Er. Chander Shekhar
Office of the Executive Engineer, Electrical Division No. 3 Sector-4, Chandigarh.
MAINTENANCE OF E.I. IN NRB AT CHANDIGARH (PROVIDING PREVENTIVE MAINTENANCE/SERVICE OF EXISTING HT EQUIPMENTS OF VARIOUS CAPACITY IN VARIOUS 11 KV SUBSTATIONS IN PUNJAB AND HARYANA HIGH COURT, SECTOR-1, U.T., CHANDIGARH).
2026_CHD_93960_1
E3/47W/76
Open Tender
Electrical Works
Percentage
15 days
Chandigarh
as per NIT
2 documents required · 2 mandatory
₹0
₹8,700
14 Sept 2026
10 Jul 2026
16 Jul 2026
10 Jul 2026
16 Jul 2026
10 Jul 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Servicing, repair & preventative maintenance of existing 11 KV HT equipments installed in 11 KV substations Punjab & Haryana High Court Sector 1, Chandigarh. The 11 KV transformers (Dry/oil type), 11 KV HT VCBs/OCBs panels(incoming /outgoing), Bus coupler (incoming /outgoing) & 11 KV HT CT PT units should be checked, cleaned from outside & inside with the help of petrol/cleaner. The VCB panels should be opened from backside and cleaning the bus bar and connection chambers including end joint f HT cable and ensure to make the equipments moisture free. Thereafter the HT/ LT connections of transformers should be checked, tighten properly including replacement of loose/sparked thimbles etc. to make the same properly functional. The HT cable connections of the HT VCB/OCB panels should also be tighten including replacement of loose/ sparked thimble etc. and tapping the joint and nut bolts with the help of HT insulation tape to make it properly functional. The main bus bar of the HT panel should also be checked & tightening of connections also be done. It also includes proper greasing of the moveable parts of the HT VCB/OCB panels/ trolleys to make it smooth adjustment. The relays of the VCB/OCB panels should also be checked according to the running load for providing proper tripping during occurrence of fault. The power supply to the motors of the HT VCB/OCB panels & DC supply to the various relays in the VCB/OCB panels should also be checked & ensure properly working including tightening of sensing/control cables etc. The job includes all labour charges required to open the covers of transformers & HT VCB/OCB panels and CT PT unit etc. after switching off the HT supply & reinstallation of the cover after servicing & restoration of supply. The job includes all labour & material required to complete the job for retesting, commissioning of the equipments & to ensure the proper functioning. The work should be carried out as per satisfaction of EIC. | |||||
| 1.01 | 11 KV HT VCB incoming /outgoing panels 400 /600/800 Amp rating of Yamuna power make | 25 | Each | 4,500 | ₹1,12,500 |
| 1.02 | 11 KV 1000 KVA dry type transformer | 10 | Each | 3,000 | ₹30,000 |
| 1.03 | 11 KV 500/750 KVA oil type transformer | 2 | Each | 2,500 | ₹5,000 |
| 1.04 | 11 KV OCB | 3 | Each | 4,500 | ₹13,500 |
| 1.05 | 11 KV CT PT unit (Incoming & outgoing compartments) | 4 | Each | 2,000 | ₹8,000 |
| 2 | S/E/T/C of 11 KV HT CT200/100/5 amp of reputed make and also compatible with existing Yamuna power VCB. The job includes the dismantling, disconnection of old unserviceable CT and install the new with proper connection, testing etc. this also includes all labour and petty material required to complete the job to the entire satisfaction of Engineer-in-charge. | 3 | Each | 31,250 | ₹93,750 |
| 3DSR 23.4 Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : | |||||
| 3.01 | 70 sq. mm | 6 | Each | 12,946 | ₹77,676 |
| 3.02 | 300 sq. mm | 2 | Each | 17,414 | ₹34,828 |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 22.36 MB
BOQ_115144.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .