Executive Engineer, MH Division Srinagar
Executive Engineer, MH Division Srinagar
Design, Supply, Installation, Testing and Commissioning of Automatic Fire alarm and Fire detection system at Forensic Science Laboratory Bemina, Srinagar
2023_PWDJK_228254_1
MHDS/TS /2023-24/83/e-tendering dated31-08-2023
Open Tender
Machineries/ Mechanical Engg Items
Item Wise
45 days
Forensic Science Lab Bemina
As detailed in NIT
6 documents required · 6 mandatory
₹2,000
Executive Engineer MHD SGR
₹68,000
Office of Executive Engineer, MH Division Srinagar
21 Oct 2023
31 Aug 2023
16 Sept 2023
31 Aug 2023
16 Sept 2023
1 Sept 2023
1 Sept 2023 - 7 Sept 2023
1 Sept 2023
Amount
FIRE ALARM SYSTEM
Design, Supply, intallation, testing and Commissioning of the following system as per the technical specification.
Microprocessor based Intelligent Addressable Main Fire Alarm Control Panel should be compatable for CPU redundancy with suitable Loops modules and each loop capable of supporting not less than 240 devices (detectors & modules should be in any combination); Loop length up to 1.5 km, 7" Color LCD touch screen display with bright colors to indicate alarms and events, 4 Nos of Integrated Ethernet Ports & 2 Nos of RS 485 for networking, 200 Nos of Soft programmable keys with status indicators for individual triggering of NAC Ouputs, evacuation speaker zones. The Panel shall support 10000 history logs in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 24 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The Panel is inclusive of Network Card (fault tolerent)
2 Loop Panel
Addressable multisensor smoke detector including mounting base with LED etc complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values. Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m.
Addressable analogue type Heat Detectors with combination of fixed type and rate of rise of temperature feature. Detetctor should have inbuilt isolators as per NFPA 72 style 7 wiring requirements and have an option of both soft & hard addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values.
Response indicator for mounting on false ceiling at the entries of the cabin for indicating the operation for detectors in the above areas including Backbox
Active Repeater panel 7" LCD touch screen display with bright colors to indicate alarms and events to be connected peer to peer with Main Fire Alarm panel. Accept, Reset functions shall be possible from the repeater panel. The user interface of Repeater Panel shall be identical to the Fire alarm Panel. All other specification shall remain unchanged like FACP.
Addessable Manual call point unit with inbuilt isolators as per NFPA 72 style 7 wiring requirements, with flexible network structures & necessary fixing arrangements with key complete as required.
2C 1.5 sq mm armoured FRLS Fire Retardant copper cables in celing with suitable clamps and screws
15 mm dia PVC conduit for laying of fire cable including necessary accessories like bend, junction box fixing of clamps etc., complete. The channel shall be recessed in wall including chipping, roup plastering etc.
Operation of the Fire Alarm and Detection system for a period of One year by way of engagement of 1 Operator for working hours
Software for integration of Fire alarm system with Fire monitoring system by way of graphical interface for displaying and monitoring small and medium fire alarm
Desktop Computer having following Hardware details • Processor: Core i5 • RAM: Minimum 8 GB • Free Disk Space: Minimum 1 GB • Gigabit Network card • Monitor resolution: Minimum 1366x768 pixel • The hardware must be dedicated specifically to the use of the software. Software preconditions Server (operating system) • Microsoft Windows 10/11 Professional (64 bit) • Microsoft Windows 10/11 Enterprise (64 bit) Microsoft Windows Server 2019 Server (database server) • Microsoft SQL Server 2014 Express (included) • Microsoft SQL Server 2014 Standard • Microsoft SQL Server 2016 Standard • Microsoft SQL Server 2017 Standard Client (operating system) • Microsoft Windows 10/11 Professional (64 bit) • Microsoft Windows 10/11 Enterprise (64 bit) Graphic card preconditions • GPU Intel 530/Nvidia Quadro P400 • Direct3D 9 compatible • Graphic card driver installed (latest available version) • Directx Runtime installed
Royale Meridian (India) Private Limited
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .