Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.5 LAccepted-AOC 0 | ₹15.5 L Quoted ₹16.5 L | L1 | Accepted-AOC Accepted being lowest |
| 2 | L2₹17.8 L+₹1.4 L (8.41%)Rejected-Finance | ₹17.8 L+₹1.4 L (8.41%) | L2 | Rejected-Finance Rejected being other than lowest |
| 3 | L3₹19.5 L+₹3.1 L (18.8%)Rejected-Finance | ₹19.5 L+₹3.1 L (18.8%) | L3 | Rejected-Finance Rejected being other than lowest |
Tender Value
₹18 L
EMD Value
₹36,000
Closing Date
13 Mar 2023, 10:00 amClosed
GE (I) (CG) RATNAGIRI
Garrison Engineer I CG Ratnagiri SLUY Shed Plot W19 23 MIDC Mirjole Ratnagiri 415 639
REPAIR/MAINTENANCE OF INTERNAL ELECTRIFICATION, COOLING APPLIANCES, UG CABLE, PIPELINE, AND DG SET AT ICGAS AND ICGS RATNAGIRI UNDER GE(I) (CG) RATNAGIRI
2023_MES_573443_2
8163/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
RATNAGIRI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (I) (CG) RATNAGIRI
₹36,000
Yes
30 Mar 2023
14 Feb 2023
14 Mar 2023
14 Feb 2023
13 Mar 2023
22 Feb 2023
Amount
Repair /Replacement of internal electrification M&L for taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendents, regulators, sockets etc removing materials for taking credit and making good disturbed surfaces of walls, floors, etc complete all as specified and directed.
M&L for taking down unservicable/partly unservicable light fittings any type, tube light fitting and fixtures, etc, and making good to the disturbed surfaces of walls/floor etc to macth with existing surfaces including white washing/colour washing/distempering to match with existing wall/floor/ceiling finishes complete all as specified and directed.
M&L for dismantling unserviceable main switch/ kitkat DBs/ MCB including wooden board from existing position and making good disturbed surfaces of wall to match with existing surfaces
M&L for taking down sub main wiring with conduit of any size/capacity including conduit complete all as specified and making good disturbed sufaces to match with the existing surfaces.
S&F point wiring with PVC insulated unsheathed FRLS stranded copper conductor cable of size 1.5 Sq mm, with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sq mm stranded for earth continuity wire, to be drawn in and including, PVC medium grade conduit not less then 25 mm dia.concealed in walls/roof/floors with GI sheet metal sunken modular switch/\- terminal Box 1.2 mm thick with Zinc coating 0f 120 GSM and Modular plate and brass screws with cup washers all as directed and specified Note : (1) Rate is inclusive of Cutting/chases of wall/floor/ceiling (a)One light point controlled by one, one way switch
(b) One ceiling /exhaust fan point controlled by one switch and regulator
(c) One 3 pin 5 amp socket out point on the same board with other switches.
(d) One3 pin 5 amps socket out let point on independent board
(e) one light point controlled by two 2-way switches
All as per same in item No 5 above but for one socket outlet 16 Amp on independent board with 2.5 Sq mm cable and 2.5 Sq mm earth wire. ( power point 15 Amps sockets)
S&F modular Switch piano flush type single pole one way 5 amps complete all as specified and directed.
S&F modular Switch piano flush type double pole two way 5 amps complete all as specified and directed.
S&F modular Switch piano flush type single pole one way 15 amps complete all as specified and directed.
S&F modular Socket out let 2 in one, 5/3 pin 5Amp complete all as specified and directed.
S&F modular Bell push, flush type 5 Amps complete all as specified and directed.
S&F modular Electronic regulator 100/120 Watt step type complete all as specified and directed.
S&F Call bell AC-230 Volt single pole ding dong complete all as specified and directed.
S&F modular white cover plate with frame 3 module Make Legrand, Schneider, hager or equivalent make complete all as specified and directed.
S&F LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complet with all assoceries intenallt prewired & including connecting up with 2 core flexible cppper conductor cable with sutable size complete all as specified and directed.
S &F LED tube light fittings decorative ultra slim linear fixture with extruded alluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x20 Watt ,4 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & including connecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nos etc.complete all as specified and directed.
S&F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x10 Watt ,2 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & including connecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nos etc complete all as specified and directed.
S&F Sub main wiring power/circuit using PVC insulated unsheathed FRLS, stranded copper conductor cable 2 Single core of size 16 Sqmm, earth continuity conductor of size 16 Sqmm to be drawn through in and including PVC conduit concealed in walls/roof/floors complete all as specified and directed. Notes:- (i)Two wires of 16 sqmm and one wire of 16 sqmm & PVC conduit shall be measured as one unit.
S&F Sub main wiring power/circuit using PVC insulated unsheathed FRLS, stranded copper conductor cable 2 Single core of size 10 Sqmm, earth continuity conductor of size 10 Sqmm to be drawn through in and including PVC conduit concealed in walls/roof/floors complete all as specified and directed. Notes:- (i)Three wires of 10 sqmm & PVC conduit shall be measured as one unit..
S&F Sub main wiring power/circuit using PVC insulated unsheathed FRLS, stranded copper conductor cable 2 Single core of size 6 Sqmm, earth continuity conductor of size 6 Sqmm to be drawn through in and including PVC conduit concealed in walls/roof/floors complete all as specified and directed.Notes:- (i)Two wires of 6 sqmm and one wire of 6 sqmm & PVC conduit shall be measured as one unit
S&F Sub main wiring power/circuit using PVC insulated unsheathed FRLS, stranded copper conductor cable 2 Single core of size 4 Sqmm, earth continuity conductor of size 4 Sqmm to be drawn through in and including PVC conduit concealed in walls/roof/floors complete all as specified and directed.Notes:- (i)Two wires of 4 sqmm and one wire of 4 sqmm & PVC conduit shall be measured as one unit.
S&F Sub main wiring power/circuit using PVC insulated unsheathed FRLS, stranded copper conductor cable 2 Single core of size 2.5 Sqmm, earth continuity conductor of size 2.5 Sqmm to be drawn through in and including PVC conduit concealed in walls/roof/floorscomplete all as specified and directed. Notes:- (i)Two wires of 2.5 sqmm and one wire of 2.5 sqmm & PVC conduit shall be measured as one unit
S&F Sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 2 Single core of size 1.5 Sqmm, earth continuity conductor of size 1.5 Sqmm to be drawn through in and including PVC conduit fixed on walls/roof/floors all as directed by Engineer in Charge.Notes:- (i)Two wires of 1.5 sqmm and one wire of 1.5 sqmm PVC conduit shall be measured as one unit.(For Bldg security light & Staircase lighting)
S&F MCCB DB VERTICAL TYPE , suitable for 125 amps MCCB as incommer,made of sheet steel , powder painted with NUTRAL bus bar 200 A, neutral link, IP-43-IK09 protection grade , 415Volts TPN with 4 way Double door complete all as specified and directed. L&T CAT NO-DBVTL004DD/ LEGRAND CAT NO-607913/ / schneider/ ABB
S&F MCB DB made of sheet steel , powder painted with NUTRAL bus bar 200 A, neutral link, earth bar and Din rail ,230 Volts SPN with 12 way Double door , IP-43-IK09 protection grade, L&T / schneider/ ABB
S&F MCB DB made of sheet steel, powder painted with bus bar 200 A, neutral link, earth bar and Din rail , 230 Volts SPN with 12 way Double door IP-43-IK09 protection grade
S&F MCB DB made of sheet steel, powder painted with bus bar 200 A, neutral link, earth bar and Din rail , 230 Volts SPN with 8 way Double door IP-43-IK09 protection grade
S&F MCB DB made of sheet steel, powder painted with bus bar 200 A, neutral link, earth bar and Din rail , 230 Volts SPN with 4 way Double door IP-43-IK09 protection grade
S&F MCB SP 63 Amps 'C' series, breaking capacity 10 KA of rating (For Spn 12 Way DB) complete all as specified and directed.
S&F MCB SP 40 Amps 'C' series, breaking capacity 10 KA of rating (For Spn 8 Way DB) complete all as specified and directed.
S&F MCB SP 6-32 Amps 'C' series, breaking capacity 10 KA of rating complete all as specified and directed.
S&F 4 Pole MCCB 63 Amp, 50 Hz, 415 V with rupturing capacity 16 KA cables with suitable connections with suitable size of glands etc complete including testing & commissioning complete all as specified and directed. ( incoming for VTPN DB)
S&F ISI marked RCBO 63 A, 30 mA, 230 V DP for AC applications, conforming to IS 12640 (Part-2)- 2016, having front face indication for earth leakage fault, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters complete all as specified and directed.
S&F ISI marked RCBO 40 A, 30 mA, 230 V DP for AC applications, conforming to IS 12640 (Part-2)- 2016, having front face indication for earth leakage fault, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters complete all as specified and directed.
S&F ISI marked RCBO 32 A, 30 mA, 230 V DP for AC applications, conforming to IS 12640 (Part-2)- 2016, having front face indication for earth leakage fault, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters complete all as specified and directed.
M&L for taking down and dismantling of ceiling fan, segregation of unserviceable parts, cutting and removing out copper winding, cleaning the armature, rewinding of fan armature with appropriate gauge of super enamelled copper wire with necessary insulating materials such as vertex paper, cotton tape, PVC insulation tape etc varnishing with approved grade of insulation varnish and heating up, re-assembling the fan complete with replacement of unserviceable spares parts, (spare parts will be measured & paid separately) including necessary lathe work for fixing of bush/bearing greasing the same with approved grade of grease, making all electrical connection and supply and fixing the following items and including necessary transportion to workshop, for 1200/1400/1500mm sweep fan :- (I) Split pin - 02 Nos (ii) Connection block - 1 No (iii) Insulation rubber bush. - 01 No
M&L for fixing or hanging only ceiling fan after winding fan under item No. 01 above and connecting up including provision of 3 core 1.5 Sqmm cable from ceiling rose or connector to fan( max up to 1m length) complete all as specified and directed.
All as pr item No. 37 here-in-above but exhaust fan of size 225mm to 450mm sweep (except rubber roll, split pin)
Fixing only Exhaust fan after winding fan under item No. 38 above and connecting up including provision of 3 core 1.5 Sqmm cable from ceiling rose or connector to fan( max up to 1m length) complete all as specified and directed.
M&L for overhauling of ceiling fan of any make and sweep after opening and cleaning rotor bearing and stator properly and oiling/greasing of bearing/ bushes, reassmbling the same, fixing and coonecting on its existing position and testing on completion all as specified and as directed including taking down. Note- (A) Overhauling of ceiling fans will be carried under supervision of AGE E/M. (B) The spares required shall be measured and paid separately in the relevant items.
M&L for taking down exhaust fan, of any size and type & cleaning/servicing and overhauling the same, refixing the same on its existing position and connection up complete all as specified and directed.
Supply, fixing and connecting up flexible copper wire twin core of 23/.0078 complete all as specified and directed.
Supply only gun metal bush of any size complete all as specified and directed.
Supply only bearing for ceiling fan complete all as specified and directed
Supply only fan condensor 2.5 MFD complete all as specified and directed.
Supply only fan condensor 4 MFD complete all as specified and directed.
Supply only split pin complete all as specified and directed.
S&F canopy of ceiling fan bottom and upper side of size 1200/1400/1500mm. (Set of two)
M&L for painting of ceiling fan 1200/1400 mm sweep complete including fan blade down rod with synthetic enamelled paint of white tint including cleaning and removing dust and dirt and making smooth surface for painting including writing MES No complete all as specified.
S&F GI tubing light grade 15 mm dia use as down rod of ceiling fan ,cut to required length & incl. drilling of hole at both side complete all as specified and directed.
S&F in repairs mild steel work in framed work such as Fan hooks, Clamps, gratings, ladders etc., with ends of bars welded and/ or riveted, or forged and similar work confirming to Fe 410 - O or Fe 310 - O and incl painting to surfaces using two coats of metallic primer and a coat of synthetic enamelled paint of desired colour complete all as specified and directed.
S&F heating element 3000 watt trangular type make of Bajaj / Tosiba / Havells complete all as specified and directed.
S&F heating element 3000 watt circular type make of Bajaj / Tosiba / Havells complete all as specified and directed.
S&F heating element 2000 watt make of Bajaj / Tosiba / Havells complete all as specified and directed.
S&F hetting element 2000 watt for solar system make of Bajaj / Tosiba / Havells complete all as specified and directed.
S&F themostate for geyser Make : Bajaj / Tosiba / Havells complete all as specified and directed.
S&F neone lamp for geyser yellow / red Make :- L&T complete all as specified and directed.
S&F anchor bolts 75mm long made out of stain less steel complete all as specified and directed
Repair of UG cable and switchgear M&L for excavation in trenches for laying of cables, poles and stay not exceeding 1.5 mtr wide and not exceeding 1.50 mtr deep and getting out.in soft rock complete all as specified and directed.
All as per item no 59 above but depth exceeding 1.5 mtr and not exceeding 3.00 mtr deep and getting out.
M&L for returning & filling in, including spreading and leveling, watering and well ramming in layers n.exc. 25cm complete all as specified and directed
M&L for removing excavated materials not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed
M&L for plain cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation of poles etc complete all as specified and directed.
M&L for plain cement concrete 1:3:6 type C-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete for stays ,foundation and platform for transformer installation complete all as specified and directed.
M&L for plain cement concrete 1:3:6 type C-2 using 20 mm graded stone aggregate for coapping of pole complete all as specified and directed.
M&L for taking up of under ground HT Cable of any size along with protection cover/ bricks and removing from site complete all as specified and directed.
M&L XLPE insulated screned PVC beded galvanised steel strip or wire armoured earthed electric power cable (heavy duty) with aluminium conductor 11/6.35 KV grade suitable for earthed system cross sectional area 95 sqmm 3 core H.T.U.G cable laid in tranches/through GI pipe/fixed along with pole complete all as specified & directed Note -Excavation and earth work shell be measured and paid for separately under relevant item of schedule.
M&L XLPE insulated screned PVC beded galvanised steel strip or wire armoured earthed electric power cable (heavy duty) with aluminium couductor 11/6.35 KV grade suitable for earthed system cross sectional area 120 sqmm 3 core H.T.U.G cable laid in tranches/through GI pipe/fixed along with pole complete all as specified & directed Note -Excavation and earth work shell be measured and paid for separately under relevant item of schedule.
M&L for taking down of faulty HT under ground cable of size upto 120 sqmm from trenches /pole/wall etc for detecting fault including repair and jointing at site including relaying at the same location complete all as specified and directed.Note- Excavation /earth work and cable jointing &jointing kit shall be measured and paid for separately under relevent item of schedule.
M&L for unwashed Sand cushioning to under ground cable provided with a layer of 8 cm deep before laying and 15 cm covering above the top edge of cable after laying complete all as specified and directed.Note : maesurement shall be done after puning down of sand.
M&L for unreinforced precast concrete cable cover class HVP type -I of size 300mmx180mmx40mm complete all as specified and directed
M&L for relaying dismantled HT cable cover covering with width equal to length of bricks as mechanical protection to cable complete all as specified and as directed.
M&L for steel tubing GI light grade for cable protection passing under road /floor or for fixing to poles all as specified and as directed of size 80 mm dia Make - ITC / JINDAL /ZENITH/TATA/ PRAKASH SURYA
M&L for steel tubing GI light grade for cable protection passing under road /floor or for fixing to poles all as specified and as directed of size 100 mm dia Make - ITC / JINDAL /ZENITH/TATA/ PRAKASH SURYA
M&L for RCC hume pipe for Road crossing of cables class NP-2 of size 100mm dia complete all as specified and directed
M&L for cutting of hardstanding/ Road for laying of pipe line/cable and making good surfaces after laing of pipe line/ cable up tp 30cm in depth complete all as specified and directed.
S&F cable end termination suitable for XLPE ,HT under ground cable,95/120 sqmm,3 core,11000 volt ,heat shrink type indoor end termination complete all as specified and directed.
Supply and fix cable end termination suitable for XLPE ,HT under ground cable,95/120 sqmm,3 core,11000 volt ,heat shrink type out door end termination complete all as specified and directed.
S&F cable straight through suitable for XLPE ,HT under ground cable,95/120 sqmm,3 core,11000 volt ,heat shrink type complete all as specified and directed.
M&L for serving of water capacity 0.25 Lakh/ltr disinfection equipment using silver ionization process complete with replacement of spare part such as silver electrodes, indication switches and one coat of over the surface of cabinet base. The qoted rate includes all minor parts to functioning of the plant
M&L for un-reinforce precast cable cover class I LV of size 250mm x 150mm x 40mm complete all as specified and directed.
M&L for relaying of un reinforced precast cable cover class LV of size 250mm x 150mm x 40mm complete all as directed.
S & F pin type insulator 11000 Volts grade 150mm height, 150mm dia all as specified and directed by Engr-in-Charge., porcelain White, Brown or Green including one GI spindle, two GI washer, one GI nut complete all as specified and directed.
S & F HT disc insulator porcelain vitreous 45mm height, 255mm dia, ball and socket type. White / brown with M.S. galvanized iron fitting suitable for working pressure 11KV all as complete all as specified and directed.
Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.
Dismantling of U/S existing cross arms by means made from channels, angles, U/S FI clamps, nuts, bolts etc. from OH line and removing complete all as specified and directed.
M&L cross arms ,bracings,supports,clamps and back plate fabricated from structural steel sections including nuts ,bolts, in any shape or size as indicated or directed and inclusive of two coat of aluminium paint over a coat of red oxide complete all as specified and directed.
All as per item No.86 above but using old existing cross arms received against item No.87 above including cleaning, removing stain and painting of two coats of aluminum paints over a coat of Red oxide (primer) complete all as specified and directed.
Dismantling of Air Break Gang Operated switch vertical/Horizontal mounted HT 33/11 KV incluidng insulator and operating Mechanism for repair/ replacement of broken/worn out components and insulators etc. complete all as specified and directed.
M&L Switch air break gang operated triple pole mechanically operated mounted on insulator and steel frame out door type suitable for vertical installation single brake provided with locking arrangement, consisting of MS channel ,HT post type insulator ,copper alloy high pressure assembly ,operating rod of 25 mm dia GI pipe medium grade confirming to IS-1818 of 1972 ,suitable for 11000 volt ,200 Amps lcomplete all as specified and directed. (Set of three)
Dismantling of existing U/S HT/LT pole of any size & type from its position carefully and removing from the site and necessary excavation and earth work in any soil/strata, demolation of concrete, disconnection of conductor fom pole etc. complete all as specified and directed.
M&L steel, tubular swaged poles complete with cast iron base plate, nuts and taper plug , bolts, nuts and screws type 410-SP- 31 (9.0 m long) complete all as specified and directed.
All as per item No.93 above but HT pole type 410-SP-55 (11mtr long)
M&L for earthing complete with galvanized steel earth plate electrode 600mm x600 mm x 6mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to galvanized earth 32 x 6mm GI strip by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt,Earthing lead 32x6 up to 7.5m, 20mm dia medium grade GI watering pipe, PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-1991 (part-I) NOTE-: GI earth strip beyond 7.5 m & GI protection pipe shall be measured and paid for separately under relevant item of schedule .
M&L for earthing complete with copper earth plate electrode 600mm x600 mm x 3.15mm buried directly in ground vertically to a depth not less then 2.25 meter below normal ground level with top edge of the plate not less then 1.50 meter below normal ground level connected to copper strip 20X3 mm lead by means of bolts ,nuts ,check nuts and washers complete up to and including test point made out of 40 x 6mm alum flat including earthing pit , charcoal common salt ,copper strip 20 X 3mm lead up to 7.5m, 20mm dia medium grade GI watering pipe ,G.I. protection pipe 15 mm dia up to 7.5m long, 40mm GI pipe from earth electrode to ground level and PPC pit in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate ,PCC pit cover including earth work complete all as shown in electrical plate No-5 of SSR-2014 (part-I)
S&F galvanized earth strip 32 mm x 6 mm for earthing from earth plate to equipment complete all as specified and as directed.
S&F copper earth strip 20 mm x 3 mm for earthing from earth plate to equipment complete fixed on pocelain insulator every 1 meter interval all as specified and as directed.
Preparation for surface of existing steel poles including cross arms, nuts, bolts, for painting HT pole 9 mtr long above ground level and applying one coat of approved quality of aluminum paint complete all as specified and directed.
All as per item no 99 above but for 7.5 mtr long above ground level steel tubular LT pole
M&L for preparation for surface of existing two pole structure made out of steel poles including cross arms, nuts, bolts, for painting HT pole 9 mtr long above ground level and applying one coat of approved quality of aluminum paint complete all as specified and directed.
M&L Anticlimbing device ,spikes type fabricated out of ms bars(round,square and flat )including nuts,bolts,washers,and welding in two halves made to shape to suit cross section of the pole and painting with two coats of aluminium paint over a coat of primer complete all as specified and directed.
Supply & Lay Graged stone coarse Aggragated of not less then 40 mm nominal size complete all as specified & directed.
M&L for removing of old existing U/S / deffective lighting arrestor HT 33/11 KV and shifting from the site complete all as specified and directed. (Set of three)
M&L Lightning arrester non linear Metal Oxide type complete with all fittings distribution Sation class discharge capacity 10 kilo amp, current rating 5 kA suitable for 11000 volt complete with all fittings. (Set of three)
M&L for taking down old jumper connection of 2 pole structure from line/AB/DO & refixing complete with new conductor,including line tap,lugs & PVC alkadin/pipe sleeve complete all as specified and directed (ACSR conductor measure & paid seperately) Note - Jumper on cut point /2 pole structure/4 pole structure shell be provided with PVC insulated sleeves. Rates are inclusive of jumper and tree branch cutting to make safe distance from pole /OH line.
M&L for dehydration of tranformer oil, obtained from DISTRIBUTION TRANSFORMER , 11/0.433 KV etc. Dielctric strength shall not be less than 40 KV in 2.5 mm gap electrode after dehydration. Dehydration of transformer shall be carried out by using electrically operated dehydration machine including replacement of unserviceable silica gel and toping up/ replacement of unserviceable transformer oil complete all as specified and directed. (NOTE :-- Transformer oil & silica jel shall be measured and paid against respective item)
Supply & filling transformer oil of approved quality ISI marked for filling in transformer for topping up/ Replacement in 33 KV/11KV Transformer complete all as specified and directed NOTE: (I) Dielectric strength of transformer oil sall not less then 60 KA with 2.5 mm gap (lI) New Transformer oil filled to Transformer after Filtration only Rate for filteration deem include in the rate. (III)Oil to the dept for filling in a sealed barral only.
M& L for disconnecting carefully electrical connection from HT/LT sides of the transformer keeping them at safe side and taking out the transformer indoor type 315/250/200 KVA,11 / .433KV step down/step up any make carrying out complete overhauling which shall complete of the following :- (a) M & L for lifting transporting handling,the transformer to workshop and opening top cover of the transformer by unscrewing nuts, bolts,washers etc including disconnecting core assy from HT/LT bushing and lifting the same gently and taking out from the shell (container/body) of the transformer complete all as specified and directed. (b) M&L for draining out transformer oil from the above said transformer in the suitable capacity of container/drums and keeping it in safe custody for reuse complete all as specified and directed. (c) M&L for cleaning of the transformer body from inside, removing deposited dirt/sludge/foreign particles etc from the bottom/body of the transformer and drying/heating up the shell from inside before refilling of the transformer oil complete all as specified and directed. (d) Cleaning/washing through core and windings of the tansformer by hosing down with clean dry oil conforming IS 335/983,removing deposited dirt sludge/foreign particles from the windings/core and revarnishing of the windings with super varnish including heating/drying/packing complete carefully and throughly inside the heating chamber at suitable temperature to obtained required value of insulation resistance etc all as per IS complete all as specified and directed. (e) Lifting and refixing core assy inside the transformer shell gently and carefully,connecting of HT/LT/Neutral connections to the bushings assy,fixing of the tap change over incl tightenting of nut,bolts,washers of the core to reduce humming noisecomplete all as specified and directed. (f) Refilling the transformer oil in the shall of transformer only after carrying out filteration by heating upto oil 105 degree certigrade to active reqd dielectric strength and submitting the test result before and after filteration of oil in presence of Engr-In-Charge on proper performa duly signed complete all as specified and directed. (g) Refixing the top cover incl replacement of corck sheet/gasket ,tightenting of nut bolt,washers etc complete all as specified and directed. (h) Lifting/shifting to the place from where removed and reinstalling the transformer including connecting HT/LT/Neutral/Earthing connections etc complete all as specified and directed. Note:- (i) Any damage to insulator/bushes/windings etc while in the custody of the contractor shall be made good at no extra cost to govt.The serviceability of the transformer shall be checked and confirmed by the contractor before taking into his custody. (ii) The job taken for repair/overhauling should be complete with in 48 hours from the date of handing over the individual transformer,failing which necessary arrangement to be made by the contractor at no extra cost. (iii) Rewinding / re-insulation of winding of HT/LT coil will be paid seperately under relavant item of sch.
M&L for & rewinding of HT coil with copper material of same gauge & same material of exsisting coil with similar class of exsisting insulation complete all as specified and directed.
M&L for removing the LT coil from core carefully & re-insulation of LT coil with same class of insulation complete all as specified and directed.
S&F HT pocelain bushing with brass studs complete with oil seal, gaskets, ring washer at site/workshop etc for the following sizes of transformers including tacking out existing bushings, drain out transformer oil etc and REFILLING THE SAME. for 160 to 300KVA complete all as specified and directed.
S & F brass stud 16/20 mm dia of suitable length for HT/LT transformer terminal with BRASS nut and bolts and washers 8 noscomplete with oil seal, gaskets, ring washer etc for the following sizes of transformers including tacking out existing bushings and REFILLING THE SAME complete all as specified and directed
M&L for painting of DISTRIBUTION transformer indoor/out door type with smoke gray colour synthetic enamel paint one coat over the existing paint after cleaning and removing the dust and durt and cleaning with sand paper complete including writting SM Nos and MES No on transformer body with letters 100 mm heigh with white synthetic enamelled paint complete for transformer of capacity up to 315/250/200 KVA complete all as specified and directed.
S&F breather of transformer of various capacities filled with silicagel including taking out of unserviceable silacagel complete all as specified and directed.
M&L for taking of old silica Gel for dehydrating Breather of T/F cleaning the breather internally and externally and filling new silica gel blue colour in dehydrating breather.
M&L for taking down partly unserviceable / unserviceable ,SECURITY/STREET/GATE/FLOOD light fittings from pole/tower for necessary repair and make serviceable as per complaints given by dept through job card / complaint register on day to day basis & complete all as specified and directed.
S&F LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
S&F Area lighting LED JETA NEO 120 Watts, energy saving environmental friendly, long life exclusive innovatiive die cast aluminium IP 65 flood light with high power LED as light source suitable for high lighting architectural features or retail spaces complete all as specified and directed. Make : Havells Cat Part No LHEPCZU71461150
S&F post of lantern fitting made out of black ABS plastic spigot & spun alluminium funnel shaped with clear acraylic cover suitable for 26w led lamp fitting including lampcomplete all as specified and directed. bajaj cat no 112364 or wipro / philips/pyrotech
S&F power contactor , 3 pole rating not less than 32 A with 230 coil complete all as specified and directed.
S&F astro time switch, Multifunctional time swithces cat no 004767 of legrand or equivalent of L & T/MDS/GIC complete all as specified and directed.
M&L for taking down unservisable U/G cable from trenches, wall, floor etc and removing to store for safe custody upto 25 sqmm complete all as specified and directed. Note:- Excavation for taking will not paid for separatly, the cable shall be deemed to have taken down from the trenches excaveted for laying of cables
M&L for taking down unservisable U/G cable from trenches, wall, floor etc and removing to store for safe custody above 35 upto 120 sqmm complete all as specified and directed. Note:- Excavation for taking will not paid for separatly, the cable shall be deemed to have taken down from the trenches excaveted for laying of cables
M&L for taking down unservisable LT U/G cable from trenches, wall, floor etc and removing to store for safe custody above 150 to 400 sqmm complete all as specified and directed. Note:- Excavation for takeing will not paid for separatly, the cable shall be deemed to have taken down from the trenches excaveted for laying of cables
S& F XLPE insulated armoured and pvc sheated heavy duty electric cable with aluminium conductor 1100 volt grade laid in tranches passing through pipes /ducts including testing complete of following cross sectional area and size complete all as specified and directed. Note- rate is inclusive of cable gland & cable lugs. (a) 2 core, 4 sqmm cross sectional area
(b) 2 core, 6 sqmm cross sectional area
(c) 2 core, 10 sqmm cross sectional area
(f) 4 core, 10 sqmm cross sectional area
(h) 4 core, 25 sqmm cross section area
(i) 3-1/2 core, 35 sqmm cross section area
(j) 3 -1/2 core, 50 sqmm cross sectional area
(l) 3 -1/2 core, 70 sqmm cross sectional area
(m) 3 -1/2 core, 95 sqmm cross sectional area
(n) 3 -1/2 core, 120 sqmm cross sectional area
(o) 3 -1/2 core, 150 sqmm cross sectional area
S& F XLPE insulated armoured and pvc sheated heavy duty electric cable with aluminium conductor 1100 volt grade laid in tranches passing through pipes /ducts including testing complete of following cross sectional area and size Note- rate is inclusive of cable gland & cable lugs. (a) single core, 400 sqmm cross sectional area
(b) single core, 300 sqmm cross sectional area
(c) single core, 240 sqmm cross sectional area
M&L for taking down of faulty LT under ground cable of size upto 3.5x25sqmm from trenches /pole/wall etc for detecting fault including repair and jointing at site including relaying at the same location complete all as specified and directed. Note- Excavation /earth work and cable jointing &jointing kit shall be measured and paid for separately under relevent item of schedule.
M&L for taking down of faulty LT under ground cable of size above 3.5x25sqmm up to150 sqmm from trenches /pole/wall etc for detecting fault including repair and jointing at site including relaying at the same location complete all as specified and directed. Note- Excavation /earth work and cable jointing &jointing kit shall be measured and paid for separately under relevent item of schedule.
S&F MCCB 400 A 35 KA,4 POLE complete all as specified and directed. ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM94105OOR1OG /Legrand cat no-025538/schneider cat no-LV540309
S&F MCCB 250 A 35 KA, 4 POLE complete all as specified and directed. ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM92109OOP1OG /Legrand cat no-420249/schneider cat no-LV525343
S&F MCCB 200 A 35 KA,4 POLE complete all as specified and directed.,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM92109OON1OG /Legrand cat no-420248/schneider cat no-LV525342
S&F MCCB 160 A 35 KA, 4 POLE complete all as specified and directed.,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM92109OOM1OG /Legrand cat no-420247/schneider cat no-LV516343
S&F MCCB 125 A 25 KA,4 POLE complete all as specified and directed. ,thermal magnetic relese, Ics=100% Icu & L&T cat no- CM92108OOL1OG /Legrand cat no-420056/schneider cat no-LV516312
S&F MCCB 63 A 25 KA,4 POLE complete all as specified and directed. ,thermal magnetic relese, Ics=100% Icu & L&T cat no- SL98603OOOO /Legrand cat no-420013/schneider cat no-LV510315
S&F MCCB 40 A 25 KA,4 POLE complete all as specified and directed.,thermal magnetic relese, Ics=100% Icu & L&T cat no- SL98602OOOO /Legrand cat no-420013/schneider cat no-LV510316
S&F enclosure SUITABLE FOR MCCB TP complete all as specified and directed L&T CAT NO-ST2997OOOO LEGRAND/ABB/L&T
S&F ON LOAD change over switch 4 pole 320 amps with sheet metal enclosure, make -L&T /schneider/ABB/Legrand
S&F ON LOAD change over switch 4 pole 200 amps with sheet metal enclosure, make -L&T /schneider/ABB/Legrand
S&F ON LOAD change over switch 4 pole 125 amps with sheet metal enclosure make -L&T /schneider/ABB/Legrand
M&L for taking down change over switch & MCCB with enclosure any type & any size complete all as specified and directed.
M&L for disconnecting & taking down all connection of LT pannel board/FPB , incomming & outgoing LT cable, including internal wiring & internal connection & addition / alteration /repair to exsisting pannel/FPB by cutting/welding/drilling/granding & replace all internal connection by XLPE insulated single core multistranded alluminium conductor cable of suitable size for outgoing MCCB/MCB/CUTOUT including alluminium lugs & connecting all incomming & outgoing cables with alluminium heavy duty lugs & testing after repair complete all as specified and directed.
M&L for painting of LT pannel board/ LT feeder piller box, indoor/out door type any size/capacitywith smoke gray colour synthetic enamel paint one coat over the existing paint after cleaning and removing the dust and durt and cleaning with sand paper complete including writting letters 100 mm heigh with white synthetic enamelled paint complete all as specified and as directed.
S&F writting letters with radium stickers size & shape complete all as specified and directed.
M&L for taking out of centrifugal pump set 10 HP from pump foundation after disconnection from motor and transportation to workshop , dismantling the pump for repair/ overhauling incluiding cleaning of all parts of pump assembly throughly, including machine work of pump shaft inorder to obtain smooth finish including necessary polishing etc and installing back including helium gasket sheet not less then 1mm thick & to the entire satisfaction of engr-in -charge all as specified and directed. Note:- Spares as required shall be measure & paid seperately against the relevant items.
(a) S&F Casing Wear Ring-
(b) S&F shaft sleeve-
(c) S&F Inter Stage Ring-
(d ) S&F Ball bearing SKF
(e) S&F Bearing cartridge DE
(f) S&F Bearing cartridge NDE
(g) S&F shaft sleeve Nuts
(h) S&F Split Gland
(a) M&L for taking out of centrifugal pump set 3 HP from pump foundation after disconnection from motor and transportation to workshop , dismantling the pump for repair/ overhauling incluiding cleaning of all parts of pump assembly throughly, including machine work of pump shaft inorder to obtain smooth finish including necessary polishing etc and installing back including helium gasket sheet not less then 1mm thick & to the entire satisfaction of engr-in -charge all as specified and directed. Make -Crompten/Kirloskar/JYOTI, Note:- Spares as required shall be measure & paid seperately against the relevant items.
(a) supply & fix Casing Wear Ring-
(b) supply & fix shaft sleeve-
(c) supply & fix Inter Stage Ring-
(d ) supply & fix Ball bearing SKF
(e) supply & fix Bearing cartridge DE
(f) supply & fix Bearing cartridge NDE
(g) supply & fix shaft sleeve Nuts
(h) supply & fix Split Gland
M&L for disconnecting electrically and disengaging the AC Squirrel cage induction motor 3 phase 415 Vlots, 50 Cycles, and taking out to local workshop induction motor 10/3 HP for repair purpose including complete cleaning,varnishing ,insulation and greasing and including shifting back to location as directed, installing, testing and commissioning after repair complete all as specified and directed. Note- Rewinding will be measure & paid seperately under relavant item of sch.
M&L for rewinding the motor with super enamelled copper winding wire with appropriate same gauge of exsisting coil with similar class of exsisting insulation as recommended by manufacturer with high quality normex insulating paper applying best quality insulating varnish on stator/rotor windings drying them completely, testing the insulations complete all as specified and directed.
M&L for taking down unserviceable existing pressure Gauge and Supply & fix pressure Gauge dial type 0 to 14 kg/cm square complete all as specified and directed.
M&L for taking down unservicable existing motor starter of any size/capacity complete all as specified and directed.
S&F fully Automatic Star-Delta, Motor starter 10 HP in sheet-steel enclosure type MN .feature (Motor Rating AC-3 Duty, 415V, 50Hz, 3-Ph) and Relay Range 8-12 .(Make : L&T or Equivalent OF SIEMENS)
S&F fully Automatic DOL Motor starter 3 HP in sheet-steel enclosure type MN .feature (Motor Rating AC-3 Duty, 415V, 50Hz, 3-Ph) and Relay Range 4-6 .(Make : L&T or Equivalent OF SIEMENS)
M&L for spare coil for power contactor amp of make L&T/crompten/schinder/bhartiya cuttler including Taking Down
S&F thermal over load relay for type ML-1 complete all as specified and as directed.
M&L for painting of motor and pump with smoke gray colour synthetic enamel paint one coat over the existing paint after cleaning and removing the dust and durt and cleaning with sand paper complete including writting letters 100 mm height with white synthetic enamelled paint complete all as specified and as directed.
M&L for painting of pipe line with synthetic enamel paint one coat over the existing paint after cleaning and removing the dust and durt and cleaning with sand paper complete including writting letters 100 mm height with white synthetic enamelled paint complete all as specified and as directed.
M&L draining water from Ground level reservoir of 20000 Lits cap, and cleaning internal portion of tank (bottom and walls) by means coir / wire brush etc. and wash the internal portion of tanks by using bleaching powder @ 25 grams per 1000 Ltrs of water after removing sludge and mud etc to a distance not exc 50 mtr including one coat of synthetic enamel paint on all steel surfaces such as ladder, railing, inlet & over flow CI pipes connected sluice valves of the respective OH tanks/ground level reservoir etc writing letters with white paint (date of cleaning and capcity of tank) on black painted surface of tanks complete all as specified and directed.
M&L for cutting existing galvanised iron pipe in position for insertion of new pipe/tees, branches etc. (a) 15 mm dia
(b) 20 mm dia
(c) 25 mm dia
(d) 40 mm dia
(e) 50 mm dia
S&F Brass/gunmetal foot valve sring loaded, flanged/screwed end and drilled of size 80 mm dia ISI MARKED complete all as specified and directed.
S&F Brass/gunmetal foot valve sring loaded, flanged/screwed end and drilled of size 50 mm dia ISI MARKED complete all as specified and directed.
M&L for breaking down /removing of damage valve chamber and other brick/ pcc work of any size and pattern with foundation concrete including removing of demolition materials to a distance not exceeding 50 mtr and depositing complete all as specified and directed.
M&L for construction of brick masonry valve chamber of size 900x 900x1200 mm (internal dia) suitable for 150 mm dia sluice valve with necessary earth work excavation plain cement concrete 1:4:8 using 40 mm graded stone aggregate 75 mm thick in cement mortar 1:6 15 mm thick plastering 1:6 inter nally including flooring and externally rep to 15 mm below ground level plain cement concrete 1:4:8 type B1 using 20 mm graded stone aggregate in coping MS sheet cover made out of 3 mm thick MS sheet flat iron frame and bracing with locking arrangement applying two coat of synthetic enamel paint including dismantling removing the existing damage chamber completely removal of debris to a distance not exce eding 50 mtr distance depositing complete all as specified and directed.
M&L for taking up or down GI Tubing and connections including cleaning for refixing or removal to store - of size :- (a) 15 mm dia
(b) 20 mm dia
(c) 25 mm dia
(d) 40 mm dia
(e) 50 mm dia
(g) 80 mm dia
(h) 100mm dia
S&F GI tubing medium grade with all fittings and fixed complete laid in trenches of size :- (a) 20 mm
M&L for removing Unserviceable Gate valve/stop valve of water supply lines, closing the opening with plug or preparing for new as required necessary fitting complete and deposited to E/M store yard of size :- (a) 20 mm dia
(b) 25 mm dia
(c) 40 mm dia
(d) 50 mm dia
S&F gun metal Globe or Gate valve with iron wheel head, screwed both ends for iron pipe and fixed with required necessary GI fittings complete of size :- (a) 20 mm dia
(b) 25 mm dia
(c) 40 mm dia
(d) 50 mm dia
M&L for cutting existing cast iron pipe in position for insertion of new pipe/tees, branches etc. (a) 150 mm dia
(b) 100 mm dia
M&L for taking up cast iron water mains including flanged rubber joints with spigot and socket ends and lead joint burning out and recovering lead of size :- (a) 150 mm dia
(b) 100 mm dia
(c) 80 mm dia
Supply and laying cast iron pipes with spigot and socket ends centrifugally cast, Class LA, in any length laid in trenches of size (a) 150 mm dia
(b) 100 mm dia
(c) 80 mm dia
M&L for run lead joints complete for water mains with spigot & socket pipes and fittings, all as specified and directed. Bore of pipe :- (a) 150 mm dia
(b) 100 mm dia
(c) 80 mm dia
Supply & fix rubber tyton joint of following size : (a) 150 mm dia
(b) 100 mm dia
(c) 80 mm dia
Supply & fix rubber gasket joint for flange end of following size : (a) 150 mm dia
(b) 100 mm dia
(c) 80 mm dia
Supply & fix machanical joint ISI marked for spigot end pipe of following size : (a) 150 mm
M&L spigot/flanged/ socketed CI fittings. Such as bends (any type radius and angle), tapers, tees, collars & tail piece socket/flanged/spigot etc of size 200mm to 300mm dia complete all as specified and directed.
M&L for dismantling/taking out unserviceable sluice valve of size 80mm to 300mm bore dia by opening/cutting rusted nuts, bolts etc complete all as specified and directed.
S&F CI sluice Kirloskar/Upadhyay/L&T MAKE valve both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.6 ISI marked complete all as specified and directed of sizes :- 80 mm dia
S&F CI sluice Kirloskar/Upadhyay/L&T MAKE valve both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.6 ISI marked complete all as specified and directed of sizes :- 100 mm dia
S&F CI sluice Kirloskar/Upadhyay/L&T MAKE valve both ends flanged and drilled, bonnet wedge stuffing box. Gland trust plate, hand wheel made out of grey CI, complete valve confirming to IS 14846/2000 and its fittings suitable for hydraulic test pressure of 15 Kg/sqcm PN 1.6 ISI marked complete all as specified and directed of sizes :- 150 mm dia
M&L for removing unservieable bib taps 15/20mm dia from pipe line/tanks for replacing New and deposited to E/M store yard all as directed - of size :-
S&F bib tap cast copper alloywith crutch/buterfly handle screwed for iron pipe and fixed of size 15 mm dia complete all as specified and directed.
S&F bib tap high prssure of PTMT with epoxy coated screwed for iron pipe and fixed of size 15 mm dia complete all as specified and directed.
M&L for taking down old u/s indicator & Supply & fix New Digital water leval indicator system 150 mm size digit direct display,operated on 230v Ac, sutable for up to 20 meter height over head Reservior/underground sump of any capacity,preajustable alaram for upper & lower level,temp range -5 to 50 degree,humidity up to 90% RH,reset push switch for silent the alarm including 4 core 1.5 sqmm copper cable ,including
M&L for comprehensive maintenance of DG set including routing / preventive maintenance checks at least once in a month, checking up of engine and alternator for trouble free functioning and attending break downs/ complaints as and when required complete all as specified and directed. The type of work / maintenance services to be carried out during comprehensive maintenance are as under :- for 82.5 KVA DG SET a) Checking of Engine Oil level. b) Checking of oil bath cleaner oil level. c) Drain sediments from fuel tank. d) Checking of pre- cleaner dust pan. e) Checking of air cleaner restriction. f) Checking of coolant level. g) Record Oil pressure.. h) Checking /tightenig of all bolts / nuts of engine and alternator. i) Checking of Engine Oil level. j) Checking of AVM pads. k) Checking of diaphragm coupling.. l) Checking of tappet clearance. m) Clean fuel tank breather . n) Clean crank case breather . o) Checking of Air piping. p) Cleaning of oil bath Air cleaner Tray screen. q) Check / adjust Belts. r) Checking battery voltage, water level and apply jelly on terminals. s) Checking fan hub / air blower hub and water pump. t) Cleaning turbo charger. u) Tighten manifold Nuts of cops screws. v) Cleaning of electrical connections with CTC solution. w) Checking of safety contols x) Cleaning of cooling system / radiator assembly. y) Cleaning of Engine and radiator assy. Note : - for item no 57 (1)The comprehensive maintenance includes carrying out preventive maintenance Excluding replacing all the unserviceable / worn out spares to keep the DG set for trouble free functioning. (2) The rate quoted deemed to be included all the minor spares such as screws, clips washers , distilled water, electrolite etc and other spares will be measured and paid separately under supply only items. (3) Engine Oil will be issued under schedule B .
S&F set of fuel pre- filters and fine -filters as per sample and make for the following capacities of DG sets. Each set shall be comprising complete set of pre/fine filters for 82.5 KVA DG complete all as specified and directed.
S&F set of lube / engine oil filters / catridges as per sample and make for the following capacities of DG sets. Each set shall be comprising complete set of pre/fine filters for 82.5 KVA DG complete all as specified and directed.
S&F battery lead with stranded copper conductor of size 95 /70sqmm single core PVC insulated, flexible complete all as specified and directed.
S&F battery terminals of copper complete all as specified and directed.
S&F fuel pipe (rubber pipe ) upto 15 mm size from fuel tank to the DG set & over flow return fFor 82.5 KVA DG complete all as specified and directed.
S&F water outlet and inlet hose pipe from radiator to Engine and back Engine to radiator for 82.5 KVA DG complete all as specified and directed. (Set of two)
S&F lub oil pipe for 82.5 KVA DG complete all as specified and directed.
S&F maintenance free power pack unit 12 Volt,dimension-355X175X235 MM suitable for generating set 30 KVA to 125 KVA complete all as specified and directed CAT NO-XCL/12/3200 MODEL X-CELL OF make HBL POWER SYSTEM LIMIED
S&F in repairing the self starter of Mico make after removing from the Gen set of capacity 110/75/63 KVA and transporting to an authorised sevice centre complete all as specified and directed including replacement of the following U/S parts:-
a ) Armature . Qty : 1 No
b) Bendex of suitable size : 1 No
c) Bearing / bushes : 1 set
d) Relay switch of suitable size : 1 No
S&F in repairing the Dynamo/alternator of Mico make after removing from the Gen set of capacity 82.5 KVA and transporting to an authorised sevice centre complete all as specified and directed including replacement of the following U/S parts:-
a) Armature of suitable size : 1 No
b) Bearings / bushes of suitable size : 1 Set
c) Voltage rgulator of suitable size : 1 set
M&L for drain the out lived engine oil, clean the oil sumpand filling the engine oil complete all as specified and directed.
S&F V- belt for fan
Supply & fill engine oil, in sumpand filling the engine oil all as directed.
Supply and lay 3- layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain & brass threaded polypropylene random fittings laid in trenches/wall/ceiling/floor including fitting etc complete for the following sizes ;- (a) 50 mm outer dia
(b) 40 mm outer dia
(c) 25 mm outer dia
Supplying and laying 75 mm inner dia of CPVC Schedule 80 pipes & CPVC Schedule 80 Brass treaded fittings in trenches complete all as specified and directed.
Supplying and laying 50 mm outer dia of CPVC SDR Schedule 11 pipes & CPVC Schedule SDR 11 Brass treaded fittings in trenches complete all as specified and directed.
Supplying and laying 40 mm outer dia of CPVC SDR Schedule 11 pipes & CPVC Schedule SDR 11 Brass treaded fittings in trenche scomplete all as specified and directed.
Supplying and laying 25 mm outer dia of CPVC SDR Schedule 11 pipes & CPVC Schedule SDR 11 Brass treaded fittings in trenche scomplete all as specified and directed.
Repair of cooling appliances S&F in repairs to Rrefrigerator 180/310/320/360/270 Ltr. by taking down unserviceable control accessories/parts, S&F hermetically sealed comp unit suitable for above mentioned capacity refrigerator with one year guarantee, fixing & assembling in refrigerator & gas charging with R-134 a gas as per pressure & quantity recommended by the company, testing for good cooling & smooth functioning to the satisfaction of Engr-in-Charge etc complete all as specified and directed.
S&F open type relay suitable for refrigerator mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F thermostatic switch defrost type including plastic regulating knob suitable for refrigerator mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F set of copper strainer and capillary tube 0.036"x8' maximum suitable for refrigerator mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F bulb 15 watt 230 V threaded suitable for refrigerator mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F overload protector with relay suitable for refrigerator mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F starting capacitor, Cap 6 MFD suitable for refrigerator mentioned above including dismantling old unserviceable one complete all as specified and directed.
S&F 3 x 1.5 Sqmm copper flexible, stranded copper conductor PVC insulated cable, 1100 V grade (ISI marked) 5 Amps complete including dismantling old unserviceable one complete all as specified and directed.
All as item No 208 above but cable 2.5 sqmm, 15 Amp suitable for window type AC 1.5 /2 Ton capacity and deep freezers and geyser.
S&F evaporator /cooling coil suitable for Refrigerator mentioned above, fitting & assembling in refrigerator & Gas charging with R-134a gas as per pressure and quantity recommended by the company, testing for good cooling & smooth functioning to the satisfaction of ENGR-IN-CHARGE etc complete as specified and directed.
S&F Set of magnetic door gasket suitable for refrigerator mentioned above including clipping/reveting/screwing for fitting of gasket air tight joint for body & door complete for refrigerator 310 ltrs capacity complete all as specified and directed.
S&F Ice Tray plastic moulded in order to make14 Nos of ice cubes suitable for refrigerators mentioned above including dismantling old unserviceable one complete all as specified and directed.
S&F Vegetable Tray suitable for the Refrigerator mentioned above including dismantling old unserviceable one complete all as specified and directed.
S&F Chillar Tray suitable for the Refrigerator mentioned above all including dismantling old unserviceable one complete all as specified and directed.
S&F frosted glass 4 mm thick for vegitable tray suitable for refrigerator mentioned above including dismantling old unserviceable one complete all as specified and directed.
S&F door switch for refrigerator mentioned above including dismantling old unserviceable one complete all as specified and directed.
S&F Inner shelf suitable for refrigerator mentioned above including dismantling old unserviceable one complete all as specified and directed.
S&F in repairs to deep freezer of capacity 265/300/320/360 Ltr/Hr by taking down unserviceable control accessories/parts and S&F New hermetically sealed compressor unit suitable for above mentioned capacity deep freezer with one year guarantee, fixing & assembling in deep freezer complete with welding /brazing and gas charging with R-134 gas as per the pressure and quantity directed, testing for good cooling and smooth functioning to the satisfaction of Engineer-in-Charge etc complete all as specified and directed.
S&F starting capacitor, Cap 80-100 Mfd suitable for deep freezer mentioned above including dismantling old unserviceable one all complete all as specified and directed.
S&F over load protector with relay suitable for deep freezer mentioned above complete including dismantling old unserviceable one all as complete all as specified and directed.
S&F thermostat switch suitable for deep freezer mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F relay open type suitable for deep freezer mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F capillary tube 0.044"x8' maximum and silica drier type strainer suitable for deep freezer mentioned above, complete all including dismantling old unserviceable one complete all as specified and directed.
S&F fan motor of condenser 230 volts 8 watts to 10 watts suitable for deep freezer mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
All as item No 224 above but fan motor of condensor 1/3 HP suitable for 1.5 Ton air conditioners.
All as item No 224 above but fan motor of condensor of water cooler capacity 1/3 HP or 1/5 HP.
S&F in repairs to Air Conditioner 1.5/2 Ton Cap (Make-Voltas/Usha/Blue Star/Videocon/LG) by taking down unserviceavle control accessories/parts, S&F hermetically sealed compressor unitsuitable for above mentioned capacity of Split type AC with one year guarantee, fixing & assembling in air conditioner with welding/brazing and gas charging R 134 Gas as per the pressure and quantity recommened by the manufacturer, testing for good cooling and smoothing functioning to the satisfaction of Engineer-in-Charge complete all as specified and directed.
S&F Relay suitable for Air Conditioner mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F starting capacitor 80-100 Mfd working voltage 230 volts, 50 Hz, AC Surg 275 Volts RNQ suitable for air conditioner mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F running capacitor 36 Mfd, working voltage 230 volts, 50 Hz, type SMRC suitable for air conditioner mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F Thermostat Switch with regulator knob suitable for Air conditioner mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F over load protector type DC 1622 surg voltage 275 volts RNQ suitable for window type AC (1.5 Ton/2 Ton Capacity) including dismantling old unserviceable one complete all as specified and directed.
S&F return air filter made of PVC suitable for split type AC of any make and any type including dismantling old unserviceable one complete all as specified and directed.
S&F in repairs to water cooler capacity 60/120 ltr/Hr, 80/120 Ltrs/ HR & 150 Ltrs/HR by taking down unserviceable control accessories/Parts. S&F hermetically sealed comp unit suitable for above mentioned capacitt water cooler with one year guarantee, fixing & assembling in water cooler complete with welding/ brazing and Gas charging with R-134 A Gas as per the pressure and quantity recommended by the manufacture and testing or good cooling and smooth functioning to the satisfaction of Engineer-in-Charge etc complete all as specified and directed.
S&F set of Capillary tube 8' maximum and pencil drier type strainer suitable for water Cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F relay suitable for water cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F running capacitor 36/15 Mfd 230 volts AC 50 Hz suitable for water cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F starting capacitor 60-40 Mfd, 10-20 Mfd 230 volts, 50 Hz suitable for water cooler mentioned above, complete all including dismantling old unserviceable one as specified and directed
S&F over load protector suitable for water cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F thermostat Switch with plastic regulating knob suitable for water cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F spring loaded self closing water tap (push type) 15mm bore dia, Internal/External threaded, brass chromium plated suitable for drinking water cooler mentioned above complete including dismantling old unserviceable one complete all as specified and directed.
S&F float valve 15 mm bore dia size complete with PVC ball, brass chromium plated rod suitable for water cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F 3-pin top 6A 240 volts including dismantling old unserviceable one complete all as specified and directed.
S&F 3 pin top 16 Amps, 240 volts including dismantling old unserviceable one complete all as specified and directed.
S&F aluminium fan blade for blower motor for water cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F wiring set complete consisting of PVC insulated cable wiring stranded copper conductor conneting clips etc suitable for water cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F PVC flexible connection pipe high density 32 mm dia including jublee clamps outlet connection for drain water suitable for water cooler mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
S&F PVC connection pipe, type 15 mm dia 450 mm long complete with PVC union at both end suitable for water coolers mentioned above, complete including dismantling old unserviceable one complete all as specified and directed.
Supply and charging of Refrigerant Gas R 134/R22 after checking,detecting, rectifying leakages of Split Type AC's/Water cooler/Deep Freezer/Refrigerator one all as specified and directed and testing after gas charging.
M&L for servicing of Refrigerator of capacity 180/310/320/360/270 Ltr. by taking down all serviceable control accessories/parts and refixng the same & testing for good cooling & smooth functioning to the satisfaction of Engr-in-Charge etc complete all as specified and directed.
M&L for servicing of complete Deep freezer of capacity 265/300/320/360 Ltr/Hr (Make : Blue Star & Voltas) by taking down all serviceable control accessories/parts and refixng the same &, testing for good cooling and smooth functioning to the satisfaction of Engineer-in-Charge etc complete all as specified and directed.
M&L for servicing of water cooler capacity 60/120 ltr/Hr, 80/120 Ltrs/ HR & 150 Ltrs/HR by taking down all serviceable control accessories/Parts. and refixng the same and testing or good cooling and smooth functioning to the satisfaction of Engineer-in-Charge etc complete all as specified and directed.
M&L for servicing of Air Conditioner 1.5/2 Ton Cap by taking down al serviceable control accessories/parts, and refixng the same &, testing for good cooling and smoothing functioning complete all as specified and directed.
SHRIKALP ENGINEERS AND CONTRACTORS
FRIENDS N FRIENDS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .