Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹10.3 Cr
EMD Value
₹20.6 L
Closing Date
19 Oct 2026, 9:00 am
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Naveen
Municipal Corporation Panipat
Construction of Community Centre in Ward No. 1 Sector 13-17 MC Panipat.
2026_HRY_550730_1
202618063DB2 693C 460D 85BC 5EA0040703AA286ULB
Open Tender
Civil Works
Works
450 days
Panipat
Construction of Community Centre in Ward No. 1 Sector 13-17 MC Panipat.
2 documents required · 2 mandatory
₹20,000
₹20.6 L
Yes
Municipal Corporation Panipat
28 Sept 2026
28 Sept 2026
19 Oct 2026
28 Sept 2026
19 Oct 2026
28 Sept 2026
5 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.1 | NS ITEMS | - | - | - | - |
| 1.2 | Providing and fixing of COMMUNITY CENTRE PANIPAT in Acrylic Letters with light of 24` Height with power Supply and Warrenty of 2 years with fittings complete with all respect. (Acrylic Make: Astari, Marga cipta, Acast),...( Make: Hilight, Osram , GOQ)....( Make: Timex, Alutech , Aluceor or equivalent) | 1 | Each | 100 | ₹100 |
| 1.3 | Providing and fixing of signages of toilet of size 300x450mm as per design complete in all respect up to the entire satisfaction of Engineer-in-charge of the work.. (Make: Patel Brothers , JMJ Signage , Vizan Sign or equivalent) | 7 | Each | 100 | ₹700 |
| 1.4 | Providing and fixing of signages of fire exit names of size 800x300mm as per design complete in all respect up to the entire satisfaction of Engineer-in-charge of the work.(Make: Patel Brothers , JMJ Signage , Vizan Sign or equivalent) | 6 | Each | 100 | ₹600 |
| 1.5 | Providing and fixing of signages of drinking water / lift names of size 300x300mm as per design complete in all respect up to the entire satisfaction of Engineer-in-charge of the work.(Make: Patel Brothers , JMJ Signage , Vizan Sign or equivalent) | 2 | Each | 100 | ₹200 |
| 1.6 | Providing and fixing of approved coloured verticle type hot water 25 ltr geysers. The inner container shall be made of copper sleeve with PUF insulation between inner and outer container, element pipe and heating element, pressure cum vaccume release, thermostat and thermal cutout arrangements and fusible plug. The outer container shall be of powder coated finish with all other accessories including fixing brackets complete as required. | 10 | Each | 100 | ₹1,000 |
| 1.7 | Providing and fixing of 6mm Toughened glass comply with the requirement of BS EN 572 parts 1,2 and3 or ASTM C1036 assessed for optical and visual faults as described in BS EN 572-2. Spot faults to be no worsethan category C. There will be no linear /extended faults. Optical faults to be within the limits set in BS EN 572-2 of model no. ET 150 Toughened glass complete in all respect up to the entire satisfaction of Engineer-in-charge of the work. (Make: Relaxo , Modiguard, Saintgobain or equivalent) | 318.53 | Sqm | 100 | ₹31,853 |
| 1.8 | Providing and Fixing of Decorative pole of 5mtr high made of galvanised Mild steel pipes fitted with cast aluminium embellishments duly polyurethane paint coated with cast aluminium base cover. Pole Bottom Dia- 139.7x3.6mm (1 mtr), Top Dia -_ 76.1x3.2mm (2.5 mtr) Base Plate Size is 250x250x12mm Foundation Bolt 16x600x4 Nos. with Single Arm Bracket MF-82A height will be 1.5 Mtr. Long with Suitable pipes and Bracket will be completed with Aluminium Castings as per approved design and LED decorative drop down light 50w made of aluminium housing fitted with PMMA diffuser, Light Dimensions is 500x370 (With-Philips/Fulhame/HR Driver and10KVA SPD)complete in all respect as per the direction of the officer-in-charge. | 5 | Each | 100 | ₹500 |
| 1.9 | Design, manufacture supply, installation, testing and commissioning of the following extensible cubicle type indoor mounting, dead front, fully compartmentalised with hinged lockable detachable front and back openable, dust and vermin proof, floor mounting sheet steel clad switchboard fabricated out of 2 mm thick CRCA powder coated sheet steel suitable for use at 415 volts 3 phase 4 wire 50 cycle system and to withstand a symmetrical fault level as specified at 415 volts. Panels shall be fabricated in easily transportable sections, length, height, depth etc. to match with site condition. All incomer breaker and Bus Couplers shall be interlocked electrically as shown in SLD and specifications.
Note: The following provisions shall be required to be made in the switchboard as detailed below:
a) The Switchboards shall have provision to accommodate all cables from the bottom /top as required.
b) All live accessible parts shall be shrouded with 1mm thick polycarbonate/3 mm thick FRP sheet and all equipment shall be finger touch proof. The busbar insulation shall be with heat shrinkable sleeves according to the colour code. SMC shrouds and busbar supports shall be used.
c) Galvanised hardware with zinc passivation shall be used in fabrication of Switchboards.
d) All rear door of Main LT Panel shall be Almirah type with lockable arrangement.
e) Space heater shall be provided with thermostat with 6A MCB as backup protection in each section of Main LT Panel and controlled with 20 A DP MCB, 10 KA.
f) Provision of one 6/16 amp socket and compartment lighting for each vertical section of main LT Panel.
g) The panel shall display Main Incomers Bus Couplers of Main LT Panel. This line diagram shall be made from luminous non fading materials to glow in dark and each breaker legend shall be provided with bi-colour LED lights to show the Phase indication Lamp and ON/OFF status of the respective feeder (Incomers / Bus couplers)
h) All control and power wiring shall be broughtout upto the cable alley in the terminal blocks. 10% extra terminals shall be supplied along with Panel.
i) An approval shall be taken for each panel before manufacturing.
j) Suitable Aluminium earth bus to be provided throughout the length of Switchboards.
k) All indication lamps / illuminated push buttons shall be LED type.
l) 2A SP MCBs shall be used as backup protections.
m) Coil of all motor starters shall be fed from 440 V / 230 V Control Transformer.
n) All incomer meters of Main LT Panel shall be multifunction and should have all the electrical parameters like, Voltage, Ampere, KW, KVAR, KWH, PF, Frequency etc. with communication port RS-485.
o) All feeders with KWHr meter will be Electronic Dual Reading KWHr meter alongwith appropriate CT`s and 1 sq. mm control wiring from each KWHr meter for RS-485 communication till DCU`s compartment.
p) Provision for providing 230V AC supply for Dual KWHr metering when any or all DG are in operation
q) One separate compartment of minimum size 400 x 900 mm for power management system of D.C.U.`s with control wiring as per following specification and control wiring scheme. Control wiring shall be looped from each energy meter till DCU`s compartment for sending DCU register change command from data connectivity.
r) All CT and PT`s shall be cast resin type. Class - 3 CT shall be provided up to 100 amp and above that the CT shall be Class - 1.
s) Zone selective Interlocking to be hardwired between incoming and outgoing ACB of main LT Panel.
t) All incomer ACBs of Main LT Panel shall be with microprocessor based releases (O/C, S/C and E/F), display of current/voltage and communication port RS-485, however ACB Incomers in other distribution panel and outgoing of Main LT Panel shall be with standard releases.( Ics=100%Icu=Icw )
u) All Main LT Panel outgoing ACB shall be with inbuilt earth fault release with CT and MCCB shall be with earth fault module with associated neutral CT for feeder protection, for TP feeders and E/F release for FP feeders.
v) All MCCB shall be provided with Rotary handle, door interlocked and lockable in off position of MCCB.
w) All Main LT Panel outgoing MCCBs shall be with microprocessor based releases, line load reversibility, Ics = 100% Icu.
x) Rating of Neutral bus-bar shall be 50% of phase-bus bar
y) All MCB to be C Curve type
z) Micro PLC for auto load management and interlocking as per logic specified.
MAIN LT PANEL (INBUILT CAPACITOR PANEL) (Make AAA Switchgear, Indiatech panel, Neptune india)
i) 400 amps 25 kA 100 volt FP MCCB with overcurrent and short circuit and earth fault module, with heavy duty solid detachable neutral link
Metering for incoming:
a) 3 nos 400/5A Class 1, 15 VA Burden CT`s for metering and 1 nos associated Neutral CT for earth fault module.
b) Digital flush type class -1.0 accuracy multifunction meter with RS-485 communication port for measurement of THD, KVARH KW, KWH, KVAR, PF, V, A, Hz, equivalent to EM6400 NG, with 3 Nos. current transformers of required ratio, 15 VA Cl | 1 | Per Set | 100 | ₹100 |
| 2 | FEEDER PILLAR - IP55 (Make AAA Switchgear, Indiatech panel, Neptune india)
Incoming:
1 Nos. 100 Amp FP MCCB OF 25 KA Breaking Capacity
Phase indication Lamp and ON/OFF indicating lamps with MCB as backup protection.
Bus Bar:
TPN Aluminium busbars aluminium three phase and neutral busbars rated at 125 amps, 25 KA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Current density of Bus Bar to be 1.0 sq.mm / amp.
Outgoing :
5 nos. 63 amps 25 kA FP MCB
5 nos. 63 amps 25 kA DP MCB
Complete Set as required above | 1 | Per Set | 100 | ₹100 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.96 MB
BOQ_630517.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .