Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.5 LAccepted-AOC RATU RD PISKA MORE LAXMI NAGAR DISTT RANCHI JHARKHAND 834 005 | RANCHI | RANCHI | JHARKHAND | 834005 | L1 | Accepted-AOC The L1 bidder is techno-commercially qualified. The quoted rate has been accepted by the Competent Authority, NK Area. |
| Sl No | Description | Qty | Unit | R AND S ELECTRICALS L1 |
|---|---|---|---|---|
| 1.00 | Providing and fixing of HT Palm copper connector of 10 MVA Transformer | 3 | Nos | 9,950 ₹29,850 Lowest |
| 2.00 | Providing and fixing of LT Palm copper connector of 10 MVA Transformer | 4 | Nos | 17,250 ₹69,000 Lowest |
| 3.00 | Providing and fixing of 11kV Indoor type resin cast three core current Transformer CTR: ,-800- 400A/5-5-5A, Core I: Class I,15VA, Core II- 5P10, 15VA and Core III: PS Class, 15VA, Knee point voltage-120V, Short time current-25KA/1Sec, Secondary winding resistance at 75 degree C: 2 ohms, Frequency-50Hz | 3 | Nos | 43,750 ₹1,31,250 Lowest |
| 4.00 | Providing and fixing of GOAB Switch 33kV grade, 1250A, 25kA for 3 Sec, Tripple Pole, Double Break, Horizontal upright mounting with 22kV grade procelain post insulator, vertical operating pipe, phase coupline pipe. | 1 | Nos | 1,47,000 ₹1,47,000 Lowest |
| 5.00 | Providing and fixing of Numerical Transformer Differential Relay, Rated Current 5A, Auxilliary voltage 75-150V DC/AC | 1 | Nos | 1,43,000 ₹1,43,000 Lowest |
| 6.00 | Providing and fixing of IDMT/Definite Time/ Instantaneous Low - Set/High-Set Non-Directional. Numerical/Microprocessor based 3 over current Relay and 1 Earth Fault Relay, Rated Current 5A, Auxiliary voltage 85-275 VDC/AC | 2 | Nos | 41,000 ₹82,000 Lowest |
| 7.00 | Providing and fixing of Single Pole, Directional over current or Earth Fault Relay without High Set feature, Rated Current 5A, Auxiliary voltage 75-150V DC/AC | 3 | Nos | 37,550 ₹1,12,650 Lowest |
| 8.00 | Providing and fixing of Microprocessor based Alarm Annuniciator, No. of window:- 12, Ann (3R X 4C), Aux. Supply:- 90-270V AC/DC. Fault I/p:- Potential free NO or NC type with TEST, ACCEPT & RESET Push button. | 2 | Set | 33,250 ₹66,500 Lowest |
| 9.00 | Providing and fixing of Copper unarmourd control cable 1.1 kV grade, 2.5 sqmm, 12 Core | 210 | Mtr | 1,230 ₹2,58,300 Lowest |
| 10.00 | Complete wiring with materials including PVC wires, lugs, tape ferrules etc for fixing of above required items | 1 | job | 9,500 ₹9,500 Lowest |
Tender Value
₹13.7 L
EMD Value
₹17,100
Closing Date
12 Apr 2025, 5:00 pmClosed
SO EnM NK
GM OFFICE, NK AREA
Installation of 10MVA, 33kV/11kV Transformer, Sl. No. KS/1000/23/9, Make K Sambhav Powertronics with differential protection and its accessories at 22.5 MVA, 33kV/11kV-3.3kV Old Sub-station under KDH OCP, NK Area
2025_CCL_333483_1
GM (NK)/EnM/e-NIT/2024-25/ 256
Open Tender
Electrical and Maintenance Works
Item Rate
45 days
KDH OCP, NK Area
As per NIT
2 documents required · 2 mandatory
₹17,100
24 Aug 2025
28 Mar 2025
14 Apr 2025
29 Mar 2025
12 Apr 2025
29 Mar 2025
29 Mar 2025 - 4 Apr 2025
Amount
Providing and fixing of HT Palm copper connector of 10 MVA Transformer
Providing and fixing of LT Palm copper connector of 10 MVA Transformer
Providing and fixing of 11kV Indoor type resin cast three core current Transformer CTR: ,-800- 400A/5-5-5A, Core I: Class I,15VA, Core II- 5P10, 15VA and Core III: PS Class, 15VA, Knee point voltage-120V, Short time current-25KA/1Sec, Secondary winding resistance at 75 degree C: 2 ohms, Frequency-50Hz
Providing and fixing of GOAB Switch 33kV grade, 1250A, 25kA for 3 Sec, Tripple Pole, Double Break, Horizontal upright mounting with 22kV grade procelain post insulator, vertical operating pipe, phase coupline pipe.
Providing and fixing of Numerical Transformer Differential Relay, Rated Current 5A, Auxilliary voltage 75-150V DC/AC
Providing and fixing of IDMT/Definite Time/ Instantaneous Low - Set/High-Set Non-Directional. Numerical/Microprocessor based 3 over current Relay and 1 Earth Fault Relay, Rated Current 5A, Auxiliary voltage 85-275 VDC/AC
Providing and fixing of Single Pole, Directional over current or Earth Fault Relay without High Set feature, Rated Current 5A, Auxiliary voltage 75-150V DC/AC
Providing and fixing of Microprocessor based Alarm Annuniciator, No. of window:- 12, Ann (3R X 4C), Aux. Supply:- 90-270V AC/DC. Fault I/p:- Potential free NO or NC type with TEST, ACCEPT & RESET Push button.
Providing and fixing of Copper unarmourd control cable 1.1 kV grade, 2.5 sqmm, 12 Core
Complete wiring with materials including PVC wires, lugs, tape ferrules etc for fixing of above required items
Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 mtr long etc with charcoal/coke and salt as required.
Labour charge for installation of Item No. 1 to 9
Total impact of GST for the purpose of CTC
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .