| Sl No | Description | Qty | Unit | M/S GLOBUS POWER SYSTEMS L1 | TECHFORCE ENGINEERS L2 |
|---|---|---|---|---|---|
| 0.00EQUIPMENTS: | |||||
| 1.00Variable Refrigerant Volume / Flow Air-conditioning System (Heating & Cooling both) | |||||
| 1.01Supply, installation, testing and commissioning of Variable Refrigerant Flow modular type air-conditioning system suitable for Cooling & Heating both by multiple scroll compressor controlled by individual inverter complete with indoor and outdoor units with individual wired and wireless/wired remote controller for indoor units and centralized controller, interconnecting refrigerant piping, full charge of refrigerant gas (R-410A) & oil, internal control cabling and fittings etc. as per details given in specifications and having following items. The out door units shall be suitable for 3 phase 4 wire system, 415V + 10 %, 50 Hz AC supply and indoor shall be suitable for Three phase 415 V + 5%, 50 Hz AC supply Make: Daikin, O-General, Mitsubishi Heavy, Mitsubishi Electric, Hitachi, TOSHIBA & Carrier | |||||
| 1.02Outdoor Units | |||||
| 1.03Supply, installation, testing & commissioning of Modular type outdoor units equipped with highly efficient scroll /DC Twin Rotary type of compressors fully inverter controlled i.e. changes its speed in accordance to the variation in cooling loads, special heat exchanger, low noise condenser fan, & including full charging of R-410A refrigerant gas complete i/c powder coating complete as per specifications. Out door units shall be provided with MS stand of suitable size duly painted with corision resistant paint suitable for outdoor application. | |||||
| 1.04The units shall be in combination of one or more units which shall be selected in such a way that COP of each unit at 100 % shall not be less than 3.35 and 75% part load shall not be less than 3.90 on standard operating conditions i.e on 35 Deg C DB Ambient and at 27 Deg CDB & 19 Deg CWB inside conditions. The units shall be suitable to operate upto 52 Deg C ambient conditions. | |||||
| 1.05All the units shall be provided with built-in microprocessor control panel, for automatic operation and capacity control,which should be air cool.Machines shall be suitable for working with BMS system. | |||||
| 1.06It is mandatory that each compressor shall have inverter technology separately i.e. outdoor units shall have all inverter based compressor. | |||||
| 1.07Following capacities of ODUs are at standard operating condition as defined above and Vendor to indicate COP at 100% load & at part loads i.e. 75% & 50% in the data sheets/ shop drawings: | |||||
| 1.08 | 24 HP ODU Heat Pump Type. | 6 | No. | - | - |
Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
12 Oct 2020, 6:00 pmClosed
Executive Engineer
Office of Executive Engineer JKPHC Jammu
Construction of 100 bedded additional emergency with attendant waiting hall in Govt Medical College Jammu Providing and Installation of HVAC Contract No 17
2020_DGPJK_105768_1
Fresh e-NIT No 17 of PHC JAMMU DIV2020-21 2nd Call
Open Tender
Miscellaneous Works
Item Rate
120 days
Jammu
refer PQ terms and conditions
2 documents required · 2 mandatory
₹3,000
Executive Engineer JKPHC
₹2.6 L
Office of Executive Engineer JKPHC Jammu
31 Oct 2020
29 Sept 2020
13 Oct 2020
29 Sept 2020
12 Oct 2020
5 Oct 2020
29 Sept 2020 - 3 Oct 2020
5 Oct 2020
Amount
EQUIPMENTS:
Variable Refrigerant Volume / Flow Air-conditioning System (Heating & Cooling both)
Supply, installation, testing and commissioning of Variable Refrigerant Flow modular type air-conditioning system suitable for Cooling & Heating both by multiple scroll compressor controlled by individual inverter complete with indoor and outdoor units with individual wired and wireless/wired remote controller for indoor units and centralized controller, interconnecting refrigerant piping, full charge of refrigerant gas (R-410A) & oil, internal control cabling and fittings etc. as per details given in specifications and having following items. The out door units shall be suitable for 3 phase 4 wire system, 415V + 10 %, 50 Hz AC supply and indoor shall be suitable for Three phase 415 V + 5%, 50 Hz AC supply Make: Daikin, O-General, Mitsubishi Heavy, Mitsubishi Electric, Hitachi, TOSHIBA & Carrier
Outdoor Units
Supply, installation, testing & commissioning of Modular type outdoor units equipped with highly efficient scroll /DC Twin Rotary type of compressors fully inverter controlled i.e. changes its speed in accordance to the variation in cooling loads, special heat exchanger, low noise condenser fan, & including full charging of R-410A refrigerant gas complete i/c powder coating complete as per specifications. Out door units shall be provided with MS stand of suitable size duly painted with corision resistant paint suitable for outdoor application.
All the units shall be provided with built-in microprocessor control panel, for automatic operation and capacity control,which should be air cool.Machines shall be suitable for working with BMS system.
It is mandatory that each compressor shall have inverter technology separately i.e. outdoor units shall have all inverter based compressor.
Following capacities of ODUs are at standard operating condition as defined above and Vendor to indicate COP at 100% load & at part loads i.e. 75% & 50% in the data sheets/ shop drawings:
24 HP ODU Heat Pump Type.
16 HP ODU Heat Pump Type.
AIR HANDLING UNIT
Supply, installation, testing and commissioning of factory fabricated Double Skinned Floor Mounted DX TYPE Air- handling unit with mixing box having thermal break profile, fabricated out of extruded aluminium section with 0.6mm pre-coated Galvanised steel sheet outside & 0.6 mm plain Galvanised steel sheet inside with blower, blower section and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Minimum 4 Row cooling coil UV lamp. Coil should be made of Aluminium finned Copper tube with coil section, pre-filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90%, & fine filter of 5 micron particle size with an efficiency of 99%. polished stainless steel drain pan made out of 20 G sheet duly insulated complete with motor, direct / belt drive as mentioned below etc. The AHU panels shall be insulated with 43mm thick & 38 Kg/m³ density PU foam. The motor & blower assembly shall be mounted on Aluminium extruded section only. Damper shall be provided in the AHU at supply air , return air & fresh air. Apprroved MAKE:- Zeco / Edgetech .
Capcity:- 15000 CFM /30.5Tr/ 90 mm s.p.
Capcity:- 12800 CFM /29.5Tr/ 90 mm s.p.
Supply, Installation, Testing and Comissioning of Y Joint / ODU piping KIT
Supply, Installation, Testing and Comissioning of AHU KIT for following AHU
Capcity:- 15000 CFM /30.5Tr/ 90 mm s.p.
Capcity:- 12800 CFM /29.5Tr/ 90 mm s.p.
Supply, Installation, Testing and Comissioning of Corded remote controls
Heat Exchanger-HRV Unit
Supply, Installation, Testing and commissioning of HRV unit with out coil for Heat echange operation with Adjustable Air volume upto three steps with Low Noise level. Make Hitachi, Daikin,Mitsubishi, O-General, ZECO,EDGTECH or Equiv.
REFRIGERANT PIPING:-
Supply, Installation, Testing and Commissioning of Interconnecting refrigerant pipe work with (19mm/13mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoorunits as per specifications.
54 mm O.D.(insulation : 19 mm)
50.4 mm O.D.(insulation : 19 mm)
44.5 mm O.D.(insulation : 19 mm)
41.3 mm O.D.(insulation : 19 mm)
38.1 mm O.D.(insulation : 19 mm)
34.9 mm O.D.(insulation : 19 mm)
28.6 mm O.D.(insulation : 19 mm)
25.4 mm O.D.(insulation : 19 mm)
22.2 mm O.D.(insulation : 19 mm)
19.1 mm O.D.(insulation : 19 mm)
15.9 mm O.D.(insulation : 13 mm)
12.7 mm O.D.(insulation : 13 mm)
9.5 mm O.D.(insulation : 13 mm)
6.4 mm O.D.(insulation : 13 mm)
Supply and filling of GAS R-410A
DUCTING WORK
Supply, Installation Testing & Commissioning of G.S.S. ducting , 120 GSM complete in all respect along with silicon sealant. Duct Sheet make :- As per Engineer Incharge.
24 Gauge
22 Gauge
20 Gauge
18 Gauge
INSULATION WORK
Supply & Application of 09/12mm MM Thickness. XPE TOC Slim insulation Cross Linked polyethylene foam with aluminium metalized foil for insulation on Supply duct running inside Building area and with UV Foils for insulation for supply Ducts running outside building area i.e. exposed to atmosphere
19 MM thckness for Exposed duct ( supply & return )
12 MM thickness for Supply Air
9 MM thickness for Return Air
Duct Acoustic Lining
Providing and fixing of Duct acoustic lining of glass wool insulation as per the following detail, covered with perforated aluminium 26G sheet, nuts, bolts etc.complete with all accessory as required.
25 mm thick and 32 Kg density
Grilles/Diffusers / Dampers / canvas connection
Supply, installation, testing and balancing of powder coated extruded aluminium Grilles without volume control damper in accordance with As per Engineer Incharge.
Supply, installation, testing and balancing of powder coated extruded aluminium construction ceiling diffusers with removable core & anti smudge ring, without volume control dampers As per Engineer Incharge..
Supply, installation, testing and balancing of galvanised steel construction Volume Control dampers within ducts to be provided with suitable ducts lever and quadrants for manual control of volume of air flow and for proper balancing of the air distribution system. As per Engineer Incharge.
Providing & fixing of fire resistance flexible double canvas connection Make CARYAIRE or equivalent
Supply, installation, testing and balancing of Aluminium costruction collar dampers for grilles & diffusers As per Engineer Incharge.
Supply, installation, testing and balancing of Fusible Link Fire Damper with acthutar As per Engineer Incharge.
ELECTRICAL
CONTROL PANELS FOR AHU ( AIR HANDLING UNIT )
Supply Installation testing & commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing etc.
All wiring and copper earthing of motors from the panel shall be included.
The panel shall include the following components & accessories.
MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 25 KA.
DOL / SD starter as per HP ratings given.
Terminal block for power distribution as required.
Contactor, over load relay with built in single phasing protection.
Phase indicating lights and indicating light for `ON/OFF’ status.
Time delay relay for delayed automatic restart of motor.
Wiring for microswitch for stopping the fan when fire damper closes (in case of Fan only).
For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation.
All starters shall be provided with suitable potential free contract for connections to the Building Automation System.
The number of control panels shall be as follows.
DOL Starter upto 10 HP
POWER CABLE
Supply, installation and testing of following 1100 volt grade PVC insulated PVC sheathed copper conductor armoured cable on cable trays / existing trenches. The cost of termination, glands, lugs & thimble etc. shall be included in the cost of cable for completing the work as per site requirements.
Power Cable ( 4C X 25 Sq.mm)
Power Cable ( 4C X 10 Sq.mm)
Power Cable ( 4C X 6 Sq.mm)
Power Cable ( 3C X 4 Sq.mm)
Flexible Power Cable ( 3C X 2.5 Sq.mm)
Weather Proof Isolators for outdoor Units
Providing & Fixing of Isolater of suitable ratings near the outdoor for power isolation as required.
Weather proof box with MCCB of 100A ratings near the outdoor units for isolation
Weather proof box with MCB of 63A ratings near the outdoor units of Capacity for isolation
DRAIN WORK
SUPPLY & INSTALLATION OF HEAVY cPVC DRAIN PIPE WITH 9 MM THICK INSULATION
40 mm pipe for AHU drain
50 mm pipe for AHU drain
SUPPLY & INSTALLATION OF DRAIN TRAP
CABLE TRAY
SUPPLY & INSTALLATION OF CABLE TRAY WITH NECESSARY SUPPORTS REFRIGERENT PIPING
200 mm wide
300 mm wide
450 mm wide
600 mm wide
EARTHING
Providing and fixing the earthing with proper connections of following sizes.
GI STRIP 50X5
GI STRIP 25X3
MS WORK
MS channels, angles, flats and square/rectangular hollow tubes of max size 50 x 50 mm.
TECHFORCE ENGINEERS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.55 MB
BOQ_201863.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .