Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
Closing Date
28 Jun 2021, 4:00 pmClosed
Executive Engineer Jal Shakti Mech Div sgr
Executive Engineer Jal Shakti Mech Div sgr
Rate contract for various Electrical works at WSS Tangnar Stage 1 and 2nd
2021_PHE_127211_1
E-NIT-No-E-17-of-06-2021
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
Tangnar
As per NIT
2 documents required · 2 mandatory
₹200
Yes
Executive Engineer Jal Shakti Mech Div sgr
Exempted
12 Jul 2021
15 Jun 2021
30 Jun 2021
15 Jun 2021
28 Jun 2021
15 Jun 2021
Amount
Replacement of Carbon Brushes and repairs to Slip ring to 1000KW HT at WSS Tangnar-II as per detail in annexure 1
Repairs to slip-ring type 1000Kw HT motor of 13.5 cusec pumping unit at WSS Tangnar-II. as per detail in annexure 2
Repairs to contactor assembly of LR Starter of 1000KW, 11KV motor by way providing and fitting of 630A 3phase, AC3 ,415V power contactor assembly at WSS Tangnar stage –II as per detail in annexure 3
Repairs to contactor assembly of LR Starter of 1000KW, 11KV motor by way of repairing to 630 A contactor of 1350 HP 11KV Slip ring motor starter at WSS Tangnar stage –II as per detail in annexure 4
Repairs to contactor assembly of LR Starter of 1000KW, 11KV motor by way of replacement of damaged magnetic AC coil of main contactor TC-630 contactor assembly of 1000 KW LR starter panel of 13.5 cusec pumping unit at WSS Tangnar stage –II as per detail in annexure 5
Repairs/Servicing of liquid rotary starter of pumping unit no: I at WSS Tangnar-II as per detail in annexure 6
Repair to 100 KVA servo stablizer at Water Supply Scheme Tangnar stage-II.
Disassembling of 100 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer from the circuitry and shifting it from the site to work shop and back to site after conducting due repairs by loading it into the load carrier . The job further includes refitting back the voltage stabilizer into the circuitry. The job further includes cost on account of skilled/semi- skilled labour , tools and tackles required for the job and testing of Voltage stabilizer on full load. (The rate per job shall be allowed @ 12.98% of the quoted / negotiated rate of whole item.)
Disassembling of 100 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer by way of removing all the nuts and bolts and lifting the winding assembly along with core for assessing the damages and and refitting back the winding assembly into the voltage stabilizer tank along with core after conducting the due repairs . (The rate per job shall be allowed @ 6.49 % of the quoted / negotiated rate of whole item.)
Removing of damaged / burnt out windings from 100 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer leg and rewinding the same using copper winding of appropriate grade, insulation and specifications . thejob includes cost on account of skilled/semi-skilled labour required for the winding of Voltage stabilizer leg.The rates are included of the rebate on account of old scrap. (The rate per kg shall be allowed @ 1.63% of the quoted / negotiated rate of whole item.)
Providing and fitting of digital double display cards/Electronic mother board in place of damaged one. The card consists of low and high voltage cut relay and low and high voltage protection. (The rate per job shall be allowed @ 24.34% of the quoted / negotiated rate of whole item.)
Repairs to dimmers (01 no’s) by way re-alignment of the dimmer, replacement of damaged carbon brushes (The rate per job shall be allowed @ 19.48% of the quoted / negotiated rate of whole item.)
Repairs to the gear mechanism of the one phase by way of extraction of the damaged gear and pinion from it and providing and fitting of new gear and pinion. (The rate per job shall be allowed @ 8.12% of the quoted / negotiated rate of whole item.)
Impregnation / heat treatment of winding assembly of 100 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer by way of keeping it in an electric oven for about 24 hours and at appropriate temperature. (The rate per job shall be allowed @ 16.23% of the quoted / negotiated rate of whole item.)
Removing of damaged copper connection terminal bolt with washer and nut from 100 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer and providing and fitting of new copper connection terminal bolt with nut and washer. (The rate per job shall be allowed @ 2.43% of the quoted / negotiated rate of whole item.)
Removing of damaged backalite connection plate from 100 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer and providing and fitting of new backalite connection plate. (The rate per job shall be allowed @ 3.89% of the quoted / negotiated rate of whole item.)
Arresting of leakage in 100 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer tank along with radiator fins/tubes by way of soldering/ welding at the cracked spot (average length of spot = 1 cm) (The rate per job shall be allowed @ 3.89% of the quoted / negotiated rate of whole item.)
Providing and fitting of 53 KA di-electric strength T- OIL of standard make (The rate per ltr shall be allowed @ 0.45% of the quoted / negotiated rate of whole item.)
Filtration of existing T- oil upto desired strength and specifications. (The rate per ltr shall be allowed @ 0.07% of the quoted / negotiated rate of whole item.)
Total Amount forworks from s.no. 7 to7.12
Repairs to 110 V battery charger at water supply scheme Tangnar-II
Repairs to 110 V, 20 A battery charger by way of disconnecting the battery charger from the system, shifting from site to workshop, opening its cover (The rate per job shall be allowed @ 6.12% of the quoted / negotiated rate of whole item.)
Extraction of the damaged armature coil from the charger. The job includes complete rewinding of the armature coil using new copper coil as per sample and specifications. Old part extracted shall be property of the firm (The rate per job shall be allowed @ 36.73% of the quoted / negotiated rate of whole item.)
Providing and fitting of protection circuit module and rectifier diodes in place of damaged one. The job further includes providing of cable for interconnection of batteries and further connection with the battery charger. Testing of battery charger on no load and full load after carrying out repairs is included in the job (The rate per job shall be allowed @ 32.65% of the quoted / negotiated rate of whole item.)
Extraction of the damaged Display Unit and providing and fitting of new display unit. (The rate per job shall be allowed @ 24.50% of the quoted / negotiated rate of whole item.)
Total Value of s.no.8
Repairs to 36 V battery charger at water supply scheme Tangnar-II
Repairs to 36 V, 20 A battery charger by way of disconnecting the battery charger from the system, shifting from site to workshop, opening its cover (The rate per job shall be allowed @ 9.09% of the quoted / negotiated rate of whole item.)
Extraction of the damaged armature coil from the charger. The job includes complete rewinding of the armature coil using new copper coil as per sample and specifications. Old part extracted shall be property of the firm (The rate per job shall be allowed @ 36.36% of the quoted / negotiated rate of whole item.)
Providing and fitting of protection circuit module and rectifier diodes in place of damaged one. The job further includes providing of cable for interconnection of batteries and further connection with the battery charger. Testing of battery charger on no load and full load after carrying out repairs is included in the job (The rate per job shall be allowed @ 30.30% of the quoted / negotiated rate of whole item.)
Extraction of the damaged Display Unit and providing and fitting of new display unit. (The rate per job shall be allowed @ 24.25% of the quoted / negotiated rate of whole item.)
Total Value of s.no.9
Repairs to operating console at water supply scheme Tangnar stage-II
Repairs to operating console by way of dis-connecting the operating console from the system and then opening the back cover, extracting the damaged 32 A contactor from the operating console. The job includes providing and fitting of new 3-phase, 32A,3-pole contactor having 240V AC coil. The job further includes checking/ servicing of all parts of operating console and providing and fitting of axillary wiring in place of damaged one and then testing the same on full load. (The rate per job shall be allowed @ 62.04% of the quoted / negotiated rate of whole item.)
P/F of digital volt meter. The volt meter shall be square dial and 4” in size. Make: L&T/ Rishabh (The rate per job shall be allowed @ 14.60% of the quoted / negotiated rate of whole item.)
P/F of digital ampere meter along with CT coils. The volt meter shall be square dial and 4” in size. Make: L&T/ Rishabh. (The rate per job shall be allowed @ 23.36% of the quoted / negotiated rate of whole item.)
Total Value of s.no.10
Electrical/ Electronic repairs to VCB panel of unit at WSS Tangnar-IIas per detail in annexure 11
Repairs to FCMA Soft starter to motor of VT Pumping Unit at WSS Tangnar Stage-II as per detail in annexure 12
Replacement of damaged 695KW, 11KV FCMA soft starter with the stand by soft starter at WSS Tangnar-II. as per detail in annexure 13
Examining and testing the electrical equipment
Disconnecting the 11KV supply to HT VT motor by way of opening the terminal boxes and removing the connections and isolating it from the system. The VT motor shall be checked, inspected and fully examined with the help of multi meter and meger equipment of capacity above 3000Mega ohms for any sort of damage and continuity. The job includes reconnecting the terminal connections and completely tightening them and covering the lids of the terminal boxes. All the tools and tackles, skilled labour involved in the job shall be arranged by the firm. (The rate per job shall be allowed @ 17.40% of the quoted / negotiated rate of whole item.)
Disconnecting the 11KV supply to the capacitor bank by way of opening the supply connections at the connection terminals and thoroughly inspecting the fuses and internal wiring and examining the capacitors. The job includes removing all the dust and dirt from the capacitor bank by using electrical blower to completely clean the capacitor panel. The job includes reconnecting the terminal connections and completely tightening. All the tools and tackles, skilled labour involved in the job shall be arranged by the firm. (The rate per job shall be allowed @ 20.90% of the quoted / negotiated rate of whole item.)
Disconnecting the 11 KV supply line to the soft starter by way of opening the back cover of the starter and disconnecting the 11KV supply line from the coil terminals. The job includes testing and examining the epoxy coils for any sort of damage using appropriate electrical equipment .The control wiring shall be thoroughly checked and inspected with all the connections being tightened. The vacuum contactor shall be examined for its start and run operation. The temperature controller and all other electrical gadgets fitted in the soft starter shall be completely inspected and examined for proper operation. The job includes removing all the dust and dirt from the soft starter panel by using electrical blower to completely clean the panel. The 11KV cables shall then be connected back to the terminals and the cover be fitted back. All the tools and tackles, skilled labour involved in the job shall be arranged by the firm. (The rate per job shall be allowed @ 20.90% of the quoted / negotiated rate of whole item.)
Disconnecting the 11 KV supply line to the VCB control panel by way of opening the back cover of the panel and disconnecting the 11KV supply line from the VCB terminals. The job includes extraction of VCB from the panel on the trolley and testing and examining the VCB for any sort of damage using appropriate electrical equipments. The VCB shall then be fitted back in the panel and the control wiring shall be thoroughly checked and inspected with all the connections being tightened. The electrical gadgets fitted in the panel shall be completely inspected and examined for proper operation. The job includes removing all the dust and dirt from the control panel by using electrical blower to completely clean the panel. The 11KV cables shall then be connected back to the terminals and the cover be fitted back. All the tools and tackles, skilled labour involved in the job shall be arranged by the firm. (The rate per job shall be allowed @ 20.90% of the quoted / negotiated rate of whole item.)
Disconnecting all the cables of different sizes from the electrical equipment and testing and examining the same for any sort of fault by using advanced multi meters for continuity and earth faults. The job includes reconnecting the cables and tightening them in their respective terminals. All the tools and tackles, skilled labour involved in the job shall be arranged by the firm (The rate per job shall be allowed @ 19.90% of the quoted / negotiated rate of whole item.)
Total Value of s.no. 14
Cleaning/ Grass Cutting of 33KV / 11 KV sub stations at WSS Tangnaras per detail in annexure 15
Replacement of CT coil of 800A out-going panel at WSS Tangnar-IIas per detail in annexure 16
Replacement of motor protection relay to out-going panel of unit 1/2/3/4 at WSS Tangnar-IIas per detail in annexure 17
Replacement of OC/EF relay to 800A Incoming panel at WSS Tangnar-IIas per detail in annexure 18
Replacement of High Speed Master Trip relay to 800A Incoming/ Outgoing panels at WSS Tangnar-IIas per detail in annexure 19
Replacement of Trip circuit supervision relay to 800A Incoming panels at WSS Tangnar-IIas per detail in annexure 20
Replacement of multifunction meter to Out Going / In coming panel at WSS Tangnar-IIas per detail in annexure 21
Replacement of multifunction meter to soft starter panel at WSS Tangnar-I as per detail in annexure 22
Replacement of annunciation window installed on Out Going panel of pumping unit 1/2/3/4 at WSS Tangnar-IIas per detail in annexure 23
Replacement of annunciation window to In coming panel 1 / 2 at WSS Tangnar-IIas per detail in annexure 24
Replacement of ampere meter to 800A Out Going / In coming panel at WSS Tangnar-IIas per detail in annexure 25
Replacement of temperature scanner to Out Going panel of pumping unit 1/2/3/4 at WSS Tangnar-IIas per detail in annexure 26
Repairs to soft starter of pumping unit motor at Water supply scheme Tangnar stage-Ias per detail in annexure 27
Repairs to operating console at water supply scheme Tangnar stage-I as per detail in annexure 28
Repairs to 200 KVA voltage stabilizer at WSS Tangnar stage –I
Disassembling of 200 KVA , 3 phase , 415 ±15 % Volt manually operated oil cooled voltage stabilizer from the circuitry and shifting it from the site to work shop and back to site after conducting due repairs by loading it into the vehicle . The job further includes refitting back the voltage stabilizer into the circuitry. The job further includes cost on account of skilled/semi- skilled labour , tools and tackles required for the job and testing of Voltage stabilizer on full load. The rate per job shall be allowed @ 7.99% of the quoted / negotiated rate of whole item.)
Disassembling of 200 KVA , 3 phase , 415 ±15 % Volt manually operated oil cooled voltage stabilizer by way of removing all the nuts and bolts and lifting the winding assembly along with core for assessing the damages and and refitting back the winding assembly into the voltage stabilizer tank along with core after conducting the due repairs . The rate per job shall be allowed @ 7.10% of the quoted / negotiated rate of whole item.)
Removing of damaged / burnt out windings from 200 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer leg and rewinding the same using copper winding of appropriate grade, insulation and specifications . the job includes cost on account of skilled/semi-skilled labour required for the winding of Voltage stabilizer leg.The rates are included of the rebate on account of old scrap. The rate per kg shall be allowed @ 0.89% of the quoted / negotiated rate of whole item.)
Removing of damaged plate type voltage regulator switch from 200 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer and providing and fitting of new plate type voltage regulator switch having copper contact points with 6 steps . the job includes cost on account of skilled/semi-skilled labour required for work The rate per job shall be allowed @ 56.83% of the quoted / negotiated rate of whole item.)
Removing of damaged plate type voltage regulator switch from 200 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer and providing and fitting of new copper contact point -01 no. complete of appropriate specifications to plate type voltage regulator switch having copper contact points with 6 steps . The job includes cost on account of refitting back the voltage regulator switch and skilled/semi-skilled labour required for work. The rate per job shall be allowed @ 11.54% of the quoted / negotiated rate of whole item.)
Impregnation / heat treatment of winding assembly of 200KVA , 3 phase , 415 ±15 % Volt voltage stabilizer by way of keeping it in an electric oven for about 24 hours and at appropriate temperature. The rate per job shall be allowed @ 19.90% of the quoted / negotiated rate of whole item.) The rate per job shall be allowed @ 9.77% of the quoted / negotiated rate of whole item.)
Removing of damaged copper connection terminal bolt with washer and nut from 200 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer and providing and fitting of new copper connection terminal bolt with nut and washer. The rate per job shall be allowed @ 1.33% of the quoted / negotiated rate of whole item.)
Removing of damaged backalite connection plate from 200 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer and providing and fitting of new backalite connection plate. The rate per job shall be allowed @ 2.13% of the quoted / negotiated rate of whole item.)
Arresting of leakage in 200 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer tank along with radiator fins/tubes by way of soldering/ welding at the cracked spot (average length of spot = 1 cm) The rate per job shall be allowed @ 2.13% of the quoted / negotiated rate of whole item.)
Providing and fitting of 53 KA di-electric strength T- OIL of standard make The rate per ltr shall be allowed @ 0.25% of the quoted / negotiated rate of whole item.)
Filtration of existing T- oil upto desired strength and specifications. The rate per ltr shall be allowed @ 0.04% of the quoted / negotiated rate of whole item.)
Total Value of s.no.29
Repairs to 500 KVA voltage stabilizer at WSS Tangnar stage –I
Disassembling of 500 KVA , 3 phase , 415 ±15 % Volt manually operated oil cooled voltage stabilizer from the circuitry and shifting it from the site to work shop and back to site after conducting due repairs by loading it into the load carrier . The job further includes refitting back the voltage stabilizer into the circuitry. The job further includes cost on account of skilled/semi- skilled labour , tools and tackles required for the job and testing of Voltage stabilizer on full load. The rate per job shall be allowed @ 7.40% of the quoted / negotiated rate of whole item.)
Disassembling of 500 KVA , 3 phase , 415 ±15 % Volt manually operated oil cooled voltage stabilizer by way of removing all the nuts and bolts and lifting the winding assembly along with core for assessing the damages and and refitting back the winding assembly into the voltage stabilizer tank along with core after conducting the due repairs . The rate per job shall be allowed @ 6.58% of the quoted / negotiated rate of whole item.)
Removing of damaged / burnt out windings from 500 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer leg and rewinding the same using copper winding of appropriate grade, insulation and specifications . the job includes cost on account of skilled/semi-skilled labour required for the winding of Voltage stabilizer leg.The rates are included of the rebate on account of old scrap. The rate per kg shall be allowed @ 0.82% of the quoted / negotiated rate of whole item.)
Removing of damaged plate type voltage regulator switch from 500 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer and providing and fitting of new plate type voltage regulator switch having copper contact points with 6 steps . the job includes cost on account of skilled/semi-skilled labour required for work. The rate per job shall be allowed @ 57.56% of the quoted / negotiated rate of whole item.)
Removing of damaged plate type voltage regulator switch from 500 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer and providing and fitting of new copper contact point -01 no. complete of appropriate specifications to plate type voltage regulator switch having copper contact points with 6 steps . The job includes cost on account of refitting back the voltage regulator switch and skilled/semi-skilled labour required for work. The rate per job shall be allowed @ 10.69% of the quoted / negotiated rate of whole item.)
Impregnation / heat treatment of winding assembly of 500KVA , 3 phase , 415 ±15 % Volt voltage stabilizer by way of keeping it in an electric oven for about 24 hours and at appropriate temperature. The rate per job shall be allowed @ 11.51% of the quoted / negotiated rate of whole item.)
Removing of damaged copper connection terminal bolt with washer and nut from 500 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer and providing and fitting of new copper connection terminal bolt with nut and washer. The rate per job shall be allowed @ 1.235% of the quoted / negotiated rate of whole item.)
Removing of damaged backalite connection plate from 500 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer and providing and fitting of new backalite connection plate. The rate per job shall be allowed @ 1.97% of the quoted / negotiated rate of whole item.)
Arresting of leakage in 500 KVA , 3 phase , 415 ±15 % Volt voltage stabilizer tank along with radiator fins/tubes by way of soldering/ welding at the cracked spot (average length of spot = 1 cm) The rate per job shall be allowed @ 1.97% of the quoted / negotiated rate of whole item.)
Providing and fitting of 53 KA di-electric strength T- OIL of standard make The rate per ltr shall be allowed @ 0.23% of the quoted / negotiated rate of whole item.)
Filtration of existing T- oil upto desired strength and specifications. The rate per ltr shall be allowed @ 0.035% of the quoted / negotiated rate of whole item.)
Total Value of s. no. 30
Repairs to 50KVA servo stabilizer at Water Supply scheme Tangnar
Disassembling of 50 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer from the circuitry and shifting it from the site to work shop and back to site after conducting due repairs by loading it into the load carrier . The job further includes refitting back the voltage stabilizer into the circuitry. The job further includes cost on account of skilled/semi- skilled labour , tools and tackles required for the job and testing of Voltage stabilizer on full load. The rate per job shall be allowed @ 8.96% of the quoted / negotiated rate of whole item.)
Disassembling of 50 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer by way of removing all the nuts and bolts and lifting the winding assembly along with core for assessing the damages and and refitting back the winding assembly into the voltage stabilizer tank along with core after conducting the due repairs . The rate per job shall be allowed @ 8.96% of the quoted / negotiated rate of whole item.)
Removing of damaged / burnt out windings from 50 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer leg and rewinding the same using copper winding of appropriate grade, insulation and specifications . the job includes cost on account of skilled/semi-skilled labour required for the winding of Voltage stabilizer leg.The rates are included of the rebate on account of old scrap. The rate per kg shall be allowed @ 2.25% of the quoted / negotiated rate of whole item.)
Providing and fitting of digital double display cards/Electronic mother board in place of damaged one. The card consists of low and high voltage cut relay and low and high voltage protection. The rate per job shall be allowed @ 22.41% of the quoted / negotiated rate of whole item.)
Repairs to dimmers (01 no’s) by way re-alignment of the dimmer, replacement of damaged carbon brushes The rate per job shall be allowed @ 17.93% of the quoted / negotiated rate of whole item.)
Repairs to the gear mechanism of the one phase by way of extraction of the damaged gear and pinion from it and providing and fitting of new gear and pinion. The rate per job shall be allowed @ 6.72% of the quoted / negotiated rate of whole item.)
Impregnation / heat treatment of winding assembly of 50 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer by way of keeping it in an electric oven for about 24 hours and at appropriate temperature. The rate per job shall be allowed @ 17.93% of the quoted / negotiated rate of whole item.)
Removing of damaged copper connection terminal bolt with washer and nut from 50 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer and providing and fitting of new copper connection terminal bolt with nut and washer. The rate per job shall be allowed @ 3.36% of the quoted / negotiated rate of whole item.)
Removing of damaged backalite connection plate from 50 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer and providing and fitting of new backalite connection plate. The rate per job shall be allowed @ 5.38% of the quoted / negotiated rate of whole item.)
Arresting of leakage in 50 KVA , 3 phase , 415 ±15 % oil cooled Servo stabilizer tank along with radiator fins/tubes by way of soldering/ welding at the cracked spot (average length of spot = 1 cm) The rate per job shall be allowed @ 5.38% of the quoted / negotiated rate of whole item.)
Providing and fitting of 53 KA di-electric strength T- OIL of standard make The rate per ltr shall be allowed @ 0.63% of the quoted / negotiated rate of whole item.)
Filtration of existing T- oil upto desired strength and specifications. The rate per ltr shall be allowed @ 0.09% of the quoted / negotiated rate of whole item.)
Total Value of s.no.31
Repairs to 160.5 KVAR automatic power factor correction panel by way of disconnecting the power supply to the panel and then carrying out the following repairs:
Replacement of damaged MCCB by way of the extraction of damaged/burnt out 400 A MCCB .The job includes providing and fitting of 400 ampere, 415 V, 3-pole, 50 Hz MCCB in place of damaged one. The breaking capacity of the MCCB shall be 50 kA and shall conform to IS/IEC 60947-2 standards. The MCCB to be of L&T (D-sine) or Schiender make The rate per job shall be allowed @ 49.37% of the quoted / negotiated rate of whole item.)
Replacement of damaged APFC relay by way of the extraction of damaged/burnt out relay .The job includes providing and fitting of power factor correction relay.The relay to be of BELUK/L&T make and shall conform to latest IS specifications. The rate per job shall be allowed @ 19.75% of the quoted / negotiated rate of whole item.)
Replacement of damaged low voltage MPP capacitors by way of the extraction of damaged/burnt out capacitors and then providing and fitting of new capacitors of below mentioned capacities:
3K VAR The rate per job shall be allowed @ 1.27 % of the quoted / negotiated rate of whole item.)
5 K VAR The rate per job shall be allowed @ 2.11% of the quoted / negotiated rate of whole item.)
7.5K VAR The rate per job shall be allowed @ 3.17% of the quoted / negotiated rate of whole item.)
10 K VAR The rate per job shall be allowed @ 4.23% of the quoted / negotiated rate of whole item.)
12.5 KVAR The rate per job shall be allowed @ 5.29% of the quoted / negotiated rate of whole item.)
15 KVAR The rate per job shall be allowed @ 6.35% of the quoted / negotiated rate of whole item.)
20 KVAR The rate per job shall be allowed @ 8.46% of the quoted / negotiated rate of whole item.)
Total Value of s.no. 32
P/F of 12V 80Ah battery Make Excide/ Amron/Sukam
Repairs/replacements to the lighting system at Water Supply Scheme Tangnar.
Repairs to flood light luminary fitted on the tubular pole in the premises of the of the pump station by way of disconnecting the luminary from the system, dismantling it from the pole arm and then extracting the damaged metal halide lamp from the luminary. The job includes providing and fitting of new Philips/Havels/ABB make 400W, 200-250 V metal halide single ended lamp in place of damaged one. The job further includes providing and fitting of minor wiring as per site requirement.Assembling the luminary, fixing back on the wall, connecting with the system and testing of the same is included in the job. All the tools and tackles, skilled labour required for the job is to be arranged by the firm. The rate per job shall be allowed @ 2.07% of the quoted / negotiated rate of whole item.)
Repairs to flood light luminary fitted on the inside and outside walls of the pump station by way of disconnecting the luminary from the system, dismantling it and then extracting the damaged metal halide lamp from the luminary. The job includes providing and fitting of new Philips make 400W, 200-250 V metal halide single ended lamp in place of damaged one. The job further includes providing and fitting of minor wiring as per site requirement.Assembling the luminary, fixing back on the wall, connecting with the system and testing of the same is included in the job. All the tools and tackles required for the job is to be arranged by the firm The rate per job shall be allowed @ 1.55% of the quoted / negotiated rate of whole item.)
Repairs to high bay luminaries by way of disconnecting it from the system and then dismantling it from the ceiling of the pump house and then extracting the damaged mercury vapour lamp from the luminary and then providing and fitting of 250 W, 220-250 V mercury vapour lamp in place of damaged one. The job further includes providing and fitting of minor wiring as per site requirement. Assembling the luminary, fixing on the wall, connecting with the system and testing of the same is included in the job. All the tools and tackles required for the job is to be arranged by the firm The rate per job shall be allowed @ 1.29% of the quoted / negotiated rate of whole item.) Make Philips, Havells,ABB
Providing and fitting of luminary assembly consisting of LED. The luminary assembly is to be fixed on the walls of the pump house bay by suitable sized brackets under the machine floor. The job further includes providing and fitting of appropriate size copper wire and connecting of the luminaries with the electrical system. Acceptable make Havells/Philips/Abb
25 W The rate per job shall be allowed @ 2.76% of the quoted / negotiated rate of whole item.)
40 W The rate per job shall be allowed @ 3.88% of the quoted / negotiated rate of whole item.)
60 W The rate per job shall be allowed @ 5.17% of the quoted / negotiated rate of whole item.)
Providing and fitting of choke for 400W, 200-250 Philips make metal halide flood light luminary. The rate per job shall be allowed @ 1.55% of the quoted / negotiated rate of whole item.)
Providing and fitting of ignitor for 400W, 200-250 V Philips make metal halide flood light luminary. The rate per job shall be allowed @ 0.43% of the quoted / negotiated rate of whole item.)
Providing /fitting of 60 W LED bulbs for the bulk head luminaries installed under the machine floor. Acceptable make: Philips/Surya/Syska The rate per job shall be allowed @ 0.17% of the quoted / negotiated rate of whole item.)
Providing /fitting of B22 type angle /Straight bulb Holder for installing led Bulbs make Anchor/ SSK/GM The rate per job shall be allowed @ 0.04% of the quoted / negotiated rate of whole item.)
Providing/Fitting of 16A-20A heavy duty 3 Pin Mult plug socket with safety shutter make Anchor/ SSK/GM The rate per job shall be allowed @ 0.22% of the quoted / negotiated rate of whole item.)
Providing/Fitting of 6A 2 Pin socket make Anchor/ SSK/GM The rate per job shall be allowed @ 0.11% of the quoted / negotiated rate of whole item.)
Providing/Fitting of 10A 2 Pin socket make Anchor/ SSK/GM The rate per job shall be allowed @ 0.11% of the quoted / negotiated rate of whole item.)
Providing/Fitting of 16A-20A heavy duty- switch make Anchor/ SSK/GM The rate per job shall be allowed @ 0.17% of the quoted / negotiated rate of whole item.)
Providing/Fitting of 6A-10A switch make Anchor/ SSK/GM The rate per job shall be allowed @ 0.05% of the quoted / negotiated rate of whole item.)
Supply at site, laying, testing of 02 core 6 sq.mm XLPE Aluminum armoured cable for connecting the luminaries with the main power panel. The rate per mtr shall be allowed @ 0.13% of the quoted / negotiated rate of whole item.) Make Havells, Legrand, Polycap
Providing and fitting of 2.5 sq. mm copper conductor for connecting luminaries to the connection box at the bottom of the pole. The rate per mtr shall be allowed @ 0.04% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 06A L&T/Schiender/ABB The rate per job shall be allowed @ 0.22% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 06A (DP) L&T/Schiender/ABB The rate per job shall be allowed @ 0.60% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 10A L&T/Schiender/ABB The rate per job shall be allowed @ 0.22% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 16A L&T/Schiender/ABB The rate per job shall be allowed @ 0.22% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 20A L&T/Schiender/ABB The rate per job shall be allowed @ 0.22% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 32A (DP) L&T/Schiender/ABB The rate per job shall be allowed @ 0.60% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 32A (TP) L&T/Schiender/ABB The rate per job shall be allowed @ 0.98% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 40 A (DP) L&T/Schiender/ABB The rate per job shall be allowed @ 0.97% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 40 A (TP) L&T/Schiender/ABB The rate per job shall be allowed @ 1.50% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 63A (DP) L&T/Schiender/ABB The rate per job shall be allowed @ 0.97% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 63A (TP) L&T/Schiender/ABB The rate per job shall be allowed @ 1.50% of the quoted / negotiated rate of whole item.)
Providing and fitting of 400 ampere,415 V, 4-pole, 50 Hz MCCB in place of damaged one.The breaking capacity of the MCCB shall be 50 kA and shall conform to IS/IEC 60947-2 standards. The MCCB to be of L&T (D-sine) Schiender/ ABB make. The MCCB is to be fitted in the lighting panel. The rate per job shall be allowed @ 27.58% of the quoted / negotiated rate of whole item.)
Providing and fitting of 100 ampere,415 V, 4-pole, 50 Hz MCCB in place of damaged one.The breaking capacity of the MCCB shall be 36 kA and shall conform to IS/IEC 60947-2 standards. The MCCB to be of L&T (D-sine) Schiender/ ABB make.The MCCB is to be fitted in the submersible motor panel. The rate per job shall be allowed @ 6.90% of the quoted / negotiated rate of whole item.)
Providing and fitting of 250 ampere,415 V, 4-pole, 50 Hz MCCB in place of damaged one.The breaking capacity of the MCCB shall be 50 kA and shall conform to IS/IEC 60947-2 standards. The MCCB to be of L&T (D-sine), Schiender/ABB make. The MCCB is to be fitted in the lighting panel. The rate per job shall be allowed @ 22.41% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 1.0 Sqmm cable Make Havells, Legrand, Polycap The rate per mtr shall be allowed @ 0.02% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 1.5 Sqmm cable Make Havells, Legrand, Polycap The rate per mtr shall be allowed @ 0.03% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 2.5 Sqmm cable Make Havells, Legrand, Polycap The rate per mtr shall be allowed @ 0.04% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 4 Sqmm cable Make Havells, Legrand, Polycap The rate per mtr shall be allowed @ 0.07% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 12Sqmm 2 cores AL cable Make Havells, Legrand, Polycap. The rate per mtr shall be allowed @ 0.13% of the quoted / negotiated rate of whole item.)
P/F of industrial Exhaust Fan (Size – 24” ).The Exhaust fan is to be fitted in the openings of the wall about 20 ft above MFL. Accepted make: Crompton/Philips/Havells The rate per job shall be allowed @ 12.93% of the quoted / negotiated rate of whole item.)
Providing of Table Fan Havells, Crompton,Philips, Havells The rate per job shall be allowed @ 2.15% of the quoted / negotiated rate of whole item.)
Total Value of s.no.34
Minor repairs/replacements to the incoming/out-going/starter panels at Water Supply Scheme Tangnar.
Providing /Fitting of Contactor MNX-A1 of make L&T, Havells, ABB The rate per job shall be allowed @ 1.62% of the quoted / negotiated rate of whole item.)
Providing /Fitting of Contactor MNX-9 of make L&T, Havells, ABB The rate per job shall be allowed @ 1.62% of the quoted / negotiated rate of whole item.)
Providing /Fitting of Contactor MNX-12 of make L&T, Havells, ABB The rate per job shall be allowed @ 1.84% of the quoted / negotiated rate of whole item.)
Providing /Fitting of Contactor MNX-18 of make L&T, Havells, ABB The rate per job shall be allowed @ 2.09% of the quoted / negotiated rate of whole item.)
Providing /Fitting of Contactor MNX-25 of make L&T, Havells, ABB The rate per job shall be allowed @ 2.50% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 06A of make L&T, Havells, ABB The rate per job shall be allowed @ 0.51% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 06A (DP) of make L&T, Havells, ABB The rate per job shall be allowed @ 1.40% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 10A of make L&T, Havells, ABB The rate per job shall be allowed @ 0.51% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 16A of make L&T, Havells, ABB The rate per job shall be allowed @ 0.51% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 20A of make L&T, Havells, ABB The rate per job shall be allowed @ 0.51% of the quoted / negotiated rate of whole item.).
Providing /Fitting of MCB 32A (DP) of make L&T, Havells, ABB The rate per job shall be allowed @ 1.40% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCB 32A (TP) of make L&T, Havells, ABB The rate per job shall be allowed @ 2.29% of the quoted / negotiated rate of whole item.)
Providing /Fitting of MCCB 630A of make L&T, Havells, ABB The rate per job shall be allowed @ 76.83% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 1.5 Sqmm cable (8 core) copper Control CablingMake Havells, Legrand, Polycap The rate per mtr shall be allowed @ 0.61% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 1.5 Sqmm cable 12 Core (Copper)Control CablingMake Havells, Legrand, Polycap The rate per mtr shall be allowed @ 0.80% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 2.5 Sqmm cable 2 core (Copper)Control CablingMake Havells, Legrand, Polycap The rate per mtr shall be allowed @ 0.19% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 2.5 Sqmm cable 4 Core (Copper) Control CablingMake Havells, Legrand, Polycap Make Havells, Legrand, Polycap5 The rate per mtr shall be allowed @ 0.34% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 4 Sqmm cable 4 Core (Copper) Control Cabling The rate per mtr shall be allowed @ 0.76% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 10 Sqmm cable 4 core (Aluminum)Control CablingMake Havells, Legrand, Polycap The rate per mtr shall be allowed @ 0.30% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 70 Sqmm cable Single core armoured (Copper) XLPE cable Make Havells, Legrand, Polycap The rate per mtr shall be allowed @ 2.02% of the quoted / negotiated rate of whole item.)
Providing /Fitting of 120 Sqmm cable3.5-core armoured XLPE (Aluminium) cable Make Havells, Legrand, Polycap The rate per mtr shall be allowed @ 1.35% of the quoted / negotiated rate of whole item.)
Total Value of s.no.35
Repairs to 800A ACB at WSS Tangnar Stage 1st as per the detail in Annexure. 35
Providing/ Fitting of Aluminum Bus bars of below sizes
1” x 4 mm The rate per mtr shall be allowed @ 5.33 % of the quoted / negotiated rate of whole item.)
1” x 6 mm The rate per mtr shall be allowed @ 7.26% of the quoted / negotiated rate of whole item.)
2” x 4 mm The rate per mtr shall be allowed @ 8.96% of the quoted / negotiated rate of whole item.)
2” x 6 mm The rate per mtr shall be allowed @ 13.08% of the quoted / negotiated rate of whole item.)
4” x 6 mm The rate per mtr shall be allowed @ 29.06% of the quoted / negotiated rate of whole item.)
4” x 8 mm The rate per mtr shall be allowed @ 36.31% of the quoted / negotiated rate of whole item.)
Total Value of s.no.37
Providing/ Fitting of Aluminum Thimbles to the cable end. The thimbles need to be duly crimped using suitable size crimping tool
70 Sq mm The rate per mtr shall be allowed @ 13.56% of the quoted / negotiated rate of whole item.)
95 Sq mm The rate per mtr shall be allowed @ 14.69% of the quoted / negotiated rate of whole item.)
120 Sq mm The rate per mtr shall be allowed @ 15.25% of the quoted / negotiated rate of whole item.)
185 Sq mm The rate per mtr shall be allowed @ 15.82% of the quoted / negotiated rate of whole item.)
240 Sq mm The rate per mtr shall be allowed @ 18.08% of the quoted / negotiated rate of whole item.)
300 Sq mm The rate per mtr shall be allowed @ 22.60% of the quoted / negotiated rate of whole item.)
Total Value of s.no.38
Repairs to connection box of 80 HP electrical motor at WSS Tangnar-I as per detail in Annexure 36
Providing/ Fitting of spreader Set for various size MCCB’s at WSS Tangnar-Ias per detail in Annexure 37
Repairs to electric control panel of sludge pumps WSS Tangnar-
Replacement of motor starter contactor by way of extraction of the damaged starter from the panel box and then providing and fitting of new contactor. The contactor to be of siemens model-3TF47.The contactor shall be equipped with auxillary contact block and overload relays. The rate per job shall be allowed @ 90.91% of the quoted / negotiated rate of whole item.)
Replacement of motor protection relay of the panel box by way of extraction of the damaged relay from the panel and then providing and fitting of new relay. The relay to be of siemens make SPG D2 model or equivalent in L&T/ABB The rate per job shall be allowed @ 9.09% of the quoted / negotiated rate of whole item.)
Total Value of s. no. 41
Repairs to 80HP motor of pumping unit no 1/2/3 at WSS Tangnar-I
Impregnation to the 80 HP VT motor by way of decoupling the 80 HP vertical motor from the 11-cusec VT pump after disconnecting all the power cables from the connection box of the motor and then shifting the motor to a safer place within the pump house. The job includes opening the upper shield cover, extracting the rotor from the stator and cleaning the windings from the dust and other foreign matter using air blower. The job includes impregnating the windings by applying approved Dr. Beck Varnish and drying by suitable means. Reassembling the motor, coupling it with the motor and testing on load The rate per job shall be allowed @ 52.94% of the quoted / negotiated rate of whole item.)
Repairs to 80HP motor by way of disconnecting the power supply to motor. Job further includes removing of old damaged copper leads from motor. The job further includes providing/ fitting ofnew copper leads in place of damaged one. Job includes providing / Fitting of terminal end connectors to the newly connected joint. The job further includes brazing of copper cable end terminals with winding terminals using brazing tools like brazing torch, copper brazing rods, flux rods etc. The brazing to be be carried out by technically sound personal having expertise in work. The winding of the motor is to be protected by insulated sheets from any kind of damage during the brazing process. The job includes insulation of brazed joint of motor using f-class insulation tapping. Providing and fitting of the copper thimbles to the cable ends duly crimped and tapped is included in the job. Reconnecting the power supply to motor and then testing on idle load and then on full load The rate per job shall be allowed @ 47.06% of the quoted / negotiated rate of whole item.)
Total Value of s.no. 42
Replacement of antipumping Relay to incoming/ OutGoing/Outdoor VCB Panels at WSS Tangnar Stage 2 as per detail in Annexure 40
M/S ALAMDAR ELECTRICAL AND MECHANICAL WORKS
M/S UNIVERSAL ENTERPRISES
Bahir Brothers
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .