LAccepted-AOC H NO 309 REHARI COLONY JAMMU DISTT JAMMU J K 180005 | JAMMU | JAMMU AND KASHMIR | 180005 | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹49.9 L+₹11.8 L (30.8%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹60.2 L+₹22.0 L (57.7%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹66.7 L+₹28.5 L (74.6%)Rejected-Finance 0 SHOP NO 48 BHAGAT SINGH COMPLEX VYAPAR VIHAR ROAD CAR PLANET VYAPAR VIHAR BILASPUR BILASPUR CHHATTISGARH 495001 | BILASPUR | CHHATTISGARH | 495001 | L4 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
23 Aug 2023, 6:00 pmClosed
GE 865 EWS
GE 865 EWS, PIN-913 865 C/o 56 APO
SPECIAL REPAIR OF LT OH CONDUCTOR INTO UG CABLES PANELS WITH CONNECTED ITEMS AT DEF AND EMP COY SR TO DISTR SYSTEM WITH ALLIED WORKS AT OLD CORPS POWER HOUSE SR TO ELECTRIC WIRING OF HQ 14 CORPS AND PROVN OF CERTAIN MINOR WORKS UNDER GE 865 EWS LEH
2023_MES_603981_2
865/EWS(NIT-69)/2023-24
Open Tender
Civil Works
Item Rate
180 days
GE 865 EWS
As per tender documents and as per policy in vogue
9 documents required · 9 mandatory
₹500
Yes
GE 865 EWS
₹1 L
Yes
20 Oct 2023
2 Aug 2023
30 Aug 2023
2 Aug 2023
23 Aug 2023
10 Aug 2023
Amount
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. Or for shafts, wells, cesspits,manholes, pier holes, etc. N exc 10 sq m on plan and n exc1.5 m in depth and getting out in hard/dense soil complete all as specified and directed by Engr-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm, complete all as specified and directed by Engr-in-Charge.
Removing excavated material n.exc 50 mtr and depositing where directed at a level n exc. 1.5 m above the starting point., complete all as specified and directed by Engr-in-Charge.
M&L for sand cushioning to underground cables 8cm below the cable before laying and 15cm above the cable after layingc complete all as specified in clause 19.75 of SSR PART -I complete all as specified and directed. Note: Punned thickness of 18cm shall be measured and paid under this item.
Supplying and laying un-reinforced, factory made, machine pressed,precast concrete cable cover, class LV, type 1, flat, size 250mm x 150mm x 40mm complete all as specified and as directed.
M&L for 50 mm bore light grade galvanished iron water tubing with all fittings and fixed on walls and ceiling or laid in floors complete all as specified and directed.
M&L for 80 mm bore light grade galvanished iron water tubing with all fittings and fixed on walls and ceiling or laid in floors complete all as specified and directed.
Dismantling of ACSR conductor any size complete all as specified and directed.
Dismantling and taking out damaged / rusted cross arms, of MS channel or angle section etc complete and setting aside for reuse within 50 mtrs. all as specified and directed.
Dismantling and taking out damaged / rusted GI earth wire / cradle guard complete all as specified and directed.
Dismantling of insulator complete of any size and type from exisiting site all as directed by Engr -in- Charge.
Dismantling of stay assembly of any size and type (demolition of concrete, etc. and excavation measured separately) from existing size complete all as directed by Engr -in- Charge.
Disconnecting and taking down old unserviceable LT armoured XLPE cables from trenches of any size/core any voltage grade from trenches/poles/pipes complete all as directed by Engr -in- Charge.
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 25 Sqmm 4 core laid in trenches or passing through pipes, ducts or fixed to walls/poles complete all as specified and directed by Engr-in-Charge. Make as per PS.
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 16 Sqmm 4 core laid in trenches or passing through pipes, ducts or fixed to walls/poles complete all as specified and directed by Engr-in-Charge. Make as per PS.
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 35 Sqmm 3.5 core laid in trenches or passing through pipes, ducts or fixed to walls/poles complete all as specified and directed by Engr-in-Charge. Make as per PS.
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 50 Sqmm 3.5 core laid in trenches or passing through pipes, ducts or fixed to walls/poles complete all as specified and directed by Engr-in-Charge. Make as per PS.
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 95 Sqmm 3.5 core laid in trenches or passing through pipes, ducts or fixed to walls/poles complete all as specified and directed by Engr-in-Charge. Make as per PS.
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 150 Sqmm 3.5 core laid in trenches or passing through pipes, ducts or fixed to walls/poles complete all as specified and directed by Engr-in-Charge. Make as per PS.
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 500 Sqmm 3.5 core laid in trenches or passing through pipes, ducts or fixed to walls/poles complete all as specified and directed by Engr-in-Charge. Make as per PS.
Supply, installing , testing & commissioning of LT panel board, outdoor cubical type, floor/wall mounted on MS angle iron frame of size 50 x 50 x 6 mm thick, made out of 3.15 mm thick CRCA sheet powder coated for load bearing members for double doors both side openable and covers, Suitable for 3 phase 4 wire 50 cycle 500 Volts system weather and vermin proof, including internal wiring with suitable size copper cable, heat shrinkable sleeves, chromium plated brass cable glands, lugs, 2500Amps Busbar and necessary excavation earth work, PCC grouting etc. to comprising of the following, after installation of LT Panel with connection of cable complete all as directed by Engineer -in- Charge . a) MCCB 800 Amps 4 Pole 50KA 415V, 50Hz (Main Incoming) -01 No b) MCCB 250 Amps 3 Pole 36KA, 415V, 50 Hz (Outgoing) 02 No c) MCCB 200 Amps 3 Pole 36KA 415V, 50Hz (Outgoing) 02 Nos d) MCCB 160 Amps 3 Pole 36KA 415V, 50Hz (Outgoing) 01 Nos (e) MCCB 63 Amps 3 Pole 36KA 415V, 50Hz (Outgoing) 01 Nos (f) ON load four pole Change Over with advance Neutral Switch 800Amps- - 01 Nos (g) Digital type panel mounted 3 phase Voltmeter with LED display - 07 Nos (h) Digital type panel mounted 3 phase Ammeter incl suitable CT with LED display - 07 Nos (i) Indicator lamp RYB LED type(3 Nos) - 01 Set
Supply, installing, testing & commissioning of LT panel board, outdoor cubical type, floor/wall mounted on MS angle iron frame of size 50 x 50 x 6 mm thick, made out of 3.15 mm thick CRCA sheet powder coated for load bearing members for double doors both side openable and covers, Suitable for 3 phase 4 wire 50 cycle 500 Volts system weather and vermin proof, including internal wiring with suitable size copper cable, heat shrinkable sleeves, chromium plated brass cable glands, lugs, 600 Amps Busbar and necessary excavation earth work, PCC grouting etc.. to comprising of the following, after installation of LT Panel with connection of cable complete all as directed by Engineer -in- Charge . a) MCCB 200 Amps 3 Pole 36KA 415V, 50Hz (Main Incomming ) 01 No b) MCCB 100 Amps 3 Pole 16KA, 415V, 50 Hz (Outgoing) 01 No c) MCCB 63 Amps 3 Pole, 16 kA 415V, 50Hz (Outgoing) 02 Nos (d) MCB 63 Amps SPN, 10 kA 415V, 50Hz (Outgoing) 04 Nos (e) Volt meter, Ampere meter, Indicator Lamp complete - 01 Set
Supply, installing , testing & commissioning of LT panel board, outdoor cubical type, floor/wall mounted on MS angle iron frame of size 50 x 50 x 6 mm thick, made out of 3.15 mm thick CRCA sheet powder coated for load bearing members for double doors both side openable and covers, Suitable for 3 phase 4 wire 50 cycle 500 Volts system weather and vermin proof, including internal wiring with suitable size copper cable, heat shrinkable sleeves, chromium plated brass cable glands, lugs, 750 Amps Busbar and necessary excavation earth work, PCC grouting etc.. to comprising of the following, after installation of LT Panel board with reconnection of old cable complete all as directed by Engineer -in- Charge . (a) MCCB 250 Amps 3 Pole 36KA 415V, 50Hz (Main Incomming)- 01 No (b) MCCB 100Amps 3Pole 16KA, 415V, 50 Hz (Outgoing)- 02 No (c) MCCB 63Amps 3 Pole, 16 kA 415V, 50Hz (Outgoing)- 02 Nos (d) MCB 63Amps SPN, 10 kA 415V, 50Hz (Outgoing)- 04 Nos (e) Volt meter, Ampere meter, Indicator Lamp complete - 01 Set
M&L in replacement for Earthing complete with galvanised steel earth plate electrode 60 cm X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and inclduing GI Strip 32X6 mm as earthing lead, by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No 5 of MES SSR Part I and testing on completion including excavation and earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS frame and cover 6 mm thick in cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric or XPM (weight not less than 4 Kg per Sqm) with cast iron frame, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs complete all as specified and directed Note- (i) earth resistance not more than 1.0 OHMS.Writing of details on the surface of the pit with paint. (ii) In case earth resistance more than 1.0 ohms, the contractor wiil re earthing at no extra cost. (iii) On testing, if the earth resistance less than specified is not obtained, earthing will be regenerated at NO EXTRA COST till the desired earth resistance is obtained.
Supply and fixing cable route indicator, made of MS sheet of size 200 mm x 150 mm x 3 mm thick, spot welded with angle iron of size 40 x 40 x 5 mm thick, 750 mm long embedded in PCC (1:2:4) type B-2 ( using 40mm graded crushed stone aggregate) block 30cm x 30cm x 40cm in ground including one coat of synthetic enamel black paint over one coat of red oxide zinc chrome primer and writing with white paint and showing size of cable HT /LT complete all as directed & specified.
Cutting the existing bituminuos road for passing of UG Cable in road crossing and making good the disturbed surface of road to its original specification complete all as directed.
Supply and fixing FR/PVC pole box for loop in and loop out of size 200mm x 180mm x 98mm including 3 pole and Neutral bakelite connector and one SP 6 Amp MCB and necessary clamp and nut bolts for fixing arrangements complete all as specified and directed by Engr-in-Charge. Make :- As per PS
S&F Timer switch with sensor alongwith Pre-down switching off timer (nature switch), three phase, inclusive of 3 Phase load of 5KW with 3 Nos contactors,3 Nos incoming MCB and 3 Nos Outgoing MCB rating of 16-20 Amps and main load circuit wiring (Copper) of min 10 Sqmm with operating illumination level for switching ON should be less than 60 lux for 30 seconds and for switching off must be greated than 10 lux for 30 seconds, multiple option switch for automatic and manual operations, cabaple to handle lightning load upto 5KW per phase, including power contactor capacity 25 Amp conforms to IEC 60947-4-1 IS 13947-4-1 completely enclosed with plastic body panel conforming to IP 66 degree of protection complete all as specified and directed by Engr-in-Charge. Make: Kakatiya Energy Systems Pvt Ltd Model No SWADEEP-02EC5kW3P / Havells/ Legrand
Sub main wiring with earth wire with the size (2x2.5 Sqmm) 240 volts grade single core FRLS PVC insulated unsheathed multistranded copper conductor confirming to IS-694 drawn through and including non-metalic PVC casing caping ISI marked with all accessories etc with one run of 2.5 Sqmm (1x2.5 Sqmm) single core FRLS PVC insulated unsheathed copper conductor cable as earth wire, sinking of MS boxes and making good to match with existing surfaces complete all as specified and directed by Engr-in-Charge. Note:- 2 runs of 2.5 Sqmm (2x 2.5 Sqmm), 1 run of 2.5 Sqmm (1x2.5 Sqmm) cable and one metre of casing caping will be measured as one unit.
Supply and fixing in replacement off load changeover switch 1250 Amps, 4 pole in sheet metal enclosure, side /front handle operated complete all as specified and directed
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 630 Sqmm 3.5 core laid in trenches or passing through pipes, ducts or fixed to walls/poles including taking down old unserviceable cable complete all as specified and directed by Engr-in-Charge. Make as per PS.
Supply and laying, jointing and testing cable, LT XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable heavy duty 1100 volts grade with stranded aluminium conductor in size 240 Sqmm 3.5 core laid in trenches or passing through pipes, ducts or fixed to walls/poles including taking down old unserviceable cable complete all as specified and directed by Engr-in-Charge. Make as per PS.
M&L for earthing of machinery/equipment installed at power house/substation using 32x6mm galvanised strip and galvanised plate of size 600x 600x6mm as earth electrode complete all as specified and directed by Engr-in-Charge.
S&F of Galvanised iron strip 32x6mm buried in ground complete all as specified and directed.
Taking down carefully copper/Aluminum point wiring (Light, Fan, Socket or power) complete fitting such as switches, ceiling, regulator, sockets etc removing materials to be store for keeping in safe custody for taking credit and making good disturbed surfaces of walls, floors etc complete all as speciifed and directed by Engr-in-Charge
M&L for point wiring for one light point or fan point controlled by one light/exhaust fan controlled by one way switch with PVC insulated FRLS copper conductor stranded cable of size 1.5 sqmm and including PVC casing/caping terminated in pressed steel terminal boxes for fixing and 1.5 sqmm PVC insulated copper wire as earth wire connected to earth wire connected to earth folly and 3.0mm thick plastic laminated sheet cover all as specified and directed by Engr-in-Charge.
All as per item No 38.00 here-in-before but 1.5 Sqmm for one 3 pin 6 Amps socket outlet including 1.5 sqmm insulated copper wire as earth wire to the same earth dolly on the same board complete all as specified and directed by Engr-in-Charge.
All as per item No 38.00 here-in-before but 1.5 Sqmm for one 3 pin 6 Amps socket outlet including 1.5 sqmm insulated copper wire as earth wire to the same earth dolly on the independent board complete all as specified and directed by Engr-in-Charge.
All as per item No 38.00 here-in-before but one socket outlet 15 Amps 3/5 pin on independent board cable of size 2.5 sqmm sixe with 2.50 Sqmm for continuty complete all as specified and directed by Engr-in-Charge.
S&F in replacement switch socket combination 2 in 1,3 pin, 5 Amps flush type universal, ISI marked complete all as specified and directed
S&F switch socket combination 2 in 1,3 pin, 5 Amps flush type universal, ISI marked complete all as specified and directed
S&F in replacement for socket outlet 3Pin, 5A, flush type complete all as specified and directed
S&F socket outlet 3Pin, 5A, flush type complete all as specified and directed
S&F in replacement for switch socket combination 2 in 1,3 pin, 5 and 15 Amps flush type universal, ISI marked complete all as specified and directed
S&F switch socket combination 2 in 1,3 pin, 5 and 15 Amps flush type universal, ISI marked complete all as specified and directed
S&F in replacement for switch piano flush type one way single pole 5 Amp 240 volts, ISI marked complete all as specified and directed
S&F switch piano flush type one way single pole 5 Amp 240 volts, ISI marked complete all as specified and directed
S&F ceiling rose surface bakelite 65x50 mm two to three terminals.all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement for MCB distribution board Double door, regal grey, sheet metal enclosure, TPN vertical 415 volts 4 way with 200 amps rated bus bar concealed to wall and making flush with wall surfaces and making good to disturbed surfaces of walls to match with the exisiting surface etc complete all as specified and directed
Supply and fixing MCB distribution board Double door, regal grey, sheet metal enclosure, SPN 240 volts 8 way with 200 amps rated bus bar concealed to wall and making flush with wall surfaces and making good to disturbed surfaces of walls to match with the exisiting surface etc incl taking down old DBs complete all as specified and directed
Supply and fixing MCB distribution board Double door, regal grey, sheet metal enclosure, SPN 240 volts 12 way with 200 amps rated bus bar concealed to wall and making flush with wall surfaces and making good to disturbed surfaces of walls to match with the exisiting surface etc complete all as specified and directed
Supply and fixing MCB SP 6 to 32 Amps, 'C' series, 230 V A/C complete incl taking down old MCBs all as specified and as directed by Engineer-in-Charge.
Supply and fixing MCB SP 6 to 32 Amps, 'C' series, 230 V A/C complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing MCB SPN 40 to 63 Amps, 'C' series, 230 V A/C complete incl taking down old MCBs all as specified and as directed by Engineer-in-Charge.
Supply and fixing MCB SPN 40 to 63 Amps, 'C' series, 230 V A/C complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing MCB TPN 63 Amps, 'C' series, 230 V A/C complete incl taking down old MCBs all as specified and as directed by Engineer-in-Charge.
S&F sub main wiring with earth wire with the size two runs of 6 Sqmm (2x6 Sqmm) 240 volts grade single core FRLS PVC insulated unsheathed multistranded copper conductor confirming to IS-694 drawn through and including non-metalic PVC casing caping ISI marked with all accessories etc with one run of 6 Sqmm (1x 6 Sqmm) single core FRLS PVC insulated unsheathed copper conductor cable as earth wire, sinking of MS boxes and making good to match with existing surfaces including taking down old existing sub main wiring complete all as specified and directed by Engr-in-Charge. Note:- 2 runs of 6 Sqmm (2x 6 Sqmm), 1 run of 6 Sqmm (1x6 Sqmm) cable and one metre of casing caping will be measured as one unit.
S&F sub main wiring with earth wire with the size four runs of 10 Sqmm (4x10 Sqmm) 240 volts grade single core FRLS PVC insulated unsheathed multistranded copper conductor confirming to IS-694 drawn through and including non-metalic PVC casing caping ISI marked with all accessories etc with two run of 10 Sqmm (2x 10 Sqmm) single core FRLS PVC insulated unsheathed copper conductor cable as earth wire, sinking of MS boxes and making good to match with existing surfaces including taking down old existing sub main wiring complete all as specified and directed by Engr-in-Charge. Note:- 4 runs of 10 Sqmm (4x 10 Sqmm), 2 run of 10 Sqmm (2x 10 Sqmm) cable and one metre of casing caping will be measured as one unit.
S&F sub main wiring with earth wire with the size two runs of 10 Sqmm (2x 10 Sqmm) 240 volts grade single core FRLS PVC insulated unsheathed multistranded copper conductor confirming to IS-694 drawn through and including non-metalic PVC casing caping ISI marked with all accessories etc with one run of 10 Sqmm (1x 10 Sqmm) single core FRLS PVC insulated unsheathed copper conductor cable as earth wire, sinking of MS boxes and making good to match with existing surfaces complete all as specified and directed by Engr-in-Charge. Note:- 2 runs of 10 Sqmm (2x 10 Sqmm), 1 run of 10 Sqmm (1x 10 Sqmm) cable and one metre of casing caping will be measured as one unit.
S&F surface/wall mounted LED fittings with LED tube 18 watts, 6000K capacity decorative ultra slim round profile LED lighting fixture with extruded polycarbonate, environmental friendly, energy efficient 4 feet long type bracket including necessary connection prewired and making connection with 3 core copper flexible cable of appropriate size from ceiling rose/PVC conductor to light fittings with complete accessories complete all as specified and directed. Make: As per PS
S&F of LED 36 watt recessed 2 x 2 feet luminaire (Warm/White) to enhance the delight of occupants with comfortable experience through its design and glare free soft illumination and connection of 3 core copper wire with all assessories complete all as specified and directed by Engr-in-Charge.
S&F of spot light bright electronics 9W LED focus wall light with metal body (Warm white/White) having reflector for brighter light including connection of 3 core copper wire with all assessories complete all as specified and directed by Engr-in-Charge.
Supply and fixing exhaust fan, made of steel body complete with louvers shutter, voltage 230V, 50Hz, RPM 1200, copper winding of sweep 300mm including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
S&F decorative surface mounting dome shaped pendant light fitting on table with 7.5W LED filament lamp including all connections and accessories complete all as specified and directed by Engr-in-Charge.
HEENA CONSTRUCTION CO
Feroz Engineering Works
Sona Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .