| 3 | Not Admitted-Fee/PreQual/Technical NEW MADHO NAGAR SAHARANPUR SAHARANPUR UTTAR PRADESH 247001 | SAHARANPUR | UTTAR PRADESH | 247001 | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹3,000
Closing Date
6 Dec 2021, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE, ECWD, SRE
EE, ECWD, SRE
The Works of Increasing Capacity of 33/11 KV SubStation JAIN BAGH (Distt. Saharanpur)
2021_PVVNL_643914_2
ST-17/ECWD/SRE/2021-22
Open Tender
Electrical Works
Lump-sum
90 days
SAHARANPUR
PLEASE REFER TENDER DOCUMENTS
2 documents required · 2 mandatory
₹1,180
EE, ECWD, SAHARANPUR
₹3,000
Yes
13 Dec 2021
26 Nov 2021
6 Dec 2021
26 Nov 2021
6 Dec 2021
30 Nov 2021
26 Nov 2021 - 26 Nov 2021
90 days
Amount
Post Insulator Structure:- Post Insulators structure and Plinth for the same as per drawing No. RES-39 details:- a) Excavation of earth (0.45x0.45x1.0)m for 02 Nos. Pits of above structures.
b) Fabrication of P.I.'s, structure by using M.S. Channel (100x50) mm size and 3.5 m minimum height with 2 Nos. M.S. Angle (65x65x6)mm size on top of structure for installation P.I.'s.
c) C.C. work of ratio 1:3:6 (cement, coarse sand and 20 mm size stone Ballast) for the above plinths for structure of P.I.'s structure 02 Nos. after ramming of earth of size (0.3x0.3x1.0)m. Over stone pad of size 300x300x75mm
d) 12mm thick plaster with cement mortar ratio 1:4 (cement & fine sand) of plinth of 0.4m upper side.
e) Supply & fixing of stone pad of size 300x300x75mm
Renovation of Transformer Plinth a) Providing and making RCC work on top of plinth in Ratio 1 : 2 : 4 (3.46×3.46)mtr size of 0.10 Mtr in thickness. The work also include proper ramming of surface.
b) Grouting of 02 Nos. 90/105 lb. Rail pieces of 3.46 M long and (50×50×6)mm M.S. Angle in R.C.C. work at the top of plinth work also includes cutting of rail and angle pieces etc.
c) 12 mm thick plaster with cement mortar ratio 1:4 (cement & fine sand) of plinth of 0.5 M above ground level.
d) Neat cement Coating of 3 mm thick on top surface of Plinth of Transformer.
Earthing of outdoor equipment, details as given below:- a) Cutting of 32mm.dia M.S. Bar-3Mtr.long and making one end in conical shape by forging process and driving it into the earth at each corner of bridge outside control room and proper welding with M.S.Bars.
b) Digging of Pits for making delta by laying 32mm. dia M.S.Round in tringle shape. Electric welding on cross joints by providing “U” Clamp in size 25x6mm. of M.S.Flat, with over lap joint by providing M.S.Round-12mm dia, on both sides of over lap joints of M.S.Round, by electric welding. All joints shall be painted with black bituminious paint.
c) Making earthing of 33KV LA, Neutral link structure, Power T/F body (both side) by providing G.I.Strip in size 50x6mm. with 32mm. dia M.S.Round laid in trench with proper electric welding.
d) Making proper earthing of other structure such as, 33KV VCB, CT's, L.A, P.I, Cable support structure, Bus isolator by laying G.I.Strip size (50x6)mm for connecting the earth mat. The work also includes digging of earth, cutting, bending, tening, over laping and welding the earth strip with earth mat by using high quality are welding and paints of joints with black bituminous paint in already digged trenches.
e) Painting of G.I.Earth Strip of size (50x6) mm with two coats of ISI mark synthetic channel green paint.
f) Supply of G.I. Strip size 50x60mm for earthing of outdoor & indoor equipment
Painting of Structures Painting of the following structure with one coat of ready mixed primer and two coats of ISI Mark Aluminium paint after rubbing with sand paper to the surface of the structure including labour and T&P complete in all respect. a) Bus Isolator, Post Insulator, Fuse Set and L.A's & CT/PT unit.
b) Cable support structure and Neutral support structure, M.S.Frames.
Installation of switch yard structures : a) Fabrication and erection of cable support made of two pieces of M.S. Channel (100x50x6)mm, 2.75 meter long, joined to each other by means of 5 Nos. M.S. Angle (50x50x6) mm pieces of size 0.5Mtr long each by welding at equal intervals and grouting in a block of size (300x300x700)mm in C.C. 1:3:6 complete with one coat of ready mixed primer and two coats of Al. paint. Work includes providing of three Nos. M.S. clamps made of (50x6)mm M.S. Flat for holding the cable including nuts and bolts with stone Pad of size (300x300x75mm).
b) Fabrication and erection of neutral earthing L Type support made of M.S. Channel size 100x50mm. Structure shall be 4 Mtr. long with 1 Mtr. Arms. Structure shall be grouted in ratio 1:3:6 in block size 300x300x700mm and painted with one coat of Ready Mixed primer and Two coat of enamel Aluminium paint work includes connecting neutral bushing rod of power Transformer and M.S. Earthing strip with the help of flexible copper bond, M.S. Bolt and washer with stone Pad of size
c) Fabrication and grouting of M.S. frames 3.60 mt. long for support of copper Bus Bar. Bus Bar will be provided in L.V. side of Power transformer. The M.S. frame shall be made of M.S. channel (100x50)mm in 'T' shape. Providing 2 Nos. support of M.S. Angle iron (50x50x6)mm, 0.60mt. long below the top channel, drilling of 3 Nos. hole on the top channel for fixing of 11 KV pin insulator. The M.S. frame shall be painted with one coat of primer & two coat of aluminium paint and grouting the frame in C.C. ratio 1:3:6 in a block of size (300x300x700) mm with stone Pad of size (300x300x75mm). The work also includes the fixing of 3 Nos. 11 KV pin insulator with pin and binding the copper Bus Bar with the pin insulator by Aluminium binding wire in complete.
d) Supply & Fabrication of copper bus bar of size (2500x50x6)mm in L.V. side of 5 MVA 33/11 KV, power transformer, Work includes connection of outside bus bar in L.V. side busing rod of Power Transformer and other side with outdoor 11 KV cable box as well as providing empire tape and H.T. tape etc. for proper insulation work. Including providing PVC colour tape to identify each phase.
Removal of 33/11 KV, 5 MVA Transformer : a) Disconnecting 33 KV side and 11 KV side connection of 5 MVA Transformer.
b) Draining of oil from conservator, radiators of existing 5 MVA T/F, at 33/11 KV S/S JAIN BAGH (Distt. Saharanpur) into the dry & clean drums and staking at the safe place at 33/11 KV S/S JAIN BAGH (Distt. Saharanpur). Empity oil drums will be arranged by contractor it self.
c) Opening of conservator radiators and other accessories from existing 5 MVA Transformer.
d) Shifting of 5 MVA Transformer main body and other accessories from the substation switchyard to outside of switchyard at safe place.
Installation of 33/11 KV, 10 MVA Transformer : a) Dragging/lifting of 33/11 KV 10 MVA Transformer on plinth from the unloaded place.
b) Erection of 33/11 KV 10 MVA Transformer on plinth, by fixing all accessories, like Radiators, Conservator Tank, Filling the Transformer Oil to desired level and ensuring that there is no leakage, complete job in all respect. Empty oil drums will be arranged by contractor it self.
c) Connecting of 33 KV side and 11 KV side connection of Installed 10 MVA Transformer.
H.T. Power Cable Laying : a) Laying 11 KV, (3×300) mm2/(3×400) mm2 XLPE, Cable from power transformer to 11 KV Incoming switch gear in the cable trench 0.45 m wide, 0.90m depth. Providing 150 mm local sand for cushion beneath and 150 mm above the cable (quantity of local sand required 0.375 cubm/m in length). Making of Chulla for safely laying of cable at incoming switchgear end. The cable shall be duly protected by brick. On both side of cable by laying brick vertically and bricks would also be laid horizontally on top of vertically laid bricks along the cable (minimum 18 Nos. of bricks are to be laid top and outer side along the cable. The work includes digging of trenches, laying of cable in under ground trenches, joining of terminal's, back filling of earth and testing and commissioning of power cable etc. Spare cable shall be left over and laid in the trenches in shape of 6m ring at both ends.
b) Laying and dressing of 11 KV 3×300 mm2/3×400 mm2 power cable in air/Trench.
Preparation of 11 KV Power Cable ends : a) Making of 11 KV XLPE Heat shrinkable out door jointing kits after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs.
b) Making of 11 KV XLPE heat shrinkable indoor jointing kits in switch gears after carefully removing the insulation of cable, providing and crimping of proper size of lugs, plumbing and taping of cable with good quality available insulation tape with J/Kit boxes. Fixing and insulating of lugs on cable with switch gear complete in all respect.
Installation of 33 KV Post Insulators: Installation of 3 Nos. PI on structure. The work includes fabrication for proper fixing, if required.
Providing & fixing of following 33 KV connecting clamps duly casted made of aluminium alloy complete with G.I. Nut, bolts, washers and spring washers suitable for ACSR Dog Conductor a) 33 KV Transformers Clamps
b) 33 KV Post Isolator Clamps
To provide required No. of technicians with proper testing equipments to work on power T/f, HT/LT panels during testing as assisting technical hands of test team during commissioning & energisation.
Loading, Safe carriage & unloading of following stock material from any stores centres under PVVNL, depending upon the availability of material at Stores Centres, with loading & unloading at both ends respectively. A) Steel, 3.5Mtr long Rail Pieces, Angle channel, M.S.Round etc.
b) 11 KV Cable 3×300mm²
c) 11KV cable J/kit 3x400mm² / 3x300mm²
d) 33KV Post insulator
M/S KUMAR TRADERS KAKA NAGAR
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .