| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.6 LAccepted-AOC | ₹9.6 L | L1 | Accepted-AOC LOWEST |
| 2 | L2₹11.1 L+₹1.5 L (15.9%)Rejected-Finance BOOTH NO 56 MAIN MARKET SECTOR 40 C CHANDIGARH U T 160036 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160036 | ₹11.1 L+₹1.5 L (15.9%) | L2 | Rejected-Finance NOT LOWEST |
| 3 | L3₹11.7 L+₹2.1 L (21.9%)Rejected-Finance | ₹11.7 L+₹2.1 L (21.9%) | L3 | Rejected-Finance NOT LOWEST |
| 4 | L4₹11.8 L+₹2.2 L (23.0%)Rejected-Finance 852 EKTA VIHAR 1 C NEAR ANAND NAGAR 9 B PATIALA 147001 | PATIALA | PATIALA | PUNJAB | 147001 | ₹11.8 L+₹2.2 L (23.0%) | L4 | Rejected-Finance NOT LOWEST |
| 5 | L5₹11.8 L+₹2.2 L (23.0%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹11.8 L+₹2.2 L (23.0%) | L5 | Rejected-Finance NOT LOWEST |
Tender Value
₹12.7 L
EMD Value
₹25,480
Closing Date
10 Aug 2020, 6:00 pmClosed
CWE Patiala
HQ CWE BLDG NO 26 NEW LAL BAGH PATIALA - 147 001
SUPPLY INSTALLATION AND COMMISION OF ROOF TOP 15 KWP SOLAR PANELLED POWER PLANT IN BLDG NO P-17 UNDER GE NORTH PATIALA
2020_MES_344781_2
8320/PAT/T-11/E8
Open Tender
Coal Works
Item Rate
120 days
Patiala
As per cover 1
6 documents required · 6 mandatory
₹500
Yes
GE North Patiala
₹25,480
Yes
14 Sept 2020
24 Jul 2020
12 Aug 2020
24 Jul 2020
10 Aug 2020
5 Aug 2020
24 Jul 2020 - 31 Jul 2020
Amount
Design, procure, erect install, test and commission including connecting to local utility grid; Grid connected solar photovoitaic plant of 15 KW capacity (roof top) including solar photovoitaic Module, DC cabling, Module Mounting Structures, Combining Boxes, Lightning Protection of SPV modules and other accessories, string inverter, consisting of following main componenets: - Poly Crystaline Silicon Solar Photovolaic minimum of 315Wp, not less than 15KW capacity, having efficiency 16.28% min under standard conditions, form fill factor more than 0.74, plant performance ratio > 75% , made of high transmitivity glass front surface and it shall give high encapsulation gain ( transmittance above 90% and bending less than 0.3%). The electrical parameters of SPV modules under standard test condition of irradiance 1000 W/sqm2, AM 1.5 Spectrum and temp 25 degree Celsius shall be as under Max Peak Power Pmax > 315W Voltage at Max Power :>38.81V Current at Pmax: >8.12 A Short Circuit Current : > 8.84 A Open Circuit Voltage: >45.94 Module Efficiency: > 16.28% . (a) Rated outputof the modules shall have positive tolerance of 3-5% and no negative tolerance is allowed. (b) It shall perform satisfactority in RH 85% with temperature up to +85 degree C and should withstand wind of 150 kmph on the surface of panel. (c) PV modules shall be warrented for their output peak watt capacity, and it shall not fall of its initial value below 90% in first 10 year end and 80% after the end of 25 years.
(d) Each module shall have RFID tag encapsulated with solar cell bearing following details: Name of manufacture of SPV Module, Name of Manufacturer of solar cell and module) country of Origin ( both cell and module) Peak wattage, Im, Vm and fill factor of the module IV curve of module. (e) The temperature coefficient of the module shall not be more than 0.50% degree celcius. (f) PV modules must confirm to latest edition of IEC 61215/ IS 14286. In addition the modules must confirm to IEC 61730 Part I and II for construction and testing & safety qualifications and confirming to IEC 62804 PID. (g) It shall also be in confirmity to latest minimum technical specification issued by MNRE from time to time. Modules should be of 48 cell configuration and should be of MNRE approved companies/agencies in category/ rating 'SA-1A' . (h) Provision of earting and earth strip/ cable etc for earth of solar Pvmodule/ array etc as per latest IS/MNRE norms to be provided and cost of the same is deemed to be included in the item and no extra amount will be paid to the contractor on this account. (i) Both cell and SPV modules shall be made in India and must conform to DSR norms of MNRE (j) The minimum net annual generation shall be 1500 units per kilowatt. Make: Vikram solar, Waaree, TATA, ADANI, RENEWSYS
(k)DC Cables & AC Cables: Suitable size of XLPE insulated tinned copper cable of solar grade, 1100 volt and UV resistant for putdoor installations confirming to IEC 60227/15694 & 60502/ is 1554 (Pt& I&II) of minium size 6sq.mm All cables and connectors for use of installation shall be of solar grade which can withstand harsh environmental conditions including high temperature, UV radiations, rain, dirt,burial and attack by moss and microbes for 25 years ans voltage as per latest IEC/IS. All the cables/wires shall be provided with UV resistant printed ferrules for DC side .The size of the cable shall be such that average voltage drop at full power from PV module to inverter shall be less than 1.5%. The AC cables along with AC DB with necessary arrangement to Connect with the existing power supply to be done. The size of XLPE LT cable To be got approved by Engineer in charge. Suitable electronic smart meter To be fixed to measure generation of electricity. Cable batch no,drum no, IS code and size and make shall be metioned on every one meter or as per OEM practice .The wiring of the module interconnection shall be in suitable size UPVC/HDPE pipe. The cost of interconnecting DC copper cable, and earth work for trenches suitable to accommodate solar grade cables from SPV module upto inverters are included in the item. Make: Lapp, Havells, Polycab, Leoni, Siechem
(l)Module Mounting Structure: Design, procure, fixing, support structure made of hot dipped galvanisized iron with min 85 micron thickness including necessary PCC foundation and associated work and fixing mounting arrangement suitable for SPV modules so as it can withstand wind speed of 150km per hour. The array mounted structure has to be so designed that it occupies minimum space without sacrificing the output of SPV panels, Nuts, bolts,mounting structure including module mounting structure shall have to be adequately protected from atmosphere and weather prevailing in the area. All the modules fixing fastners shall be of stainless steel of grade SS316.The module mounting structure to be fixed tilt to optimise the maximum generation in a year. MMS design shall be supported with stadpro report and submitted for the approval of the acepting officer. Cost of all equipments, copper strip up to earth test point and earthing etc are included in this item. The cost of sufficient earthing for lightning protection is included in this included in this item and no extra payment will be made to the contractor on this account.
(m)String Inverter: Procure, fixing, testing and commissioning of 15 KW -1 No 50+3 Hz (min) 3 phase 460 volt, THD< 3%, at nominal power inverter suitable to convert DC power of solar PV module/arry/ to AC for further feeding to grid confirming to IEC 61683 for efficiency, IEC 62109 or equivalent for safety and IEC 62093 for reliability. The input DC technical specification of 10 KW inverter are as under: Input (DC) DC V oltage Range: 575-850 V Max DC Voltage:1000 V Nominal Power : 15 kW Max output power : 15 kW Nominal AC current : as per standards Nominal oUTPUT vOLTAGE: 460V Output Frequency : 50/60 Hz Harmonic Distortion current : < 3% Efficiency : 98.3% Standby operation consumption (feed in) : < 20 W
Operating temperature up to 85 degree centigrade . The inverter shall have minimum IP 65 protection, ground fault monitoring, grid monitoring , protection against anti-islanding, DC reverse polarity, AC and DC short circuit current and over current, AC and DC over voltage and temperature . The inverter shall adjust voltage and frequency levels to suit the grid . The inverter shall be selfcommulated with Pulse Width Modulation (PWM) technology and shall be capable of synchronise maximum with in one min. Maximum Power Point Tracker(MPPT) confirming to IEC 62093 shall be integrated in the inverter to maximum the energy drawn from the PV array. The inverter shall be suitable nos of protected inputs (as per design) and outgoing shall be protected by Surge protections (MOVs) .The inverter shall be provided with protection class I (IEC 62103) .The inverter should have MODBUS, PROFIBUS, ETHERNET comn ports .The inverter shall include appropriate self protection and self diagnostic feature to protect itself and the PV array from the damage in the event of the inverter componant failure or from parameters beyond the inverters safe operating due to internal and/or external causes. Inverter shall have protection arrangement against ground leakage faults, over voltage, ( SPD) & over current. Inverter should interfaces with Ethernet, RS485, irradation and temperature sensor, Auxilary equipment and power supply, external stop signal. Should have residual monitoring system. Make: ABB , SMA, Refusol, Fronius, Power One,Kaco,Delta
Supply and fix VERTICAL Water heater storage type, electric,capacity 25 litres BEE 5 star rated complete all as specified and directed by Engineer in charge.
M&L for GI tubing medium grade of 15 mm dia including cutting / chasing into wall for concealed tubing and making goog distuberd suface with cement mortar 1:3 and finishing surface to match with surrounding surface, fixing to existing G I pipe including drilling and tapping, including all necessary fittings such as union,socket, elbow etc, complete all as specified and directed.
M&L for GI tubing medium grade of 25 mm dia including cutting / chasing into wall for concealed tubing and making goog distuberd suface with cement mortar 1:3 and finishing surface to match with surrounding surface, fixing to existing G I pipe including drilling and tapping, including all necessary fittings such as union,socket, elbow etc, complete all as specified and directed.
S&F vitreous china premium/1st quality wall hung wash basin white, flat back, size 500x400 mm including pedestal, screws & plug and brackets etc. all accessories as recommended by manufacturer incl. CP bottle trap 32 mm with inlet and outlet screwed for pipe or connections incl all necessary accessories for fixing, packing, union and incl 32mm brass CP waste coupling and completein all respect as per manufacturer's instructions complete all as specified.
S&F central hole brass chromium plated basin mixer with regular spout with/without popup waste system with 450 mm long braided hoses complete. Make : Jaquar (Continental Series) / Hindware (Contessa Plus Series) / Cera (Ocean Series) / Prayag ( Neptune Series)
S&F overhead shower 120mm dia with 225-230mm long cromium plated 3 ways diverter shower arm with wall flange and incl all necessary accessories as recommended by manufacturer for fixing complete in all respect all as specified. Make : Cera / Hindware / Jaquar.
Material and labour for point wiring with 2.5 Sqmm copper conductor (Multi-stranded) PVC insulated and unsheating FRLS electric cable 1100 volts cable in and including concealed PVC Conduit of suitable size (as per conductor run) with all fittings such as bend/corners/ accessories and including PVC insulated electric cable 1100 volts 1.5 Sqmm ( multi-stranded) copper conductor single core( Green colour) cable as continuous earth wire connected to common earth dolly in CI/PVC box covered with 3 mm thick plastic laminated sheet complete all as specified and as directed by the Engineer-in-Charge. Note : i) Eye/bottle thimbles shall be used for connection in switches/sockets & MCB's in DB's without any extra cost. ii) Electric rewiring should be done in proper colour coding i.e. Red for phase, Black for neutral and Green for Earth, complete all as specified and directed.
M&L for box type, 3 pin, 20 Amp flush type Inbuilt socket with 15A sp MCB nad plug top for electric connection to geysers all as specified and directed.
S&F PVC connections 15mm size with brass nuts at both ends of length 450mm complete all as directed and specified.
S&F CP connection 15 mm size with brass nuts at both ends of length 450 mm of superior quality suitable for hotwater supply and all as specified and directed by Engr-in-Charge.
S&F angle valve, fancy type chromimum plated, screwed down high pressure with screwed both ends for iron pipe or for union of 15 mm dia complete all as specified and directed.
Supply and fix LED security light fitting 70 watt complete with 40 mm gi pipe bracket , ms clamp for fixing on walls
L-7 Primewave Communications
Fisco Energy Private Limited
Arneja Builders
R D Bansal
Abacus Infrastructures Pvt Ltd
STAR POWER DISTRIBUTION PVT LTD
UNITED ENGINEERING CORPORATION
Oorja On Move Infra Pvt Ltd
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .