Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.9 LAccepted-Finance | L1 | Accepted-Finance Rate quoted is lowest | |
| 2 | L2₹7.2 L+₹27,600.40 (3.98%)Accepted-Finance | L2 | Accepted-Finance Rate quoted is second lowest | |
| 3 | L3₹7.2 L+₹30,885.70 (4.45%)Accepted-Finance | L3 | Accepted-Finance Rate quoted is highest |
Tender Value
₹7.1 L
EMD Value
₹8,000
Closing Date
20 Jul 2020, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
SE ETC Sultanpur 400KV S/S Campus Payagipur Sultanpur
INSTALLATION OF NEW 63MVA 132/33KV T/F AND OTHER ASSOCIATED WORKS FOR ADDING 01 No. 132/33KV T/F BAY AT AT 220KV S/S, SOHAWAL UNDER E.T.D., AYODHYA.
2020_UPTCL_488121_1
T. NO. 40/ETCS/2020-21
Open Tender
Electrical Works
Item Wise
30 days
Sultanpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹944
SE ETC Sultanpur
₹8,000
23 Jul 2020
27 Jun 2020
21 Jul 2020
27 Jun 2020
20 Jul 2020
27 Jun 2020
27 Jun 2020 - 20 Jul 2020
180 days
Amount
Following works are to be carried out at 220 KV Substation Sohawal, Ayodhya for the installation of new 63 MVA 132/33 KV Transfromer along with associated works for adding 01 No. 132/33kV Transformer bay including all cost of men, misc, consumables, T&P, Crane etc. to complete the Job satisfactorily
Erection of Transformer & CRP Panel including shifting etc.
Shifting of main tank of 132/33 KV, 63 MVA T/F to its plinth from place of unloading up to 20 meter distace including turning of tank, if required.
Additional shifting upto 20 meter (1 job for every 05 meter)
Complete erection of 132/33 KV, 63 MVA Transformer including radiators, conservator tank, all bushings, turrets,connecting pipe lines, cooling fans, Marshalling box.
Filling and topping of the Transformer oil in tank, radiators, conservator tank, all bushings , turrets, connecting pipe lines, cooling fans, Marshalling box etc.
Centrifuging of oil in main Transformer tank un-interrupted till the desired BDV value of the oil is achieved including recording all the parameters hourly such as temperature, vacuum, insulation resistance etc, centrifuging machine. Operator and all T&P will be arranged by the contractor.
Complete earthing of 63 MVA Transformer with 75 X10 mm/ 50X6 mm size M.S. Flats as per standard practice at 02 points.
Earthing of main tank of the Transformer, RTCC Panel, Marshalling box,drive mechanism of the cooling fans etc., with already laid earth-mat shall be earthed as per standard practice.
Earthing of Transformer HV & LV neutral with 75 X 10 mm, MS Flat connecting with delta including making of new delta painting and other associated works as per technical specification.
Earthing of 132 KV and 33 KV LAs in a ring formation with 50 X 6 mm, MS Flat connecting with electrodes including making of the ring with the help of 3 m electrodes (06 nos.) at the depth of 1 meter below the ground level along with painting and other associated works as per technical specification.
Erection of following Control and Relay Panels in Control Room of 220KV S/S Sohawal including grouting, earthing & Termination of control panels, as per cable schedules including Providing & Fixing of Cable Glands of appropriate sizes and ferrules etc. with all other associated works as per technical specification.
132/33 KV 63 MVA new Transformer Control and Relay Panel
Erection of 63 MVA Transformer RTCC Panel including termination after shifting from storage place to Control Room as per direction of engineer
Erection of main and auxiliary structures
Main Structure (ATMS & AXM)
Auxiliary Structures
Erection of following Equipments as per instruction manual and technical specifications including shifting of materials from Central Stores to Erection Site including all associated works(raising of height of various structures if needed) :
145 KV SF6 CB with structure
132 KV Bus isolator
132 KV Tandem Isolator
132 KV LA (with structures)
33 KV VCB with structure
33 KV BI without earthblade
Jumpering, Stringing, etc. of various Equipments/ Bus Sections
Laying and Stringing 132 KV Jack Bus (approx.12m) of Twin ACSR 'Moose' Conductor using new conductor by necessary cutting in proper length including Hoisting of Disc Insulator Strings & Tension Fittings etc. (to be provided by Department) and there after jumpering to HV & LV Bushing, T/F LAs(HV & LV side) and 33kV CTs alongwith shifting of all materials from Store to Switchyard (01 Job for each phase of Bus Bar)
Jumpering of various equipments with ACSR "Moose" conductor using new conductor by necessary cutting in proper length between 132 KV Main Bus to Bus Isolator in 132 KV Bay alongwih shifting of new Conductor and Clamp/ Connectors etc. from Substation Stores to Swithyard
Jumpering of various equipments with ACSR "Moose/Panther Conductor " between 132 KV Bus Isolator to CB and CB to to 132 KV CT including /Transfer Bus Isolators/Transfer Bus Droppers etc. in 132/33 KV 63 MVA T/F-III HV Bay by due cutting and bending of conductor and fixing & tightening etc. Of the Conductor/ Clamps/Connecotrs/Spacers etc.
Jumpering of various equipments with Twin ACSR "Moose Conductor " in 132/33 KV 63 MVA T/F-III LV Bay between 33 KV Main Bus to Bus Isolator Isolator, CTs and CB by due cutting and bending of conductor and fixing & tightening et. Of the Conductor/ Clamps/Connecotrs/Spacers etc.(01 Job for all 3 phases)
Laying of following sizes Control Cables in the Cable Trenches from Control and Relay Panels in Control Room to various Equipments, Junction Box etc. in Swithcyard as per cable schedule, its sddling with 25X3 mm size including carriage of Cable Drums from Stores to work site & shifting back to stores including allother associated works required for the satisfactorily completion of the Job as per technical specification.
Laying of 2X2.5 sq. mm size Control Cable
Laying of 4X2.5 sq. mm size Control Cable
Laying of 6X2.5 sq. mm size Control Cable
Interconnection & termination of of the above laid control cables between Control and Relay Panels & erected equipments i.e. 63 MVA T/F CB, CT, CT Junction Box, PT, PT Junction, box. Including making necessary holes in Gland Plates or Boxes whereever required along with supply of Cable glands of appropriate size and providing of Ferrules for each core of the cables & its termination with crimping type Copper Lugs alongwith preparation of Interconnection Drawing and Commissioning of the Panel/ Feeders in co-ordination with T&C Wing includoing providing 02 sets of Hard Copies of as executed Interconnection Drawing including all other associated works required for the satisfactorily completion of the Job as per technical specification. (01 Job for Each Bay i.e. 02 jobs for 63 MVA T/F HV and LV side)
Cutting, Straightening and Laying 700 mm below inside ground & above ground of 50X6 mm & 75X10 mm size M.S. Flats (to be provided by the department) as per requirement for Earthing of newly erected equipments and Structures as above including welding with main Earthmat and with the object to be earthed including excavation, backfilling, painting of the Earthmat above groung level in Bus Green colour including all other associated works to complete the job satisfactorily as per Technical Specifications.
Earthing of Main & aux. Structures and Equipments with 50X6 mm size M.S. Flat
Earthing of cable trenches with 25X6 mm size M.S. Flat
Delta Earthing of 132Kv and 33kV L.A. as per technical specification
Assisting in complete testing and commissioning of all the equipments of the bay along with the transformer.The work also includes complete oil testing of the transformer from NABL accredited lab.
Perfect Power Transformer Associates
Meena Elect and Engg Works
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .